EIN Bill Burr Code 400By William (Bill) Burr

Section 42 — Electric Welders 

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the Code. These notes are based on the 25th edition.

Rule 42-000 Scope – states that Section 42is a supplementary or amendatory section of the code and applies to the installation ofelectric welders. The CEC Handbook provides additional notes and diagrams to better explain this section. There are two main types of welders - arc and resistance welders. Arc welders use a sacrificial rod to weld the metal target material together. Resistance welders fuse the metal target material together. Arc welders are divided further into transformer and motor-generator types.

Rule 42-002 Special terminology – contains definitions for special terms that apply to Section 42 that are not defined in Section 0 such as: actual primary current, duty cycle, and rated primary current. These terms will be important when calculating the ampacity of the supply conductors for welders.

Rule 42-004 Receptacles and attachment plugs – along with Appendix B notesoutlines that: 

  • where receptacles are installed for the plug and cord-connection of a portable welder, the ampacity rating of the overcurrent protection for the circuit can be more than the rating of the receptacle, but the receptacle must have a rating equal to or greater than the ampacity of the supply cable required for the primary current of the cord-connected welder. This is important because the high instantaneous inrush start-up current of the welder will exceed the branch circuit conductor ampacity. This prevents nuisance tripping. 
  • where a welder receptacle is installed, it must be labeled to indicate:
  • the receptacle is for a welder connection only,
  • the AWG size of the insulated conductors,
  • whether the insulated supply conductor is Cu/Al,
  • the conductor insulation designation and temperature rating, and
  • the ampere rating of the overcurrent device protecting the receptacle insulated supply conductors based on the duty rating (80% or 100%) 

Transformer arc welders and inverter welders

Rule 42-006 Supply conductors – provides the factors in determining the ampacity of insulated supply conductors for transformer type arc or invertor welders. The ampacity depends on the duty cycle of a single welder, as in sub-rule (1) and the demand factors where a group of welders are supplied by one circuit as in sub-rule (2).  The CEC Handbook contains Table 42A that shows the correlation between duty cycle and demand factor and determination of the demand factor for multiple welder installations.

Rule 42-008 Overcurrent protection for transformer arc welders and inverter welders – specifies the factors to be used in calculating the rating of circuit overcurrent protection per the ampacity of insulated supply conductors and welders as in sub-rule (1). Sub-rule (2) outlines the factors in calculating the rating of the overcurrent protection for the insulated supply conductors using Tables 1,2,3, or 4Sub-rule (3) provides the factors in calculating the rating of the overcurrent protection for a feeder supplying a group of transformer arc welders or inverter welders.

Rule 42-010 Disconnecting means – requires that where there is no integral disconnect on the welder, one must be provided to disconnect the supply conductors and must have sufficient current rating capacity to accommodate the overcurrent protection.

Motor-generator arc welders 

Rule 42-012 Conductors, protection, and control of motor-generator arc welders – specifies that the rules of Section 4 and Section 28 generally apply to the determination of insulated supply conductor ampacity, and selection of protection and control of that welder by the applicable factors from Table 42B. The CEC handbook outlines methods of calculation of duty related demand factors through Table 42B.

Resistance welders 

Rule 42-014 Supply conductors for resistance welders - providesthe factors in determining the ampacity of insulated supply conductors depending on the primary current or duty cycle of either an individual seam resistance welder or an automatically fed resistance welder. Table 42C and the CEC Handbook shows the relationship between duty cycle and demand factors.

Rule 42-016 Overcurrent protection – specifies the factors in determining the rating of the overcurrent protection based on the rated primary current of the welder and the allowable ampacity of the insulated supply conductors based on Tables 1,2,3 or 4. The CEC Handbook outlines methods of calculation of duty related demand factors through Tables 42A, B, and C.  For determining the rating of overcurrent Protection for a group of resistance welders use the factors contained in rule 42-014.

Rule 42-018 Control of resistance welders – requires that a resistance welder have a disconnecting switch or circuit breaker rated for the capacity of the insulated supply conductors to isolate the welder from the supply circuit.

Rule 42-020 Nameplate data for resistance welders – requires data specific to the resistance welder to be provided on the nameplate including rated KVA at 50% duty cycle, maximum and minimum open-circuit secondary voltage, short circuit current and the throat and gap setting.

In the next installment, we will be discussing Section 44 — Theatre installations

[1] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

[1] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Changing Scene

  • Prev
 Canada’s National Electrical Trade Council (NETCO) is pleased to announce that IDEAL ...
The Government of Saskatchewan is engaging the public to help ensure health and safety legislation ...
Despite electrical shock being a serious and potentially dangerous event, it is frequently ...
Acuity Brands, Inc. has announced its Care222® filtered far-UVC module with patent-pending ...
LEDVANCE, the makers of SYLVANIA general lighting in the United States and Canada, recently ...
The federal governemnt launched a Call for Proposals under the new Apprenticeship Service, to ...
ECAO and OEL are working on obtaining more contractor experiences with the ESA permit system. ...
Agents of Change is an event for stakeholders from Canada's electricity and beyond to build ...
Schneider Electric is introducing a personalized digital experience for logged in customers ...
Teledyne Technologies Incorporated announced the successful completion of the acquisition of FLIR ...


 

SaskatchewanThe Government of Saskatchewan is engaging the public to help ensure health and safety legislation meets the needs of employers and workers in the province. From August 16 to October 18, 2021 citizens can provide input on part III (occupational health and safety) of The Saskatchewan Employment Act.

"Our province has a plan for growth that includes ensuring we have safe and healthy workplaces" Labour Relations and Workplace Safety Minister Don Morgan said. 

 


Read More


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

Desert HomeA combination of stunning design, a spectacular desert setting, and exceptional architectural lighting is a winning combination for a private residence just outside of St. George, Utah. JRC Lighting was hired by the homeowner to create the lighting concept for the showpiece home.

"The house has an almost industrial look to it, with a focus on clean lines," said Kevin Meredith, principal at JRC Lighting. "My goal was to keep the lighting understated and let the architecture, and the views, sell themselves.”

 

Read More


 

 

David GordonBy David Gordon

This summer EiKO is launching its Z10 product offering. I know, what is Z10 other than the sports cars some of us remember (’69 Z10 Camaro or a 2009 BMW Z10, but let’s go with an American muscle car!)?

So, since it seemed like a sports car “name” (since sports car naming seems to be in numbers), we reached out to Sarah Eastman, VP Marketing for EiKO, who shared that Z10 is an alliance of manufacturers who have developed standards to support an easier lighting controls process within fixtures (remember, I’m not a product maven).
Read More


 

Product News

  • Prev
Atkore’s FRE Composites® BreathSaver® XW fiberglass conduit system uses a non-metallic, phenolic ...
Atkore’s FRE Composites® fiberglass conduit recently experienced increased demand in above- and ...
4 speed Supreme Series fan with an optional speed controller DMD-LED-3.      
Set up, switch out and print faster than you ever imagined with the BradyPrinter i5300 ...
Siemens whole-house protection devices defend the sensitive electronics that are susceptible to ...
LSP05GI Series LED Lighting Surge Protection Modules are designed for use in outdoor and commercial ...
Milwaukee Tool expands their Lighting Solutions once again with the introduction of the M12™ ...
M12™ Cable Stripper Kit for Cu THHN / XHHW aims to improve the cable stripping experience. With no ...
Here’s the easy, NEAT way to mount single or two-gang boxes between wood or metal studs with ...
LEDVANCE, the makers of SYLVANIA general lighting in the United States and Canada, has released the ...

 

Milwaukee M12 Cable StripperM12™ Cable Stripper Kit for Cu THHN / XHHW aims to improve the cable stripping experience. With no exposed blades, the cordless cable stripper provides safer stripping than with a knife. The cable stripper's compact, right-angle design allows you to maneuver it more easily in tight spaces with less strain on the wrist. The bushing design and adjustable depth gauge deliver cleaner, more accurate and consistent strips across all sizes.

The cable jacket stripping tool is not only compatible with all MILWAUKEE® bushings but is also compatible with competitive quick-change bushings.

 

Read More


 

 

Incoplas HybridThe Incoplas® LED Hybrid is a durable multi-purpose and corrosion-resistant LED lighting solution that can be used in heavy industrial applications where hazardous location lighting is required.

Certifications

Class 1:

Flammable Gases and Liquids

Division 2: The hazardous atmosphere is only available infrequently (i.e. in case of spill).

 

Read More


 

 

EarthTronics 25-Watt Emergency Driver for Linear HighbayEarthTronics LED emergency drivers regulate the power supplied to the LED fixture so that it can operate as a light source in the event of a power failure. The purpose of emergency lighting is to ensure that lighting is provided promptly, automatically and for a suitable time when the normal power supply fails.

This insures that people within the building can evacuate safely in the event of an emergency. All EarthTronics emergency drivers meet specific UL, CSA and NFPA requirements. Always consult local code requirements when specifying emergency lighting products.

Read More


 

Peers & Profiles

  • Prev
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...
As a 34-year-old female owner of an electrical contracting business, Danielle Gray may be unique. ...
Mark Klein is Co-President of Klein Tools, managing Sales & Marketing activities, alongside ...
Bryan Smith started his now 20-year career at the ground floor, so to speak, as a draftsperson and ...
From small construction to sophisticated industrial projects, House of Electrical Supplies has been ...
Kyle Manfredi is the owner of ARK Electrical alongside his wife, Shannon. Operating out of ...


EngWorksBy Blake Marchand

EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After a short time we realized there was a niche in hazardous locations, in particular in hazardous area classification design requirements for various facilities. And also helping people understand just how the Canadian Electrical Code applies to hazardous locations.”

Given the complexity of hazardous locations, Bozek saw a need for education while working in the field and began developing training courses designed.

Read More


 

 

Eric TordjmanBy Blake Marchand

Headquartered in Concord, Ontario, Mercury Lighting services national retail, multi-residential/commercial property management, energy service companies (ESCO), and auto dealerships. “From design to specifications, we offer turn-key services that go beyond the typical distributor model,” explained Mercury Lighting Vice President, Eric Tordjman. Their value-added approach leverages well-established supplier relations to help clients find a lighting solution that suits their needs.

“How we differentiate ourselves is we’re lighting specific, we do very little in the way of electrical, and really emphasizing our expertise towards solutions selling...

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil