In Part 1, James R. White looked at the level of training required, suggested components of a training program, and the definition of a “qualified” person. Here, he compares CSA Z462 and NFPA 70E by emergency response training, lockout/tagout and more. Also included: a handy checklist summary of CSA, NFPA and OSHA electrical safety training requirements.

NFPA 70E and Canada’s Z462 Clause 4.1.6.4 have almost identical requirements to OSHA, but also add the following:

NFPA 70E section 110.2 (D) “Decision-making process necessary to be able to do the following:

1. Perform the job safety planning

2. Identify electrical hazards

3. Assess the associated risk

4. Select the appropriate risk control methods from the hierarchy of controls identified in 110.1(G), including personal protective equipment.”

Be aware that Z462 is behind NFPA 70E by a cycle, so those requirements are, at the time of the writing of this article, not exactly the same.Typically, Z462 adopts what NFPA 70E has added in the latest edition, but sometimes not.The reader must ensure they understand the requirements of the province they reside or work in, as each Canadian province has different requirements.Z462 is the first national safety standard adapted by CSA.This article will use the wording in the 2015 edition of NFPA 70E as its basis.

Where OSHA is “non-prescriptive”, that is, they won’t usually require anything specific, NFPA 70E and Z462 are prescriptive.NFPA 70E section 110.2 (A) and Z462 Clause 4.1.6.1 state “(A) Safety Training. The training requirements contained in this section shall apply to employees exposed to an electrical hazard when the risk associated with that hazard is not reduced to a safe level by the applicable electrical installation requirements. Such employees shall be trained to understand the specific hazards associated with electrical energy. They shall be trained in safety-related work practices and procedural requirements, as necessary, to provide protection from the electrical hazards associated with their respective job or task assignments. Employees shall be trained to identify and understand the relationship between electrical hazards and possible injury.”

Note that even NFPA 70E and Z462 get somewhat vague.No one can foresee all circumstances and conditions the worker may have to perform their task in, so it is impossible to provide a step-by-step training requirement.The employer must assess the hazards at their company’s worksite and determine what training is required to protect workers.

The above section requires the training of anyone who may be exposed to electrical hazards.The training has to include electrical hazard awareness, procedures and requirements needed to avoid the hazards, understand the relationship between electrical hazards and the injuries that may be caused by those hazards.The employer must ensure the training is site-specific and covers the actual hazards the workers may encounter.

Emergency response training

NFPA 70E and Z462 require emergency response training.Using the wording in NFPA 70E:

“(1) Contact Release. Employees exposed to shock hazards shall be trained in methods of safe release of victims from contact with exposed energized electrical conductors or circuit parts. Refresher training shall occur annually.

(2) First Aid, Emergency Response, and Resuscitation.

(a) Employees responsible for responding to medical emergencies shall be trained in first aid and emergency procedures.

(b) Employees responsible for responding to medical emergencies shall be trained in cardiopulmonary resuscitation (CPR). Refresher training shall occur annually.

(c) Employees responsible for responding to medical emergencies shall be trained in the use of an automated external defibrillator (AED) if an employer’s emergency response plan includes the use of this device. Refresher training shall occur annually”.

The above section requires annual training in emergency release of shock victims, first aid and CPR and the use of AEDs, if AEDs are available at the job site.The American Heart Association requires CPR training only every two years, but NFPA 70E requires it annually.The reason for the discrepancy is that AHA recommendations apply to the general public and workers of all types.NFPA 70E applies specifically to electrical workers, who have a much higher risk of shock.

Additional training requirements in NFPA 70E/Z462

These requirements include:

• People undergoing training who can then demonstrate the ability to perform specific tasks safely can be considered qualified for that task.That person may still be unqualified in regards to other tasks, though.

• Tasks performed less often than once per year require retraining on that task before they can perform that task again.Training can be on-the-job (OJT), but be careful to document such OJT, as OSHA inspects training records in the event of an accident.

• Qualified people must be trained to select the appropriate test instrument.That qualified person must also demonstrate how to safely use the test instrument to determine the absence of voltage, interpret the indications of the test instrument, be able to inspect the test instrument to ensure it is safe to use and understand the limitations of the test instrument being used.

• Employers must conduct regular checks to ensure their employees are following the safety-related work practices required by the standards, as well as their company.

• Unqualified people must also have training.They must be trained on how to recognize and avoid electrical hazards they may encounter.If they interact with equipment, such as operating electrical equipment, especially circuit breakers, fused switches and MCCs, they must be trained to understand how the equipment functions and operates, and the hazards that may be present when operating the equipment.If PPE is required, unqualified workers must receive training on the selection, inspection, use, care and limitations of that equipment.

• Retraining (not refresher training) must be conducted at least every three years.Retraining must include changes made to NFPA 70E/Z462, company work practices, procedures and policies changes being made as a result of such changes, and:

o The annual inspections reveal worker(s) are not following safety-related work practices required by the company or 70E/Z462, or

o The company installs new technology that is different than what the worker is used to, or

o The worker must use work practices that are different than those normally used by the worker

Lockout/tagout

In addition, NFPA 70E and Z462 have requirements for lockout/tagout (LOTO) training in Article 120/Clause 4.2.2.2.2.LOTO training requirements include:

• All persons exposed or affected by a LOTO must be trained to understand the LOTO procedure and their responsibilities in its execution.

• If the worker is new or recently assigned, they require training to understand the LOTO procedure and their responsibilities.

• Retraining is required whenever the procedure(s) are revised or at least every three years.

• LOTO training must be documented.

When you need a training specialist

Most employers face the need to bring in a safety training specialist for part or all of the training requirement. The challenge can be differentiating between training options, since not all private training programs meet the requirements discussed above.Helpful guidelines:

• By these standards, initial electrical safety training cannot be done in a day.

• Initial electrical safety training must have hands-on labs with a documented demonstration of skills.

• Look at the instructor’s qualifications and check references.Being an engineer or ex-utility worker does not on its own qualify someone to present electrical safety training.

• Membership on NFPA 70E committee, Z462 committee, NEC Code-Making Panels, etc. indicates a better understanding of those documents.

• Don’t go low-bid.There’s usually a reason training is inexpensive.

• Don’t be a “box checker”, or someone who just wants to “get it over with”.People’s lives may depend on the safety training they receive.

Summary

NFPA is advocating an integrated approach to hazard risk analysis, PPE selection and safe work practices, with training as the cornerstone. It can be tempting to think of regulation-driven training as an overhead expenditure, but done right, good training improves the safety and efficiency of your technical workforce and often reduces long-term expenses.

Overview of OSHA, NFPA and CSA electrical safety training requirements

• Training is required for qualified and unqualified persons

• A qualified person is anyone exposed to or potentially exposed to electrical hazards

• Training is required to establish an understanding of their and their employer’s responsibilities for electrical safety

• Training must be such that attendees are able to recognize and avoid electrical hazards

• Initial training must have a method to immediately respond to questions from the attendees and have a hands-on portion to establish proficiency

• Trainees may not have a formal education in areas relating to electrical safety

• Training is to be effective, site-specific and cover the hazards at that location

• Computer-based and video training can be used to augment instructor-led training, but cannot replace it

• Qualified persons must have training in and demonstrate skills and knowledge of electrical equipment and power systems.Such training must cover:

o Basic construction of the equipment and power system

o The manufacturer’s recommended operating procedures, including the use of any specialized tools or attachments

o The hazards associated with operating the equipment or power system

• Qualified person training must receive training in:

o Skills and techniques to test for the presence and absence of voltage

o Skills and techniques to determine nominal (phase-to-phase) voltage of the electrical power system

o Safe approach distances for electrical shock and arc flash

o Perform safety job planning 

o Assess the risk associated with a specific job task

o Select the appropriate methods from a hierarchy of controls, including PPE

o Safety-related work practices and procedures to perform the job task safely

o How to identify and understand the relationship between electrical hazards and injury

o How to select the correct test instrument, how to inspect it, how to safely use it, what it’s limitations of use are, and interpret the indications

• Annual training is required for contact release, first aid and CPR 

• Annual training is also required for the use of AEDs, if there are AEDs on site

• Workers can be qualified to perform specific tasks, if they receive training in and demonstrate proficiency at that task while being supervised by a qualified person

• Tasks performed less often than once per year require retraining before that task can be performed again.

• Supervisors are required to perform inspections and audits, at least annually, to determine if their employees are following company procedures and NFPA 70E/Z462

• Even unqualified persons must have training in:

o How to recognize and avoid electrical hazards they may encounter

o How to operate electrical equipment

o What the hazards are associated with the use of such equipment

o What PPE may be required and when to use it

o How to inspect, maintain and store electrical PPE

o What the limitations are of electrical PPE

o What the hazards are associated with the use of such equipment

o What PPE may be required and when to use it

o How to inspect, maintain and store electrical PPE

o What the limitations are of electrical PPE


 

James R. White IS Training Director, Shermco Industries, Inc. for Fluke Corporation.This article has been lightly edited. 

 

Changing Scene

  • Prev
During the recently held IMARK Canada 2019 meeting in Niagara Falls, executives from 14 of the ...
Valard has been selected by Wataynikaneyap Power LPto provide engineering, procurement ...
The Canadian Apprenticeship Forum-Forum Canadien sur l’Apprentissage (CAF-FCA) has announced ...
Electricity Human Resources Canada has announced this year's keynote speakers for Agents of Change ...
Kiashke Zaaging Anishinaabek (KZA)/Gull Bay First Nation (GBFN) and Ontario Power Generation (OPG) ...
The BCEA's Woman's Network THRIVE Summit is taking place on October 4th at the Executive Inn ...
NSI Industries has announced the acquisition of electrical products manufacturer Bridgeport ...
The National Electrical Trade Council (NETCO)—jointly sponsored by International Brotherhood ...
IDEAL Electrical has launched its fourth annual national competition to find the best ...
IDEAL Industries Canada has announced the appointment of Sean Bernard as Regional Sales Manager to ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

SoneparSonepar Canada has announced the launch of new mobile applications for Gescan Vallen, Sesco and Lumen.

The mobile apps were officially released as of June of this year and features barcode scanning, access to pricing, product availability, store locator and much more – 24 hours a day, 7 days a week.

The new mobile app is changing the way customers can interact with the Operating Companies within Sonepar Canada. The barcode scanning functionality is a popular feature amongst customers allowing them to scan an item easily and add it to their cart.

 

Read More

 

 

 

Fredericton Transmission LineNB Power recenly announced it will seek approval to build a new transmission line in the Fredericton area, which will improve the reliability of the power grid in the region for approximately 25, 000 customers.

The new proposed 15-kilometre transmission line will run from the Rainsford Substation, in Fredericton, to the Mactaquac Terminal.

“NB Power strives to offer its customer a reliable power grid that meets or exceeds all utility standards,” said NB Power’s President and CEO, Gaëtan Thomas. “This will increase transmission reliability for customers in the Fredericton region with fewer interruptions that can be restored within minutes rather than hours or days.”

Read More

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Emergency Lighting PrinciplesBy Kevin Smee, Vice President Sales at AimLite

Most of us take light for granted. It has become so ubiquitous and cheap to use that we don’t really stop to think about emergencies. Thankfully most buildings are required by law since 1974 to be equipped with emergency lighting that automatically activates during power failures to facilitate our exit.

Emergency lighting is only one component of a building’s life safety systems, but perhaps one of the most important. 

 

 

Read More  

 

Open Office DesignOpen office design has exploded in popularity over the last 20 years. In fact, the New Yorker magazine claims that approximately 70% of all offices now have an open floor plan.[1]

How did we get here?

Although open offices have been around since the mid-1700s, the cubicle culture developed by Hermann Miller in 1964 became very popular in the 1980s and 1990s. By the early 2000s, open office design started to re-emerge in an effort to encourage more collaboration and Silicon Valley was among the first to embrace sleek, open office workspaces as the norm.

Read More

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
Standard Stanpro’s LED Tapes work on direct line voltage 120V and can easily be installed ...
Standard Stanpro’s FLUO LED is designed for 120 V applications and is easy and quick to ...
The LCAN series is an indoor and outdoor surface mount with V-type light distribution.   ...
HPS Sentinel G ventilated stand-up distribution transformers meet the latest federally mandated ...
Advanced Performance in a Classic Form Factor The UFIT LED Low Bay is the perfect combination of a ...
The clean and elegant design of EG series 1X4FT led flat panel light provides a modern alternative ...
Signify has announced new smart light products, including an upgraded Hue Go, the Smart button and ...
HomeWorks by Lutron is a lighting and shading control solution for luxury homes.   ...
Signify unveiled its brand-new Philips Hue Filament collection, perfect for those who want to bring ...
These LED lamps are designed to meet or exceed the standards set out in the California Energy ...

 

EikoThese LED lamps are designed to meet or exceed the standards set out in the California Energy Commission’s Title 20 and Title 24 (JA8) Appliance Efficiency Regulations.

FEATURES

  • MR16 GU5.3 and GU10 base; B11 Decorative E12 and E26 base
  • 80% more efficient and 30x longer life than standard incandescent
  • Shatter-resistant plastic housing for reduced risk of injury and breakage
  • Compatible with a wide array of dimmers
  • ANSI construction compliant

Read More

 

 

Peers & Profiles

  • Prev
Ali Heighton is the Program Coordinator for IBEW Local 37 who has found success as a young ...
Flextherm was founded in 1991 by current company President, Philippe Charron. For more than 25 ...
Ouellet Electric Heating began humbly in 1960 with Charles-Emile Ouellet, who started manufacturing ...
Justin Harris is a Programmer/Electrician for COREngineering, a New Brunswick based mechanical ...
Bill Maki is an Electrical Engineer from Thunder Bay, Ontario working as a Control Systems ...
Benedict Electrical Contracting Limited is a locally owned and operated family business in Owen ...
Spark Power Corp. is one of North America’s leading independent providers of integrated ...
Marcia Ranger is a master construction and maintenance electrician, as well as a college professor ...
Con’s Electric Company Limited was established in 1985. Based in Timmins Ontario, only 700 ...
Mark Unsworth is an electrical engineer with over 35 years of experience in project management, ...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil