Guide to the Canadian Electrical Code, Part 1[i] – A Road Map: Section 40 — Electric Cranes and Hoists

August 1, 2025

by William (Bill) Burr[i]

Section 40 — Electric Cranes and Hoists

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook but will hopefully provide some help in navigating the Code. These notes are based on the 25th edition.

Section 40

Rule 40-000 ScopeThis is a supplementary or amendatory section of the code and applies to the installation of electrical equipment and circuits for electric cranes, hoists, and monorails. The CEC Handbook provides additional notes and diagrams to better explain this section.

Rule 40-002 Supply conductor sizesBecause of the short duty of crane and hoist motors, insulated supply conductors are selected from Table 58, which specifically applies to Crane and Hoist installations.

Rule 40-004 Conductor protectionInsulated conductors supplying main contact conductors must be installed in approved protective wiring methods—such as rigid conduit, electrical metallic tubing, or sheathed cables—unless Rule 40-018 provides an exception. If a flexible connection to equipment is required, armoured or unarmoured cable, festoon cable, or flexible cord may be used, provided take-up devices are included to prevent cable damage and keep it clear of the operating area.

Rule 40-006 Overcurrent protectionFor main contact insulated supply conductors or directly supplied equipment, the overcurrent protection must be selected as per Rule 28-200 and Tables 29 and D16 for the motor load, plus any allowance as per Rule 14-104 where conductors have been selected with capacity for the other loads on the crane or hoist.

Rule 40-008 Disconnecting meansAll ungrounded conductorsof the main contact conductors must be capable of being simultaneously disconnected quickly for safety in an emergency and for maintenance. The disconnect must be within sight of the main contact conductors or the equipment. In addition, the disconnect must be accessible and be operable from the ground or floor over which the crane or hoist operates.

Rule 40-010 Main contact conductorsThis rule requires thatwhere there are bare main contact conductors, they must have an ampacity not less than the conductors supplying them and, if wire conductors, shall be not smaller than No. 4 AWG copper, or No. 2AWG aluminum. If the conductors are more than 18 m long, then the minimum size must be No. 2 AWG copper or No. 1/0 AWG aluminum unless intermediate strain relief is provided by clamp type insulating supports. Bare conductors may be hard drawn copper, aluminum wire, or steel or other suitable metal in the form of angles, tees, T-rails, or other rigid shapes.

Rule 40-012 Spacing of main contact conductorsBecause bare main contact conductors depend on free air space to provide insulation between phases and to ground, this rule outlines the minimum support separation required of main contact conductors installed in a horizontal plane of 75mm for monorail hoists and 155 mm for other than monorail hoists. If installed in other than a horizontal plane, the separation of the main contact conductor supports must be 200mm. They should also be supported so that the extreme limit of displacement maintains a separation of 38mm from any surface. Where the bare main contact conductors are rigid, the supports must provide a minimum separation of 25mm between conductors, collectors, and any surface.

Rule 40-014 Supporting of main contact conductorsIn addition to the spacing required in Rule 40-012, the main contact conductors must be stretched between strain insulators at each end and supported throughout the length at 6m intervals.  If building conditions preclude supporting at 6m intervals, it may be increased to a maximum of 12m intervals providing the separation between contact conductors is increased by the same proportion. In the case of rigid main contact conductors, insulated supports must be spaced at intervals of up to 80 times the vertical height of the conductor but not more than 4.5m. Refer to the CEC Handbook for diagrams illustrating support spacing and calculation notes.

Rule 40-016 Joints in rigid contact conductorsThis rule outlines the importance of ensuring that any joints made in rigid main contact conductors must maintain the same ampacity of the conductors over the joint to eliminate any overheating.

Rule 40-018 Use of track as a conductor – This rule permits a single monorail, tramrail or crane runway track to be used as one of the main contact conductors or supply circuit conductors for one phase of a 3-phase circuit, providing it is derived from a single isolating transformer, does not exceed 300 v, is bonded to ground (see Rule 10-1100 to 10-1108), and any joints meet Rule 40-016.

Rule 40-020 Guarding of contact conductorsRequires that all contact conductors be guarded against inadvertent contact with bare current-carrying parts unless incorporated in an enclosed contact assembly. In addition, as long as a minimum clearance of 6 m between bare contact conductors and grade, floor, or any working surface (including a catwalk) is maintained, guarding of bare contact conductors may not be required.

Rule 40-022 Contact conductors not to supply other equipmentThis rule prohibits the contact conductors supplying the crane, hoist or monorail feeding other equipment not essential to the operation of the crane, hoist or monorail.

Rule 40-024 Bonding – As per Rule 10-406 all exposed non-current carrying parts shall be bonded to ground. In addition, in the case of a track or rail used as a conductor, it shall be bonded in accordance with Rule 40-018. Note that metal wheels on metal rails may provide a low impedance grounding path. A flexible supply connection as per Rule 40-004(2) must contain a bonding conductor.

View all of the Guide to the Canadian Electrical Code Installments




[i] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

Related Articles


Latest Articles

  • EHRC Destination Trade Program for Third and Fourth-Year Apprentices

    EHRC Destination Trade Program for Third and Fourth-Year Apprentices

    May 14, 2026 Providing financial incentives of up to $5,000 to employers who create new Work-Integrated Learning (WIL) opportunities for third and fourth-year apprentices. Electricity Human Resources Canada’s (EHRC) Destination Trade program is Canada’s third- or fourth-year apprentice work placement initiative for the electricity industry, providing wage subsidies of up to $5,000 to small to Read More…

  • Record Attendance Marks Strong Return for MEET 2026

    Record Attendance Marks Strong Return for MEET 2026

    May 14, 2026 By Electro Federation Canada The Mechanical Electrical Electronic Technology (MEET) show saw a powerful return to Moncton, NB on May 6-7, setting a new attendance record with 7,532 participants attending the two-day event. The biennial show, now in its 26th edition, is touted as the premier industry trade show in the region Read More…

  • LLM Cybersecurity Is Now a Construction Cybersecurity Problem

    LLM Cybersecurity Is Now a Construction Cybersecurity Problem

    May 14, 2026 By Melvin Newman, PataBid CEO In a previous article, we covered how to write effective AI prompts and the real productivity benefits LLMs (large language models) can bring to construction estimating and operations. If you haven’t read it yet, it’s worth starting there. This article picks up where that one left off, Read More…

  • Smart Planning and Innovation Drive Success in Winnipeg Retrofit

    Smart Planning and Innovation Drive Success in Winnipeg Retrofit

    May 14, 2026 The Darling Ingredients retrofit project recently wrapped in Winnipeg—and it’s already being hailed as a model for future upgrades across the company’s North American facilities. Black & McDonald’s electrical division was tasked with replacing the motor control centres (MCCs) at the rendering plant, a high-stakes environment where downtime simply isn’t an option. Read More…


Changing Scene

  • Luminis Wins Red Dot Award for Ellington

    Luminis Wins Red Dot Award for Ellington

    May 14, 2026 Luminis, an established innovator and manufacturer of specification-grade, interior and exterior lighting solutions, today announced its Ellington and Trilo families have each received a Red Dot Design Award for Product Design. Dating back to 1955, the Red Dot Design Award is one of the world’s largest design competitions. Every year, the Red Read More…

  • Quarter Century Platinum Status for PCL Construction

    Quarter Century Platinum Status for PCL Construction

    May 14, 2026 PCL Construction is proud to announce it has once again been recognized as a Platinum Club member of Canada’s Best Managed Companies, earning the distinction for 2026 and reaffirming its place among the country’s most respected and well-managed private enterprises. The recognition extends PCL’s long-standing record of excellence, marking 25 consecutive years as Read More…

  • Landscape Ontario, Electrical Safety Authority Partner to Promote Electrical Safety in Landscape Trades

    Landscape Ontario, Electrical Safety Authority Partner to Promote Electrical Safety in Landscape Trades

    May 14, 2026 Landscape Ontario Horticultural Trades Association (Landscape Ontario) and the Electrical Safety Authority (ESA) have partnered to improve electrical safety awareness and compliance across Ontario’s landscape and horticultural industry. The partnership focuses on supporting safe work around electrical infrastructure, including overhead powerlines and underground systems, and providing clarity and guidance on the application of the Ontario Read More…

  • Register Now for EFC’s Annual Conference: June 2-4, 2026

    Register Now for EFC’s Annual Conference: June 2-4, 2026

    May 14, 2026 Bringing together professionals from across Canada’s electrical industry, EFC’s annual conference offers a dynamic platform for learning, networking, and business growth. Attendees will gain valuable insights from expert speakers in the business program while also being able to take advantage of dedicated B2B Head Office meeting spaces and the ever popular Electro-Lounge Read More…