This is the fourth of a series of articles detailing significant changes the Technical Committee considered the 2015 Canadian Electrical Code Part I (CE Code). The final meeting for 2015 CE Code changes took place in June of this year. The rules shown in this article are limited to changes adopted by CE Code Technical Committee and are not subject to further changes. It should be noted that until a formal memorandum of revisions to the CE Code is published by the CSA, the information provided in this article is simply based on the observations of the writer.

Photo 1. Eight plug fuses connected to 120V circuits (one ungrounded conductor).

Section 14
Section 14 has only one rule change for the 2015 CE Code in Rule 14-402.The words “because a plug fuse can be safely handled while energized in such a circuit” were removed from Item (c) and replaced with a note in Appendix B explaining why a disconnecting means is not required for a plug fuse where the circuit has only one ungrounded conductor.

Section 18
The changes for Section 18 will be covered in a future article.

Section 20

The title of Rule 20-100 has been changed from “Commercial garages — Repairs and storage” to “Commercial repair garages,” deleting the reference to storage; in addition,Subrule (3) of Rule 20-102 has been deleted. This is the subrule that detailed the areas within a storage garage that were considered a Class I, Zone 2 location. Along with these changes, Rules 20-200 to 20-206 for Residential storage garages were also deleted. The rationale provided for these changes recognized the historic lack of incidents in storage garages with respect to the electrical installations and acknowledged that the risk of an explosion related to electrical wiring in storage garages is not statistically higher than in other ordinary locations. In addition, these changes will harmonize these area classifications with the National Electrical Code.

Codes Plug Fuses

 

Photo 2. A commercial repair garage as detailed in Rule 2-100.

Codes Garage 2

The word “showroom” was also replaced with “adjacent areas” in Subrule (1) of Rule 20-100; this editorial change also allowed the deletion of Subrule (5). As with the 2012 CE Code, adjacent areas are classified as Class I, Zone 2 locations, unless the areas are elevated from a service and repair area by at least 50 mm, or separated from a service and repair area by tight-fitting barriers such as curbs, ramps, or partitions at least 50 mm high.

Photo 3. A door between the garage and an adjacent area, without elevation from a service and repair, or separated from a service and repair area by tight-fitting barriers such as curbs, ramps, or partitions at least 50 mm high.

Codes Door

Rule 20-114 covering electric vehicle charging has also been deleted in its entirety as the requirements are now covered in CSA Standard C22.2 No 280-13 Electric vehicle supply equipment.

Section 24
A new Subrule (7) has been added to Rule 24-102; this subrule requires all circuits connected to communication or nurse call equipment installed within a patient care area to be a Class I circuit, and wiring of these circuits is now required to meet the applicable rules of Sections 12 and 16.

New Subrule (7) has also been added to Rule 24-106 requiring that receptacles in a basic care area are not to be of the isolated ground type. This change is to provide consistency between the code and CSA Standard Z32-09 Electrical safety and essential electrical systems in health care facilities.

Photo 4. Isolated ground type receptacles as shown in this photo are no longer allowed in basic care areas. Compliments of Hubbell

Codes Isolated Receptacle

In Rule 24-108 the reference to CSA Standard C22.2 No. 125 was revised to include the CAN/CSA-C22.2 No. 60601 series of standards.

Section 26

Existing Rule 26-702(3) has been expanded to require receptacle covers used in a wet location to be marked “Extra-Duty.”This change is to recognize more stringent testing requirements for receptacle covers suitable for wet locations whether or not a plug is inserted into the receptacle in CSA Standard CSA C22.2 No. 42.1-13.

New Subrule (3) for Rule 26-702 will allow cover plates marked “Wet Location Only When Cover Closed,” or the equivalent, to be used for outside receptacles installed in or located at least 1 m above finished grade and not in a wet location, or where facing downward, at an angle of 45° or less from the horizontal.

Photos 5 and 5A. The “Extra-Duty” marking found on covers suitable for wet locations whether or not a plug is inserted into the receptacle is required to meet revised Rule 26-702(3).

Codes Extra Duty

Items (a) and (d)(vi) of Rule 26-712 has been revised removing the allowance of only one duplex receptacle in a dining area forming part of a kitchen. This change will require receptacles in dining areas to meet the spacing requirements for any other finished room in a dwelling unit. In addition, a revision to Item (e) of Rule 26-722 will require the dining area receptacles to be on a branch circuit that does not supply any other outlets.

Photo 6. An acceptable location of a wet location receptacle cover that is not suitable for wet locations whether or not a plug is inserted into the receptacle

Codes Wet Location

Special Terminology for Arc fault protection, Combination type arc-fault circuit interrupter, and Outlet branch circuit type arc-fault circuit interrupter has been added as Rule 26-720 that reads:

“Arc fault protection — a means of recognizing characteristics unique to both series and parallel arc faults and de-energizing the circuit when an arc fault is detected.”

“Combination type arc-fault circuit interrupter — a device that provides both series and parallel arc fault protection to the entire branch circuit wiring including cord sets, and power supply cords connected to the outlets, against the unwanted effects of arcing.”

“Outlet branch circuit type arc-fault circuit interrupter — a device that provides both series and parallel arc fault protection to downstream branch circuit wiring, cord sets, and power-supply cords against the unwanted effects of arcing and also provides series arc fault protection to upstream branch circuit wiring.”

Item (f) of Rule 26-722 covering arc fault protection for branch circuits supplying receptacles has been revised to clarify that the requirements only apply to branch circuits that supply receptacles rated 125 volts and 20 A or less. The Item also replaced the words “arc-fault circuit interrupter” with “combination type arc-fault circuit interrupter” recognising this new type of arc fault protection. In addition the circuits requiring the arc fault protection have been expanded from branch circuits that supply receptacles installed in sleeping facilities of a dwelling unit to all receptacles for a dwelling unit except branch circuit supplying receptacles installed in a bathroom or washroom located within 1 m of a wash basin, receptacles installed in a kitchen for a refrigerator, counter receptacles installed along the wall, on fixed islands and peninsular counters, and branch circuits that only supply single receptacles installed for a sump pump provided the sump pump receptacle is identified as a sump pump receptacle.

As an alternative to installing breaker style combination type arc-fault circuit interrupters, new Item (g) will allow an outlet branch circuit type arc-fault circuit interrupter to be installed at the first branch circuit outlet provided a metal raceway, armoured cable, or non-metallic conduit or tubing is used as the wiring method from the panelboard to the first outlet where the outlet branch circuit type arc-fault circuit interrupter is installed. This means non-metallic sheathed cable will not be allowed to supply the first outlet on the branch circuit where the arc fault protection is an outlet branch circuit type arc-fault circuit interrupter.

Photo 7. “Wet Location Only When Cover Closed” marking on a receptacle cover that is not suitable for wet locations whether or not a plug is inserted into the receptacle.

Codes Wet Location Cover

With the new Rule 26-720added for Special Terminology, existing Rule 26-724has been renumbered as 26-726.

These rules have all been deleted as the requirements have been moved to Section 62:

• Rule 26-750 “Installation of storage-tank water heaters” 

• Rule 26-752 “Infrared drying lamps” 

• Rule 26-756 “Induction and dielectric heating equipment” 

• Rules 26-760 and 26-762

• Subsection heading “Bare element water heaters”

Section 28

In Rule 28-200 a new Item has been inserted between Items (c) and (d) to recognize the use of self-protected combination motor controllers as motor branch circuit protection.

Photo 8. The dining area forms part of a dwelling unit kitchen. Note the walls around the table now require receptacle placement like any other finished room in a dwelling unit and a separate circuit.

Codes Dining

A new Rule 28-212 has been added to Section 28 allowing semiconductor fuses to be used in adjustable speed drive systems provided that the semiconductor fuses are integral to an approved controller. This change is a result of new CSA Standard C22.2 No. 274-13 Adjustable speed drive systems, which now recognizes semiconductor fuses used for additional drive protection. Keep in mind the semiconductor fusing is not a substitute for the motor branch circuit protection required by Rule 28-200(a).

Rule 28-602 will see two changes to address possible misapplication of manual motor controllers used for air conditioning, refrigeration or heating equipment.The first change is the addition of Item (3) (b)(iii) that will not allow the use of manual motor controllers where equipment contains overcurrent protection, and specifically requires the motor controller to be adequately rated. The second change is the addition of a new Subrule (5) requirement for the manual motor controllers to be suitable for the environment, and a requirement that the conduit be drained and sealed in accordance with Rule 22-302 where a conduit is used as part of the wiring methods to the disconnecting means located in the enclosure.

Photo 9. The old style branch circuit type arc-fault circuit interrupter acceptable in the 2012 CE Code. Compliments of Eaton

Codes Branch Circuit

Photo 10. A new style branch circuit Combination type arc-fault circuit interrupter. Compliments of Eaton

Codes New Branch Circuit

 

Section 30
Rule 30-406 has been rewritten covering the arrangement of exposed wiring on suspended luminaires. This new wording will require exposed wiring to be arranged so that neither the suspension means nor the weight of the luminaire places tension on the wiring or on the connections.

Section 32
Section 32 has two changes for the 2015 CE Code. The first change is the insertion of a new Subrule (2) for Rule 32-100 that permits the use of data communication links between fire alarm control units and transponders as described in ULC S524. The second change is to Rule 32-108 covering current power supplies. Subrule (1) has been re-written requiring a separate circuit for a fire alarm power supply, and an inserted new Subrule (2) that allows a separate branch circuit not required to be as close as practicable to the service box, for where a fire alarm system includes more than one control unit or transponder. The main reasons for these changes was to acknowledge the difficulty of installinga 15-amp overcurrent device as close as practicable to the load terminals of the service box when the main service is a large distribution switchboard, and to recognize that fire alarm systems are electrically supervised and have a built-in standby power supply with audible and visual trouble devices that would be energized for days from the standby power within the fire alarm system in the event the fire alarm branch circuit overcurrent device operated.

Photo 11. An Outlet branch circuit type arc-fault circuit interrupter. Compliments of Leviton

Codes Outlet Branch Circuit

Section 34
To correct an inconsistency between Items (c) and (d) of Rule 34-100 regarding the location and lockability of the disconnection means for a sign, Item (d) has been replaced as a new Subrule (2). This rule will still allow the disconnecting means to be located out of the line of sight or more than 9 m from the sign, provided that the disconnecting means is capable of being locked in the open position.

Section 36
Rule 36-302(1)(a) has been revised deleting the requirement that the driven ground rods for station grounding be not less than 3 m long and 19.0 mm in diameter. The rationale for this deletion was to recognize that the dimensions in the rule were inconsistent with CSA Standard 41 Grounding and Bonding Equipment that covers ground rods, and the requirement in existing Rule 36-304 requires the maximum permissible resistance of the station ground electrode regardless of the size of ground rods used. Item (a) will continue to require a minimum of four driven ground rods spaced at least the rod length apart and located adjacent to the equipment to be grounded where practicable.

Photos 12A and 12 B. A self-protected combination motor controller that can be used as motor branch circuit protection.

Codes Motor Controller

Section 46
A new Subrule (4) has been added to Rule 46-400 covering illumination of exit signs. In this new subrule the luminaires used to illuminate photo luminescent exit signs (exit signs that are not connected to an electrical circuit) are to be connected in compliance with Subrules (1) to (3). This means the luminaires used to illuminate photo luminescent exit signs must be also illuminated by an emergency power supply where emergency lighting is required by the National Building Code of Canada, and connected to a circuit that is used for no other purpose or connected to a circuit supplying emergency lighting in the area where these exit signs are installed.

Sections 62 and 64
The changes for Sections 62 and 64 will be covered in a future article.

Section 66
The scope of Section 66 limits the section to temporary installations and expands the power supplies from generators only to any source of electrical supply. The list of installations the section applies to has also been expanded from amusement parks, midways and carnivals, to include fairs, film /television or radio productions, remote broadcasting or recording locations, live performance and entertainment events, touring shows and productions, concerts, sporting events, trade shows, and similar events.

Photo 13. Exposed wiring on a suspended luminaire

Codes Exposed Wiring

Rule 66-200 has a new Subrule (3) detailing the type of grounding conductor to be used for a mobile generator. This new requirement will limit the 

• number of in-line single-pin connections to no more than two

• total length of the ground conductor to a maximum of 50 m, run in a direct shortest practicable route, with a minimum No. 4 AWG conductor that is to be dedicated to the mobile generator.

Section 68
To be consistent with the rest of the CE Code the reference to ground fault circuit interrupters has been changed to clarify that the objective of this requirement is to use Class A ground fault circuit interrupters in Rules 68-068, 68-100, and 68-202.

Photo 14. An example of station grounding that is required to meet the maximum permissible resistance of the station ground electrode detailed in CE Code Rule 36-304. Compliments of PBW High Voltage Ltd.

Codes Station Grounding

Section 74
In Section 74 the special terminology changed from “ground anchor” to “mounting stake” that reads: an angle iron, section of rigid galvanized steel conduit or other metallic post set into the ground for the purpose of supporting an elevated light fixture; and the term “pull pit” was changed to “transformer housing” to read: a below-grade junction box used as a cable pulling point, to house transformers or series lighting cable splices. In addition Rules 74-004, 74-010 changed to line up with the new special terminology.

In Rule 74-004 the reference to the 6.6 A was removed from Subrules (1) and (5) to allow for LED type luminaires for runway lighting. The maximum loading of the series system is now limited by the markings of the transformer used for the series systems.

Section 86
The special terminology definition for “Electric vehicle charging equipment” was deleted and replaced with a definition for “Electric vehicle supply equipment” that reads: “a complete assembly consisting of conductors, connectors, devices, apparatus, and fittings installed specifically for the purpose of power transfer and information exchange between the branch circuit and the electric vehicle (see Appendix B).”

Photo 15. A photo luminescent exit sign of the type required to be illuminated by an emergency power supply.

Codes Luminescent Exit

Photo 16. A transformer housing used for the series system detailed in CE Code Section 74.

Codes Transformer Housing

The definition for “Electric vehicle (see Appendix B)” was revised to read: “an automotive-type vehicle for use on public roads that 

(a) includes automobiles, buses, trucks, vans, low-speed vehicles, motorcycles, and similar vehicles, powered by one or more electric motors that draw current from a fuel cell, photovoltaic array, rechargeable energy storage system (such as a battery or capacitor), or other source of electric current; and 

(b) includes plug-in hybrid electric vehicles (PHEV); and

(c) excludes off-road electric vehicles, such as industrial trucks, hoists, lifts, transports, golf carts, airline ground support equipment, tractors, and mobility scooters for persons with disabilities.”

The definition for “Electric vehicle connector” was revised to read: “a device that, when electrically coupled to a mating device on the electric vehicle, establishes means for power transfer and information exchange between an electric vehicle and electric vehicle supply equipment.”

Photo 17. The nameplate of a transformer used for the series system. Note the maximum ampacity marking of 6.6 amp.

Codes Transformer Nameplate

Photo 18. A mounting stake and lighting transformer housing used for the series system airport runway detailed in CE Code Section 74.

Codes Mounting Stake

The definition for “Electric vehicle inlet” was deleted, and a new definition for plug-in hybrid vehicle was added to read: “Plug-in hybrid electric vehicle (PHEV) – A type of electric vehicle having an additional energy source for motive power.”

With these special terminology changes, Rules 86-300 and 86-306 have seen editorial changes to align with the revised definitions.

Rule 86-300 also has two new subrules to address circuit loading by referring code users to Section 8 and to permit the electric vehicle supply equipment to be connected on a branch circuit supplying other loads provided with control equipment that prevents simultaneous operation of the electric vehicle supply equipment with other circuit loads to prevent the calculated demand of the circuit from being exceeded.

The hazardous location requirements in Rules 86-308, 86-400, and 86-404 were replaced with a new Rule 86-404 that indicates electrical vehicle supply equipment and the supply connections located in a hazardous location must conform to the hazardous location requirements in the CE Code.

Published with the permission of EIEI http://iaeimagazine.org/magazine/2014/11/03/2015-ce-code-part-1-changes-3/.

Read Part 1 of CE 2015 Code Changes here.
Read Part 2 of CE 2015 Code Changes here.
Read Part 3 of CE 2015 Code Changes here.
Read Part 5 of CE 2015 Code Changes here.


 

Steve Douglas is an IAEI International Past President. He is also the senior technical codes specialist for QPS Evaluation Services. As the International Association of Electrical Inspectors representative on Part I and Part II of the Canadian Electrical Code, Steve is the vice chair of the CE Code Part I, chair of CE Code Part I Subcommittees for Section 2, and 12, and a member on Sections 40, 64, 68, 76 and Appendix D. In addition, Steve is the chair of the CSA Standards C22.2 No. 273 Cablebus, C22.6 No. 1, Electrical Inspection Code for Existing Residential Occupancies committee, the chair of the SPE-1000 Working Group, and a member on committees for the Objective Based Industrial Electrical Code, Safety Management Systems, Solar Photovoltaic Modules, Photovoltaic Cable, Fuel Cells, Wind Turbines, Distribution transformers, Outlet Boxes, and Wiring Fittings Hardware and Positioning Devices.

 

 Legrand: the Adorne Collection Video Gallery 

Legrand Adorne CollectionThe adorne collection makes life simply beautiful, putting a stylishly smart finishing touch on your home. With adorne you will discover real-world inspiration for turning the ordinary into extraordinary with re-imagined switches and other solutions you have to see to believe. Check out the extensive adorne video collection to learn more about adorne and the advantages in can bring to any home.

 

 

 

 

Watch the video Here

 

Changing Scene

  • Prev
ABB presented its electrification solutions that will allow customers to take full advantage of the ...
Electricity Human Resources Canada has introduced a new Board of Directors, effective as of their ...
Jacques Fiset, the new president of the EFC Quebec section, told us in a recent interview that his ...
Organised by the Hong Kong Trade Development Council (HKTDC), the twin lighting shows - the  ...
A Friday night, the end of summer, the weather is mild, and 2,500 people — customers, ...
Eaton focuses on developing personable connections in every aspect. In September, our team will be ...
During the recently held IMARK Canada 2019 meeting in Niagara Falls, executives from 14 of the ...
Valard has been selected by Wataynikaneyap Power LPto provide engineering, procurement ...
The Canadian Apprenticeship Forum-Forum Canadien sur l’Apprentissage (CAF-FCA) has announced ...
Electricity Human Resources Canada has announced this year's keynote speakers for Agents of Change ...

Ideal National ChampionshipThe 2019 Ideal National Championship was a highly charged, no-holds barred competition to determine the best electrician in North America, including teams from China, Australia and Mexico. Over 55,000 electrical contractors and electricians competed worldwide in 5 countries, and the cream of the crop competed at the 2019 Ideal National Championship in Orlando.

From November 7 to 9, 162 professionals and apprentices from the US and Canada were in Orlando to compete. 

 

 

Read More

 

 

 

Michelle BraniganBy Michelle Branigan

Have you been “ghosted” yet?

No, I’m not referring to some strange Halloween game, but rather a phenomenon which is becoming increasingly prevalent in the workplace. While the term originally referred to the dating world and what happens when someone you're involved with suddenly stops making any contact, it has now entered the workplace.

 

 

Read More

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
The classic TWR1 and TWR2 LED glass wall packs come with adjustable light output (ALO) technology. ...
Eaton has added a new ‘compact’ model to its class-leading MTL 937x-FB Fieldbus ...
The R16MTCPU, R32MTCPU, and R64MTCPU motion CPUs are dedicated motion control processors designed ...
The smallest robot controller in its class, the ultra-compact YRC1000micro minimizes installation ...
As part of the SICK AppSpace eco-system, the programmable SIM10xx Sensor Integration Machines offer ...
With the free, PC-based Festo Automation Suite commissioning software, getting a new drive package ...
Balluff’s inductive couplers connect up to eight discrete sensors across a small air gap, ...
The IP20 product family from Bihl+Wiedemann welcomes a new member:      
Eaton XT series self-powered electronic overload relays are self-contained units available at up to ...
Festo has created the Simplified Motion Series of electric drives for jobs requiring very simple ...

 

TWR2 LEDThe classic TWR1 and TWR2 LED glass wall packs come with adjustable light output (ALO) technology. TWR LED dials in to desired output to match the needs of any job site, and saves significant energy costs when replacing traditional metal halide sources. Its energy-efficient LEDs have an expected service life of more than 20 years, which eliminates frequent lamp and ballast replacements associated with traditional technologies. Cost effective, flexible, and always in stock - TWR LED is the choice for distributors and contractors alike.

 

 

 

Read More

 

 

SICK SIM10xxAs part of the SICK AppSpace eco-system, the programmable SIM10xx Sensor Integration Machines offer multiple sensor data acquisition and fusion processes, thereby providing space for new application solutions. The acquired data is processed and visualized for important information, for example quality control or process analysis. In addition, the IoT gateway functions enable connection from the edge to the cloud via the Internet in the context of Industry 4.0. The SIM10xx products feature a powerful processor and Ethernet interfaces for cameras and LiDAR sensors. Other sensors can be integrated via IO-Link, for instance for distance and height measuring purposes.

 

Read More

 

Peers & Profiles

  • Prev
Stephanie Medeiros leads ABB Canada’s Electric Vehicle Charging Infrastructure team, as well ...
Electrical Industry Canada had the pleasure of interviewing Matt Davis of Newfoundland Power, ...
An electrician by trade, Daniel Lacovetsky is the founder and President of Powertec Electric, an ...
Mike Morneau began his professional career in graphic arts after earning a Bachelor of Technology ...
AimLite offers a vast choice of lighting lines to facilitate any lighting project’s needs. ...
John Krill has been in the energy and construction industries for 35-years, now he serves as Canem ...
Ali Heighton is the Program Coordinator for IBEW Local 37 who has found success as a young ...
Flextherm was founded in 1991 by current company President, Philippe Charron. For more than 25 ...
Ouellet Electric Heating began humbly in 1960 with Charles-Emile Ouellet, who started manufacturing ...
Justin Harris is a Programmer/Electrician for COREngineering, a New Brunswick based mechanical ...

 

Stephanie MedeirosBy Blake Marchand

Stephanie Medeiros leads ABB Canada’s Electric Vehicle Charging Infrastructure team, as well as transit bus charging in the United States and Canada. She has been with ABB in various positions for 10 years, compiling a diverse skill set that includes work all over the world.

After receiving a degree in Electrical Engineering from McGill University, Medeiros got her start in the industry out of school volunteering with the Canadian government as an electrical engineering intern, where she travelled to Peru to help improve their water treatment infrastructure. 

Read More

 

 