EIN Bill Burr Code 400The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook**, but will hopefully provide some help in navigating the Code.

Section 54 — Community Antenna Distribution and Radio and Television Installations

Rule 54-000 states that this is a supplementary or amendatory section of the code and applies to community antenna distribution, equipment for the reception of radio and television broadcast transmission, and equipment employed in the normal operation of a radio station licensed by the Government of Canada as an experimental amateur radio station. The section does not apply to equipment and antennas used for broadcast transmission and for coupling carrier current to power line conductors. Appendix B and the CSA CEC Handbook provide additional explanations and diagrams.

Rule 54-002 provides definitions for special terminology used, including cable distribution plant, customer distribution circuit, customer service enclosure, multitap and blocking device, that need to be referenced when reading this section.

Rule 54-004 specifies that community antenna distribution is used to distribute radio and television frequency signals commonly known as cable TV (CATV), and that rules 54-100 to 54-704 apply. Where other than a coaxial cable wiring system is employed, the requirements of Sections 56 or 60 prevail.

Rule 54-006 notes that generally equipment under this section is not required to be approved as per Rule 2-024 unless specifically specified in this section.

 Rule 54-008 specifies that rules 54-800 to 54-1006 apply to radio and television receiving equipment and amateur transmitting equipment.

Rule 54-010 explains that if insulated conductors or parts of community antenna distribution circuits are in a cable along with communication circuit conductors, then the rules of Section 60 – Electrical Communication Systems apply. Where protectors and grounding for the coaxial cables are required, then the rules of this Section 54 apply.

 Community antenna distribution

Rule 54-100 requires that all conductors used in community antenna distribution must be coaxial cable and, if installed in buildings, be selected in accordance with Rule 12-102 3).

 Rule 54-102 provides conditions and voltage and current limitations for using coaxial cable for supply to the customer service enclosure, and between two or more customer enclosures. Because the CATV cables enter buildings and are connected to televisions, radios and computers, the voltage and current levels must be limited to minimize shock and fire hazards.

In addition, cables and equipment must be bonded to ground, power blockers and locks installed on customer service enclosures, and any signal amplification must be energized by a class 2 transformer. Appendix B contains a sketch outlining the various limitations.

Rule 54-104 notes that, where installed in hazardous locations, all CATV circuits and equipment must also meet the requirements of Sections 18, 20 and 24.

Rule 54-106 specifies that if the CATV circuits are operated by a utility, within the scope of Section 60, they are not subject to electrical inspection. However, where transformers, amplifiers or current limiting devices are used, the junction with the electric supply is subject to inspection.

Rule 54-108 states that supports for cables on buildings must be suitable for the purpose.

Protection

Rule 54-200 requires that the outer conductive shield of coaxial cable be bonded to ground or be provided with a protective device close to the point of entry to a building, in case of accidental contact with lightning arrestor or insulated power conductors. Note also that the protector operation must not interrupt the building grounding system. 

Rule 54-202 provides the specifications and location for a protector device. Appendix B notes for 54-200 and 54-202 provide a description of the point of entry to a building.

Grounding

Rule 54-300 details the requirements for grounding the outer conductor or protector of a coaxial cable.

Rules 54-302 and 54-304 outline that the installation of grounding electrodes and connections conform generally with Section 10. The purpose of grounding CATV coaxial cable is for bleeding off, to ground, excess voltage from accidental energizing or lightning strikes, and not for a low-impedance fault current path. Therefore, the driven length of a rod electrical can be a minimum of 2 m.

Conductors within buildings

Rules 54-400 to 54-408 provide requirements for CATV cables in conformance with Section 12 in terms of separation from other insulated conductors, cables in a vertical shaft, penetration of fire separations, prohibited placement in ducts or plenum chambers, except as permitted by Rules 2-130 and 12-010, and, installation of raceways in accordance with Section 12.

Equipment

Rule 54-500 requires that community antenna distribution amplifiers and other power sources be readily accessible, adequately ventilated, connected to the system ground with a minimum No. 6 AWG copper conductor, and be provided with a lock or similar closing device.

Rule 54-502 provides that exposed equipment and terminations be located in accordance with Rule 2-202, except in a joint use room, where a 900-mm separation from adjustable electrical equipment is required.

Rule 54-504 notes that non-powered or exclusively coaxial powered equipment are considered grounded if effectively connected to the grounded coaxial cable shield.

Conductors outside of buildings

Rule 54-600 specifies that overhead CATV cables on poles conform to the Canadian Electrical Code, Part III.

Rule 54-602, permits CATV cables to pass over buildings, provided a minimum distance, vertically from the roof, is maintained at 2.5 m. In addition, CATV cables may not be attached or run within 2.5 m vertically of a roof, except for garage or auxiliary buildings.

Rule 54-604 requires that CATV cables on buildings be separated from:

  • insulated light or power conductors, not in cable or conduit, by at least 300 mm, or by a continuous non-metal-type raceway,
  • combustible material, by being supported on glass, porcelain, or other insulating material, except where the outer conductive sheath of the coaxial cable is grounded, and
  • other communication cables, attached to the same building, to prevent interference with maintenance operations, and not cause abrasion to the insulated conductors, strand, or equipment of the other system.

Rule 54-606 outlines that CATV cables entering buildings must pass through a non-combustible, non-absorptive insulating bushing, a metal raceway, or masonry.

Rule 54-608 requires a minimum separation of 2 m between CATV cables and lightning conductors on buildings.

Rule 54-610 requires CATV cables installed over or adjacent to swimming pools to conform to rules 68-054 and 68-056.

Underground circuits

Rule 54-700 requires that direct buried CATV cables be:

  • suitably designed for direct burial,
  • installed outside of the same vertical plane that contains differing cables other than communication cables, except when installed in accordance with the metal shield as per the last item in this list,
  • maintained at a minimum 300 mm horizontal separation from differing cables, other than communication cables, except when installed in accordance with the metal shield as per the last item in this list,
  • placed at a minimum depth of 600 mm, or 450 mm if rock bottom is encountered at a lesser depth,
  • reduced to 450 mm depth for service wires under parkways and lawns,
  • placed with a layer of sand 75 mm deep, both above and below the cable, if in rocky or stony ground,
  • placed at a minimum depth of 900 mm under an area that is subject to vehicular traffic,
  • reduced to 600 mm with mechanical protection consisting of a treated plank at least 38 mm thick placed over the cable, with first backfilling with 75 mm of sand or earth, containing no rocks or stones,
  • placed in a conduit, suitable for earth burial, placed to facilitate cable replacement and to minimize traffic damage, or
  • equipped with a metal shield, when in a common trench with random separation of insulated power cable operations at 750 V or less, and the CATV cables.

Rule 54-702 requires that underground raceway for CATV cables:

  • be separated from the electric power system by not less than 50 mm of concrete or 300 mm of well-tamped earth,
  • be located to maintain a minimum depth of 600 mm in areas subject to vehicular traffic and 450 mm in all other areas, or encased in concrete,
  • not terminate in the same maintenance hole used for an electric power system, unless all requirements of Clause 6 of CAN/CSA-C22.3 No. 7 are adhered to,
  • not be placed in the same raceway containing electric lighting, power, or Class 1 circuit conductors,
  • be suitable for wet locations,
  • enter the building above ground where practicable, and
  • be sealed with a suitable compound, in such a way that moisture and gas will not enter the building or will be suitably drained.

Rule 54-704 permits the bushings or raceways required by Rule 54-606 to be omitted where the entire street circuit is run underground and the circuit is placed to prevent contact with electric lighting, power, or Class 1 circuits of more than 300 V.

Receiving equipment and amateur transmitting equipment

Rules 54-800 and 54-802 require that the lead-in conductor from an outdoor antenna to a receiving station or an amateur transmitting station be provided with a lightning arrestor, that will drain static charges from the antenna, except where the lead-in cable sheath is grounded between the antenna and the entrance to the building, or the antenna is grounded.

For receiving stations, the lightning arresters must be located:

  • as near as practicable to the entrance of the cables to the building,
  • outside the building, or
  • inside the building between the point of entrance of the lead-in and the radio set or transformer, and,
  • not near combustible material, nor,
  • in a hazardous location.

Grounding for receiving equipment and amateur transmitting equipment

Rules 54-900 to 54-912 specify that grounding conductors must be:

  • copper, aluminum alloy, copper-clad steel, bronze or other corrosion resistant material, and may be bare,
  • securely fastened in place directly, but may be attached to the supporting surface without the use of insulating supports,
  • protected where exposed to mechanical damage,
  • run in as straight a line as is practicable from the lightning arresters or antenna mast, or both, to the grounding electrode, and
  • connected to a grounding electrode, as specified in Section 10, but may be run either inside or outside the building.

Rule 54-914 specifies that the protective grounding conductor providing mast ground and lightning arrestor connections is in accordance with Section 10.

Rule 54-916 permits a single grounding conductor to be used for both protective and operating purposes. The disconnection of the operating ground must not affect the protective ground circuit.

Rule 54-918 requires that exposed non-current-carrying metal parts of radio and television equipment installed in basic, intermediate, and critical care areas of hospitals as defined in Section 24, be bonded to ground as per Rule 24-104(7).

Rule 54-920 requires that radio interference eliminators, capacitors and noise suppressors connected to power leads be protected from mechanical damage.

Rule 54-922 notes that masts, metal support structures, and antenna frames for receiving stations must be bonded to ground in accordance with Section 10.

Transmitting stations

Rule 54-1000 specifies that transmitters must be enclosed in a metal frame or grille, and thoroughly shielded or separated from the operating space by a barrier or other equivalent means.

Rule 54-1002 requires the bonding to ground of:

  • all exposed metal parts of transmitters,
  • external metal handles,
  • controls accessible to the operating personnel, and
  • accessories such as microphone stands.

Rule 54-1004 requires that all access doors of transmitters be provided with interlocks, that will disconnect all voltages in excess of 250 V, when any access door is opened.

Rule 54-1006 states that all audio-amplifiers located outside the transmitter housing be suitably housed and readily accessible and adequately ventilated.

In the next installment, we will be discussing Section 56 — Optical fiber cables

[i] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

[ii] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Are You Ready For Winter?

Schneider

 

A special offer for you this season

Buy $350 worth of eligible Surge Protection Devices from Schneider Electric and get a free jacket. Hurry Now! Offer ends February 28th 2022.

CTA: Get Offer Now!


 

 

 

 

 

Top Recurring Revenue Business Ideas for Electricians

Simpro

We’ve all heard the saying, “Money doesn’t grow on trees.” Sadly, there’s no way to plant dollar bills for your electrical business that will grow into hundreds overnight (wouldn’t that be nice?).

While I can’t gift you a money tree, after talking to dozens of our electrical customers, I can tell you that one of the best ways to grow your business is through recurring revenue.

What is Recurring Revenue and Why Should Your Electrical Business Have It?

Recurring revenue is predictable, stable revenue that comes into your business at regular intervals. It helps you better maintain cash flow, reduce reliance on one-time sales and most importantly, allows you to forecast revenue so that you can make better decisions for the future of your business. 

Read More


 


 

The EPLAN AdvantageWhat is EPLAN?

One platform, multiple solutions – the Eplan Platform offers engineering software such as Preplanning for systematic preliminary planning, Electric P8 for preparing circuit diagrams and Pro Panel for 3D enclosure planning, all from a single source. Standardised interfaces and integration processes enable continuous data flows throughout the value chain, with additional links to various system solutions from Rittal.

This year, EPLAN has introduced its new EPLAN Platform 2022 to help address challenges in the design, engineering and manufacturing phases of the panel building process...

Read More


 

Changing Scene

  • Prev
The 2021 Canadian Electrical Code, Part I (twenty-fifth edition) automatically comes into force on ...
The Ontario Electrical League (OEL) is celebrating 100 years of reliability within the electrical ...
ECAO and NECA have announced that on January 1 ECAO officially joined NECA as their 119th Chapter. ...
A virtual event hosted by CAF-FCA to engage employers about the business case for apprenticeship. ...
British Columbian organizations developing low-carbon building solutions can now apply for a third ...
More and more businesses, industries and people are going ‘grid independent.’ This means Licensed ...
CSA Group, a global leader in Testing, Inspection and Certification, has announced the opening of a ...
Sense announced a new standards-based open source effort to enable software to ...
In November, the 2021 Virtual AD Supplier Summit Industrial & Safety–Canada Division event saw ...
Electro-Federation Canada (EFC), through the support of its members, is proud to support university ...


EIN NECA ECAO 400ECAO and NECA have announced that on January 1 ECAO officially joined NECA as their 119th Chapter. Executive Director Graeme Aitken joined NECA CEO David Long on LinkedIn Live to announce the partnership.

Given the similarities between the two organizations, ECAO is looking to create more opportunities for its electrical contractor members and this further collaboration will allow them to facilitate that. As well as drawing on the educational opportunities that NECA can offer.

“What we’re looking for is integration, professionalism, but most importantly to expand our community."

Read more


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

 ESABy Blake Marchand

This technical Q&A was done as part of ESA’s annual Licence Holder Meeting on November 18th. A recording of the entire meeting is available online. The technical Q&A began with a general overview of ESA’s top 5 changes provided to the 2021 Canadian Electrical Code by Malcom Brown. 

Following that, Brown goes through a number of questions submitted by LECs (Licenced Electrical Contractors), covering several topics, including EV energy management systems, GCFI and AFCI protection, nuisance tripping for washing machines and microwaves, smoke alarm requirements, and common inspection defects.

Read More


 

Product News

  • Prev
Designed for use with non-metallic liquid-tight conduit type B. Produced from UV rated plastic for ...
 In ABB's ongoing commitment to offer superior value at every touchpoint, from ordering to ...
The IDEAL 61-517 GFCI Receptacle Tester is a 120V AC plug in outlet tester that indicates proper ...
The preassembled SCRG cable prevents ice build-up on roofs and gutters that could damage these ...
Low-dosage LED UVC device for continuous disinfection in occupied spaces provides an additional ...
Greenlee, part of Emerson’s professional tools portfolio, introduces the new ESG45LX Gator Hard ...
The Fluke 417D is accurate, durable, and easy to use—just point and shoot. The simple design and ...
Mercmaster™ LED Luminaires deliver exceptional efficiency, performance and advanced engineering. ...
The SSW Series of Sealed Screwless Wall Plates from SensorSwitch™ is designed to protect wall ...
The Fluke TiS75+ thermal camera offers features to help tackle almost anything teams face in the ...


Gator Hard CutterGreenlee, part of Emerson’s professional tools portfolio, introduces the new ESG45LX Gator Hard Metal Cutter, a tool solution for the high-voltage industry, featuring an industry-first shock-load damping system that minimizes released energy while making cuts.

The ESG45LX is ideal for overhead one-handed operation and cuts up to 1/2-inch Rebar (Schedule 60) and EHS Guy Strand and 5/8-inch Ground Rod and Standard Guy Strand. It has a compact, lightweight design, weighing less than eight pounds with battery, and is 33 percent lighter than an earlier model thanks to a redesigned flip-top style latch that reduces overall weight.

Read More


 

 

Peers & Profiles

  • Prev
Watt’s the Word is a recently launched Electrical Industry Podcast hosted by Zack Hartle and ...
Allana Kellett-Jamieson loves working in the electrical sector and is proud of the great focus ...
As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the ...
Karen Pullen knows what it’s like to be the only woman on a construction site, and as a proud ...
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...


Watt's The WordBy Blake Marchand

Charlie Harte is the Canadian President & CEO for LEDVANCE LLC, as well as holding the role of VP of Marketing & Customer Experience for the U.S. and Canada region. Harte was named as the Canadian President in February 2020 and not long after was also named as the VP of Marketing and Customer Experience. Our interview centered around his experience joining LEDVANCE right before the pandemic, how he approaches leadership, where LEDVANCE wants to find success, and his perspective on the broader industry.

Harte spent 30 years working for some top brands in the building materials industry where he honed a strong skill set in sales, marketing, strategic planning, business development, and leadership. He joined the organization a month before the global pandemic which provided a unique scenario. “You’re starting to lead an organization with whom you almost have no connection,” he noted.

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2022 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil