Guide to the Canadian Electrical Code, Part 1[i], 26th Edition– A Road Map: Section 56

February 6, 2026

By William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook**, but will hopefully provide some help in navigating the Code.

Section 56 — Optical fiber cables

56

Rule 56-000 states that Section 56 is a supplementary or amendatory section of the code and applies to the installation of optical fiber cables in conjunction with all other electrical systems.

Rule 56-002 provides a special terminology definition for an Optical Fiber Cable – a cable consisting of one or more optical fibers that transmits modulated light for the purpose of control, signalling or communications.

Rule 56-102 outlines that there are 3 types of optical fiber cables:

  • Non-conductive cables containing no metal other conductive materials.
  • Conductive cables containing non-current carrying conductive material such as strength member, metal vapour barriers or metal sheaths or shields, and,
  • Hybrid cables that contain both fiber optic and current carrying electrical conductors.
Rule 56-104 requires that optical fiber cables
  • installed, within buildings, be approved types as listed in Table 19 and
  • where installed outdoors be suitable for the location with respect to moisture, corrosive atmosphere, temperature, degree of enclosure and exposure to mechanical damage.
  • Also note that OFNP, OFNR, OFNG, OFN, OFNH, OFCP, OFCR, OFCG, OFC, and OFCH have a minimum cable temperature rating of 60 °C.
  • Where a cable is used in a greater temperature the rating must be marked on the cable.

Rule 56-106 states that, as per paragraph (a) in the Scope of the code, optical fiber installations, by a utility in its function as a utility, are not subject to inspection and acceptance by an inspector.

Rule 56-200 prohibits non-conductive optical fiber cables from occupying the same raceway, cabinet, panel, outlet box or similar enclosure with insulated conductors of electric lighting, power or Class I circuits, unless they are functionally associated, and the number and size of insulated conductors meet applicable requirements of the wiring method. For industrial establishments, where authorized persons supervise and maintain the installation, this prohibition may be waived.

Rule 56-202 Conductive optical fiber cables
  • are permitted to occupy the same raceway with Class 2 circuits in accordance with Section 16; communication circuits in accordance with Section 60; or community antenna distribution and radio and television circuits in accordance with Section 54.
  • must not occupy the same raceway, panel, cabinet, or similar enclosure housing electric lighting, power, or Class 1 circuits.
  • must not occupy the same cabinet, panel, outlet box, or similar enclosure housing the electrical terminals of a Class 2, communications, community antenna distribution, or radio and television circuit, unless they are functionally associated with the Class 2, communication, community antenna distribution, or radio and television circuit; or the conductive optical fiber cables are factory assembled in the enclosure.
  • for industrial establishments only, where conditions of maintenance and supervision ensure that only authorized persons service the installation, conductive optical fiber cables are permitted to occupy the same raceway, cabinet, panel, outlet box, or similar enclosure as electric power, control, or instrumentation cables provided the total length of each conductive optical fiber cable does not extend beyond the boundaries of the industrial establishment.
  • The conductive non-current-carrying members of conductive optical fiber cables shall be grounded in accordance with Section 10

Rule 56-204 permits optical fiber cables to be incorporated in hybrid cables with electric lighting, power, or Class I circuits not exceeding 750 volts, or Class 2, communications, community antenna, or radio and television circuits conductors with associated functions. In every case, the hybrid cable is classed as per the type of insulated conductors in the cable and installed according to the rules for that type.

Rule 56-206 requires that where an optical fiber cable penetrates through a fire separation it shall be installed in accordance with Rule 2-128 to prevent fire spread.

Rule 56-208 requires optical fiber and hybrid cables installed in a vertical shaft to be totally enclosed in non-combustible raceway unless they meet the flame spread requirements of the National Building Code of Canada or local building legislation for buildings of non-combustible construction (FT4).

Rule 56-210 provides that optical fiber cables must not be installed in ducts or plenum chambers unless they meet the flame spread requirements of the National Building Code of Canada or local building legislation and the provision of Rule 12-010 – Wiring in ducts and plenum chambers.

Rule 56-212 requires that all raceways containing optical fiber cables must be installed in accordance with Section 12.

Rule 56-214 requires that where conductive optical fiber cables are exposed to lightning or accidental contact with lighting or power cables the metal parts must be bonded to ground at the point, as close as possible, to the point the cable enters the building. 

Previous Installment: Section 54

In the next installment, we will be discussing Section 58 — Passenger ropeways and similar equipment.


[i] Source: CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2024 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

Related Articles


Latest Articles

  • Cooper Lighting Solutions: Project Spotlight – Maple Ridge Fire Hall No. 4 – Maple Ridge, BC

    Cooper Lighting Solutions: Project Spotlight – Maple Ridge Fire Hall No. 4 – Maple Ridge, BC

    July 17, 2026 Maple Ridge Fire Hall No. 4 Lighting Project Highlights How Cooper Lighting Solutions Can Help Support a Facility Built to Serve the Community Day & Night Maple Ridge Fire Hall No. 4 is a 22,800-square-foot post-disaster facility designed to support emergency response, training, maintenance, and daily operations. The two-storey hall includes apparatus… Read More…

  • Canada Lighting Industry: Trends, Growth & Future Outlook 2026

    Canada Lighting Industry: Trends, Growth & Future Outlook 2026

    The Canada lighting industry is entering a transformative phase driven by sustainability goals, smart infrastructure development, energy-efficiency regulations, and increasing demand for connected technologies. Lighting is no longer viewed as a basic utility across commercial buildings, industrial facilities, public infrastructure, residential projects and retail environments. Now, it has become a strategic component of modern building… Read More…

  • Notice to Archive 24-ECV-002-024-MMTE: Rule 2-024 Use of Approved Equipment – Meter Mounted Transfer Equipment

    Notice to Archive 24-ECV-002-024-MMTE: Rule 2-024 Use of Approved Equipment – Meter Mounted Transfer Equipment

    July 13, 2026 Variance 24-ECV-002-024-MMTE was introduced to allow meter-mounted transfer equipment (MMTE) to be approved under SPE-1000 while no Canadian certification standard existed. With the publication of ANSI/CAN/UL 1008M:2025 Transfer Switch Equipment, Meter-Mounted, a recognized certification standard is now available making the use of the SPE-1000 approval unnecessary. The variance will be archived effective… Read More…

  • ESA Electrical Wiring Inspector – Ontario (Ongoing Recruitment/Talent Pool)

    ESA Electrical Wiring Inspector – Ontario (Ongoing Recruitment/Talent Pool)

    July 13, 2026 If becoming an Inspector is of interest to you and you meet the requirements outlined below, please submit a fully completed online application, including a detailed resume outlining previous employment (including employer names and dates of employment), work history, education, and the date of issue of your original 309A Certificate of Qualification.… Read More…


Changing Scene

  • Build Canada Homes and the Société d’habitation du Québec Launch the Next Phase of their Partnership to Deliver Thousands of Affordable Homes

    Build Canada Homes and the Société d’habitation du Québec Launch the Next Phase of their Partnership to Deliver Thousands of Affordable Homes

    July 17, 2026 Following the announcement in April 2026 of the first phase of the partnership between Build Canada Homes and the Société d’habitation du Québec to build more than 850 affordable homes, the governments of Canada and Quebec are confirming the progress of talks by the joint Build Canada Homes–Société d’habitation du Québec Collaboration… Read More…

  • New Project to Expand and Modernize the Chicoutimi Hospital

    New Project to Expand and Modernize the Chicoutimi Hospital

    July 17, 2026 The project, estimated at over $840 million, will provide the region’s residents with modern facilities better suited to current needs and will tangibly improve access to safe, high-quality care. $36.1 million will come from the Build Communities Strong Fund (BCSF), secured through an agreement with the federal government. The project includes the… Read More…

  • EB Horsman & Son Adds Signage to New Grand Prairie Branch

    EB Horsman & Son Adds Signage to New Grand Prairie Branch

    July 17, 2026 EB Horsman & Son’s new Grande Prairie branch is continuing to move forward, and the exterior signage has officially been installed. As part of their continued growth in the region, this new location will provide customers with closer access to electrical, lighting, data communications, and process automation and controls solutions. Supported by… Read More…

  • Gescan Welcomes New Branch Manager in Kelowna

    Gescan Welcomes New Branch Manager in Kelowna

    July 17, 2026 Gescan has introduced Thomas Chiari as their new Branch Manager in Kelowna. “With more than 22 years of experience within Sonepar, including 12 years as a Branch Manager, Thomas brings a strong track record in sales leadership, team development and building lasting customer and supplier relationships. We’re excited to have Thomas on… Read More…