EIN Bill Burr Code 400The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook**, but will hopefully provide some help in navigating the Code.

Section 54 — Community Antenna Distribution and Radio and Television Installations

Rule 54-000 states that this is a supplementary or amendatory section of the code and applies to community antenna distribution, equipment for the reception of radio and television broadcast transmission, and equipment employed in the normal operation of a radio station licensed by the Government of Canada as an experimental amateur radio station. The section does not apply to equipment and antennas used for broadcast transmission and for coupling carrier current to power line conductors. Appendix B and the CSA CEC Handbook provide additional explanations and diagrams.

Rule 54-002 provides definitions for special terminology used, including cable distribution plant, customer distribution circuit, customer service enclosure, multitap and blocking device, that need to be referenced when reading this section.

Rule 54-004 specifies that community antenna distribution is used to distribute radio and television frequency signals commonly known as cable TV (CATV), and that rules 54-100 to 54-704 apply. Where other than a coaxial cable wiring system is employed, the requirements of Sections 56 or 60 prevail.

Rule 54-006 notes that generally equipment under this section is not required to be approved as per Rule 2-024 unless specifically specified in this section.

 Rule 54-008 specifies that rules 54-800 to 54-1006 apply to radio and television receiving equipment and amateur transmitting equipment.

Rule 54-010 explains that if insulated conductors or parts of community antenna distribution circuits are in a cable along with communication circuit conductors, then the rules of Section 60 – Electrical Communication Systems apply. Where protectors and grounding for the coaxial cables are required, then the rules of this Section 54 apply.

 Community antenna distribution

Rule 54-100 requires that all conductors used in community antenna distribution must be coaxial cable and, if installed in buildings, be selected in accordance with Rule 12-102 3).

 Rule 54-102 provides conditions and voltage and current limitations for using coaxial cable for supply to the customer service enclosure, and between two or more customer enclosures. Because the CATV cables enter buildings and are connected to televisions, radios and computers, the voltage and current levels must be limited to minimize shock and fire hazards.

In addition, cables and equipment must be bonded to ground, power blockers and locks installed on customer service enclosures, and any signal amplification must be energized by a class 2 transformer. Appendix B contains a sketch outlining the various limitations.

Rule 54-104 notes that, where installed in hazardous locations, all CATV circuits and equipment must also meet the requirements of Sections 18, 20 and 24.

Rule 54-106 specifies that if the CATV circuits are operated by a utility, within the scope of Section 60, they are not subject to electrical inspection. However, where transformers, amplifiers or current limiting devices are used, the junction with the electric supply is subject to inspection.

Rule 54-108 states that supports for cables on buildings must be suitable for the purpose.

Protection

Rule 54-200 requires that the outer conductive shield of coaxial cable be bonded to ground or be provided with a protective device close to the point of entry to a building, in case of accidental contact with lightning arrestor or insulated power conductors. Note also that the protector operation must not interrupt the building grounding system. 

Rule 54-202 provides the specifications and location for a protector device. Appendix B notes for 54-200 and 54-202 provide a description of the point of entry to a building.

Grounding

Rule 54-300 details the requirements for grounding the outer conductor or protector of a coaxial cable.

Rules 54-302 and 54-304 outline that the installation of grounding electrodes and connections conform generally with Section 10. The purpose of grounding CATV coaxial cable is for bleeding off, to ground, excess voltage from accidental energizing or lightning strikes, and not for a low-impedance fault current path. Therefore, the driven length of a rod electrical can be a minimum of 2 m.

Conductors within buildings

Rules 54-400 to 54-408 provide requirements for CATV cables in conformance with Section 12 in terms of separation from other insulated conductors, cables in a vertical shaft, penetration of fire separations, prohibited placement in ducts or plenum chambers, except as permitted by Rules 2-130 and 12-010, and, installation of raceways in accordance with Section 12.

Equipment

Rule 54-500 requires that community antenna distribution amplifiers and other power sources be readily accessible, adequately ventilated, connected to the system ground with a minimum No. 6 AWG copper conductor, and be provided with a lock or similar closing device.

Rule 54-502 provides that exposed equipment and terminations be located in accordance with Rule 2-202, except in a joint use room, where a 900-mm separation from adjustable electrical equipment is required.

Rule 54-504 notes that non-powered or exclusively coaxial powered equipment are considered grounded if effectively connected to the grounded coaxial cable shield.

Conductors outside of buildings

Rule 54-600 specifies that overhead CATV cables on poles conform to the Canadian Electrical Code, Part III.

Rule 54-602, permits CATV cables to pass over buildings, provided a minimum distance, vertically from the roof, is maintained at 2.5 m. In addition, CATV cables may not be attached or run within 2.5 m vertically of a roof, except for garage or auxiliary buildings.

Rule 54-604 requires that CATV cables on buildings be separated from:

  • insulated light or power conductors, not in cable or conduit, by at least 300 mm, or by a continuous non-metal-type raceway,
  • combustible material, by being supported on glass, porcelain, or other insulating material, except where the outer conductive sheath of the coaxial cable is grounded, and
  • other communication cables, attached to the same building, to prevent interference with maintenance operations, and not cause abrasion to the insulated conductors, strand, or equipment of the other system.

Rule 54-606 outlines that CATV cables entering buildings must pass through a non-combustible, non-absorptive insulating bushing, a metal raceway, or masonry.

Rule 54-608 requires a minimum separation of 2 m between CATV cables and lightning conductors on buildings.

Rule 54-610 requires CATV cables installed over or adjacent to swimming pools to conform to rules 68-054 and 68-056.

Underground circuits

Rule 54-700 requires that direct buried CATV cables be:

  • suitably designed for direct burial,
  • installed outside of the same vertical plane that contains differing cables other than communication cables, except when installed in accordance with the metal shield as per the last item in this list,
  • maintained at a minimum 300 mm horizontal separation from differing cables, other than communication cables, except when installed in accordance with the metal shield as per the last item in this list,
  • placed at a minimum depth of 600 mm, or 450 mm if rock bottom is encountered at a lesser depth,
  • reduced to 450 mm depth for service wires under parkways and lawns,
  • placed with a layer of sand 75 mm deep, both above and below the cable, if in rocky or stony ground,
  • placed at a minimum depth of 900 mm under an area that is subject to vehicular traffic,
  • reduced to 600 mm with mechanical protection consisting of a treated plank at least 38 mm thick placed over the cable, with first backfilling with 75 mm of sand or earth, containing no rocks or stones,
  • placed in a conduit, suitable for earth burial, placed to facilitate cable replacement and to minimize traffic damage, or
  • equipped with a metal shield, when in a common trench with random separation of insulated power cable operations at 750 V or less, and the CATV cables.

Rule 54-702 requires that underground raceway for CATV cables:

  • be separated from the electric power system by not less than 50 mm of concrete or 300 mm of well-tamped earth,
  • be located to maintain a minimum depth of 600 mm in areas subject to vehicular traffic and 450 mm in all other areas, or encased in concrete,
  • not terminate in the same maintenance hole used for an electric power system, unless all requirements of Clause 6 of CAN/CSA-C22.3 No. 7 are adhered to,
  • not be placed in the same raceway containing electric lighting, power, or Class 1 circuit conductors,
  • be suitable for wet locations,
  • enter the building above ground where practicable, and
  • be sealed with a suitable compound, in such a way that moisture and gas will not enter the building or will be suitably drained.

Rule 54-704 permits the bushings or raceways required by Rule 54-606 to be omitted where the entire street circuit is run underground and the circuit is placed to prevent contact with electric lighting, power, or Class 1 circuits of more than 300 V.

Receiving equipment and amateur transmitting equipment

Rules 54-800 and 54-802 require that the lead-in conductor from an outdoor antenna to a receiving station or an amateur transmitting station be provided with a lightning arrestor, that will drain static charges from the antenna, except where the lead-in cable sheath is grounded between the antenna and the entrance to the building, or the antenna is grounded.

For receiving stations, the lightning arresters must be located:

  • as near as practicable to the entrance of the cables to the building,
  • outside the building, or
  • inside the building between the point of entrance of the lead-in and the radio set or transformer, and,
  • not near combustible material, nor,
  • in a hazardous location.

Grounding for receiving equipment and amateur transmitting equipment

Rules 54-900 to 54-912 specify that grounding conductors must be:

  • copper, aluminum alloy, copper-clad steel, bronze or other corrosion resistant material, and may be bare,
  • securely fastened in place directly, but may be attached to the supporting surface without the use of insulating supports,
  • protected where exposed to mechanical damage,
  • run in as straight a line as is practicable from the lightning arresters or antenna mast, or both, to the grounding electrode, and
  • connected to a grounding electrode, as specified in Section 10, but may be run either inside or outside the building.

Rule 54-914 specifies that the protective grounding conductor providing mast ground and lightning arrestor connections is in accordance with Section 10.

Rule 54-916 permits a single grounding conductor to be used for both protective and operating purposes. The disconnection of the operating ground must not affect the protective ground circuit.

Rule 54-918 requires that exposed non-current-carrying metal parts of radio and television equipment installed in basic, intermediate, and critical care areas of hospitals as defined in Section 24, be bonded to ground as per Rule 24-104(7).

Rule 54-920 requires that radio interference eliminators, capacitors and noise suppressors connected to power leads be protected from mechanical damage.

Rule 54-922 notes that masts, metal support structures, and antenna frames for receiving stations must be bonded to ground in accordance with Section 10.

Transmitting stations

Rule 54-1000 specifies that transmitters must be enclosed in a metal frame or grille, and thoroughly shielded or separated from the operating space by a barrier or other equivalent means.

Rule 54-1002 requires the bonding to ground of:

  • all exposed metal parts of transmitters,
  • external metal handles,
  • controls accessible to the operating personnel, and
  • accessories such as microphone stands.

Rule 54-1004 requires that all access doors of transmitters be provided with interlocks, that will disconnect all voltages in excess of 250 V, when any access door is opened.

Rule 54-1006 states that all audio-amplifiers located outside the transmitter housing be suitably housed and readily accessible and adequately ventilated.

In the next installment, we will be discussing Section 56 — Optical fiber cables

[i] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

[ii] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Title: Ready, Set, Scale: How to Grow Your Field Service Business

SimProThrough many trials and tribulations, you’ve grown your business to where it is today. It’s taken blood, sweat, tears, long hours and sacrifice. But, it’s all been worth it to have something which you can call your own. It’s even more worth it when you can finally take that next step to grow your business even further and expand your service, project and maintenance work.

That moment when your hard work has finally paid off and you’re able to take your field service business to the next level. But, then it hits you - you’re not sure how to take those next steps or what you might need to make sure you don’t fail.

Read More


 

Become a Wiser Approved Installer

Schneider

Get access to exclusive benefits, product discounts and resources that will help you drive more business, and lower energy bills for your clients.

 

 

 

 

 

 

 

 

Read More


 

Switch to Smart, Switch to Easy, Switch to Beautiful

Schneider Connected LivingScrewless wall plates. Smart Outlets. Square D™ Switches and Receptacles are raising the bar on aesthetics, ease of installation, remote lighting control and connectivity.

 

 

 

 

 

 

 

Read More


 

Liteline Continues Canadian Investment

EIN BC Liteline 400Adding continued investment in Canada to its core foundation of innovative Design, installation efficiency, and personal customer service, Liteline has just announced the opening of its 12,729 square foot Showroom and Lighting Distribution Center in Langley BC.

The new Liteline Facility is located at 26550 Gloucester Way, Unit A110 and will house the new Liteline Distribution Center along with a product showroom. Stocking our 2-day QuickShip items, this new facility will service B.C. to Saskatchewan, as well as the Pacific Northwest and California in the United States allowing product to be delivered faster.

Read More


 

Changing Scene

  • Prev
E.B. Horsman & Son (EBH) has announced their Victoria location will be officially moving to a ...
 The Maritime’s largest Mechanical and Electrical event took place last Wednesday and ...
IDEAL INDUSTRIES, INC. is calling all professional and student-apprentice electricians to come out ...
Vivi White has been appointed to the Board of Directors of the Electrical Safety Authority ...
The Sonepar Ontario Region is proud to announce the relocation of their SESCO Central Distribution ...
The Electrical Safety Authority (ESA) is looking for a seasoned business executive drawn from an ...
David Rellinger, Vice President of Systems Transformation for Schneider Electric (SE), has been ...
The National Electrical Trade Council (NETCO) is pleased with the direction of the 2022 budget with ...
The Executive of Gerrie Electric Wholesale Limited is very pleased to announce the acquisition of ...
The Labour Mobility Tax deduction will provide tax recognition on up to $4000 per year, in eligible ...


Vivi WhiteVivi White has been appointed to the Board of Directors of the Electrical Safety Authority (ESA) by the Honourable Ross Romano, Minister of Government and Consumer Services.

“As Chair, I am pleased that the Ontario Government recently appointed Vivi White to the Board,” said Annette Bergeron. “The Electrical Safety Authority’s efforts over the years have greatly improved the safety of the people of Ontario. It’s an important mandate and requires a strong, talented and diverse board as we transform into a modern regulator.”

 

Read more


 

Omnicable joins ETIMETIM North America announced that OmniCable has joined the product classification standards organization. Headquartered in West Chester, PA, OmniCable has 24 locations throughout North America, and also owns Houston Wire & Cable (HWC). The company partners with many electrical manufacturers and only sells to distributors.

According to John Dean, Director of Marketing & E-Commerce, OmniCable/HWC, “The wire and cable industry is often called commodities, but there are very distinct features and attributes for the different products our manufacturers produce. 

Read More

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

FlukeElectrical distribution problems are not always immediately identified as issues with power quality. An example of this is a thermal-magnetic circuit breaker. When it trips, the indication is generally a short circuit, ground fault, or overload. At times this can be put down to an old breaker that needs replacing.

However, it’s important to investigate the types of loads on the system and monitor harmonics for a potential disturbance. This article explores common issues with power quality and how to troubleshoot those issues.

 

 

Read More


 

EIN Romex 12 2 Recall 400This recall involves a yellow electrical wire, 12/2 NMD90 75M Romex SIMpull cable, sold by the spool. Products were also sold at Home Depot designated as article 108196.  Only cables with a time stamp between 12:41 and 18:02 are affected by this recall. 

The recalled product contains a neutral wire that is a smaller 14-gauge wire, contrary to the stamp on the wire identifying both the neutral and “hot” wires as 12-gauge (i.e., "12/2"). 

The recalled product contains a 14-gauge neutral wire instead of 12-gauge (as labelled), thus it may not perform as expected in 12-gauge applications, resulting in a risk of those applications having impaired performance and/or compliance with safety codes or standards.

Go HERE for more information


 

Product News

  • Prev
The SYM-IN "In Table" model provides an attractive user interface while solid construction ...
The NEW Contractor Select™ version of the Juno Podz™ Canless Downlight is now easier than ever ...
Introducing the NEW Hi-Tech Valiant™ full-range current-limiting fuse for fire mitigation. No one ...
Appleton™ explosionproof and dust-ignition proof GR, GRF and GRTS conduit outlet boxes are ...
Southwire's new 100' LED string lights with 12,000 Lumens.    
Help provide comfort and functionality to your bathroom with the addition of the Broan BHF110 ...
The PWB-CMU8 is the first dedicated Masonry Wall Box engineered for installation in 8” block walls. ...
Now with pre-sized labels and even more materials to take on the toughest on-site labelling jobs. ...
The STACK Family is now complete! These four performance-tiered solutions were designed to help you ...
This 8’’ boot with internal metatarsal protection has a ¾ welt construction and heel stabilizer ...


Greenlee Mobile Bending Table for 881 Series Hydraulic BendersGreenlee is bringing secure and easy-to-transport conduit bending capabilities to jobsites with the introduction of its Mobile Bending Table for 881 Series Hydraulic Benders. The new product combines the latest in anti-theft protection with enhanced mobility, easy set-up and quick teardown.

“Electricians are constantly trying to do work more efficiently. Anytime we can shave time off a job, it’s a win – and this product delivers that with easier set-up and portability. At the same time, we know that protecting equipment from theft is an issue for a lot of tradespeople. The new Greenlee Mobile Bending Table for the 881 Series Hydraulic Benders is our latest solution to help professionals safeguard their investments and increase productivity,” 

Read More


 

 

Klein Tools Upgraded Testing KitKlein Tools introduces the Premium Electrical Test Kit.

Premium Electrical Test Kit (Cat. No. 69355)

  • Refreshed kit that features three new product releases geared towards a variety of electrical testing applications.
  • Kit includes instructions and all required batteries.

Manual-Ranging Digital Multimeter with Right-Angle Test Leads (Cat. No. MM320 – Exclusive to Cat. No. 69355 and Cat. No. MM320KIT)

  • Measures up to 600V AC/DC voltages, 10A DC current and 2-ohm resistance
  • Also tests batteries, diodes and continuity.

Read More


 

 

Brady M211Design, preview and print – all from your phone. Simple and intuitive, the M211 Label Printer is built for the job site, running all day on a full charge while resisting drops, shocks and crushes.

  • Simple. Easy. Intuitive.  Seamlessly design, preview and print labels from the industry leading Express Labels App on your familiar smartphone and swiftly connect to your printer.
  • Label it once.  Now with both pre-sized and continuous labels in 90+ cartridges, filled to the brim with reliable, tested and dedicated label materials that stay attached and remain legible on every surface and in any environment.

 

Read More


 

Peers & Profiles

  • Prev
Watt’s the Word is a recently launched Electrical Industry Podcast hosted by Zack Hartle and ...
Allana Kellett-Jamieson loves working in the electrical sector and is proud of the great focus ...
As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the ...
Karen Pullen knows what it’s like to be the only woman on a construction site, and as a proud ...
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...


Brent NeillyBy Blake Marchand

Brent Neilly is the Group Marketing Manager with Milwaukee, he has a background in business communications with a B.A. from Brock University, as well as experience working in the construction industry.

“When I joined TTI (Milwaukee’s parent company) it was kind of a perfect match, I had some marketing knowledge from my business degree and some industry experience from working in the trades.” Neilly gained his experience covering an area from Orillia to Timmins, Ontario when he first joined the company as a Field Sales Rep, as well as on their Job Site Core Trade Specialists in the GTA where he found his niche working with utility clients. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2022 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil