Guide to the Canadian Electrical Code, Part I — Instalment 37

Bill Burr

 

May 7, 2018

By William (Bill) Burr

In this article: Section 74 — Airport installations. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating the code.

Airport installations are series-type circuits that differ from other multiple-type circuits in that the regulator supplying them provides a constant current, variable voltage supply regardless of the load. The regulator does not respond to ground faults in a normal fashion. A single ground fault does not affect the whole system. Two or more ground faults affect only a portion of the system or a reduction in lighting intensity. A ground counterpoise is provided to protect service personnel from touch voltages when repairing or replacing broken luminaires. The CSA Handbook provides an in-depth explanation of this technology.

Rule 74-000 notes that this is a supplementary or amendatory section of the code and applies to installation of series-type constant-current circuitry supplying airport visual aid systems, including airport runway, taxiway, and approach lighting. Appendix B notes that these installations be designed by a civil engineer in accordance with good engineering practice and that the design be acceptable to the airport authorities.

Rule 74-002 contains definitions for special terminology used in this section for ground counterpoint, mounting stake, series isolating transformer, and transformer housing. It is important to understand these terms because of the special electrical characteristics of the series-type circuits used in these installations.

Rule 74-004 specifies the wiring methods for airport installations and includes:

  • type ASLC cables for the series system
  • using requirements of rule 12-012 and Table 53 for buried cables in public areas of airports
  • for areas not accessible to the public, single conductors and cables must be installed
    • at least 450 mm deep when installed in raceway
    • at least 450 mm deep and covered with at least 75 mm of sand or screened earth above and below the conductors when direct buried
    • with mechanical protection consisting of rigid conduit or concrete encased raceway buried at least 600 mm deep when installed under runways, taxiways, aprons and roads
  • where installed within a concrete or asphalt surface must be in a raceway
  • when directly buried in a trench have
    • 75 mm lateral separation between different series circuits
    • 300 mm lateral separation from low-voltage or control cables
    • 75 mm vertical separation in crossovers
    • 300 mm vertical separation of low-voltage cables crossing over in the upper position
  • Identifying each cable with a cable marker at each point where the cables are accessible at maintenance holes, transformer housings and other similar locations.

Rule 74-006 requires that direct buried series isolating transformers:

  • are installed so that the transformer and primary leads are a minimum depth of 450mm
  • that secondary conductors are colour-coded with one conductor identified
  • that secondary conductors are polarized with the identified conductor connected to the larger pin or receptacle and grounded

Rule 74-008 requires that a ground counterpoise be installed with a series lighting system.

Rule 74-010 requires that ground counterpoise conductors be

  • minimum #8 solid soft copper
  • insulated with a green finish where installed underground in raceways
  • placed 75mm above all cable in the trench
  • run in a zig-zag pattern crossing cables at 300mm intervals where outer cables are more than 150mm apart
  • placed 75 mm over non-metallic conduit and under any protective covering
  • connected to
    • ground terminal of each series isolating transformer;
    • the mounting stake of light units;
    • the sheath of metal sheathed and armoured cables supplying light units;
    • ground electrodes at all regulators, towers, and lighting equipment, and maintenance holes;
    • metallic transformer housings, lids and covers;
    • non-current carrying metal parts of inset lights; and
  • bonded together at all points where counterpoise conductors of different systems cross or come together.

In the next instalment, we will be discussing Section 76 — Temporary Wiring.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

**Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting; billburr@gmail.com

 

Related Articles


Latest Articles

  • Mastering Advanced Bidding Strategies in Electrical Contracting

    Mastering Advanced Bidding Strategies in Electrical Contracting

    December 1, 2025 By Melvin Newman, Patabid CEO & Ian Paterson, Patabid Client Success Manager and journeyman electrician with 30+ years of experience In the competitive world of electrical contracting, knowing how to estimate electrical jobs effectively can make the difference between winning profitable projects and watching opportunities slip away. For electrical contractors, mastering advanced… Read More…

  • Why Choosing the Right USB Charger Matters

    Why Choosing the Right USB Charger Matters

    December 1, 2025 Not all USB Chargers are Created Equal As the number of devices used daily increases, so does the need for a charger that delivers safe speeds and maximum charging potential. A high-quality USB charger delivers efficient charging without risk of damage, but the sea of USB chargers and outlets available on online… Read More…

  • How Homebuilding Incentives Can Pay Off for Cities, Homeowners and Local Economies: New Concordia Study

    December 1, 2025 A new study from Concordia University’s John Molson School of Business finds that improving housing affordability isn’t just a social good — it’s an economic growth opportunity. Build and Benefit: How Homebuilding Incentives Can Pay Off for Cities, Homeowners and Local Economies reframes housing policy reform as a sustainable fiscal growth strategy, demonstrating meaningful… Read More…

  • The Importance of HazLoc LED Lighting for Safe Workplaces

    The Importance of HazLoc LED Lighting for Safe Workplaces

    November 30, 2025 By CSC LED In Canada’s industrial lighting sector, one of the most critical yet often overlooked safety components is lighting designed specifically for hazardous locations, otherwise known as HazLoc (hazardous location) LED lighting. For workplaces dealing with flammable gases, vapours, combustible dust, or ignitable fibres, standard LED fixtures simply don’t cut it…. Read More…


Changing Scene

  • Skills Ontario Celebrates the Expansion of Trades & Tech Truck Program

    Skills Ontario Celebrates the Expansion of Trades & Tech Truck Program

    December 1, 2025 Skills Ontario is expanding its fleet of Trades & Tech mobile unit thanks to support from the Ontario Government. The government announced this morning it’s investment in Skills Ontario to expand experiential opportunities for Ontario’s future workforce.    “Ontario’s future relies on a strong, skilled workforce,” said David Piccini, Minister of Labour, Immigration,… Read More…

  • BC’s Canadian Mutual Recognition Agreement aims to Facilitate Interprovincial Trade

    BC’s Canadian Mutual Recognition Agreement aims to Facilitate Interprovincial Trade

    December 1, 2025 A new agreement signed by all provinces, territories, and the federal government will break down interprovincial trade barriers, making it easier for B.C. businesses to sell products across Canada, and for people to buy Canadian-made goods.   “When threats to Canada’s economic security land at our doorstep, we’re at our best when we work together as… Read More…

  • EB Horsman’s Commitment to Giving Back – A Year in Recap 2024/2025

    EB Horsman’s Commitment to Giving Back – A Year in Recap 2024/2025

    December 1, 2025 EB Horsman Cares is the company’s community engagement program that supports local children’s hospitals, communities, and non-profit initiatives with donations, fundraising, volunteering, and scholarships.  Since 1993, BC Children’s Hospital has been the primary recipient of EB Horsman & Son’s fundraising. However, as EB Horsman has continued to expand its businesses across Western… Read More…

  • Build Canada Homes Introduces Policy Framework to Guide its Investments in Affordable Housing

    Build Canada Homes Introduces Policy Framework to Guide its Investments in Affordable Housing

    December 1, 2025 Central to that work, the Government of Canada is stepping up with the recently launched Build Canada Homes, new federal agency with a mandate to scale up the supply of affordable housing across Canada. Build Canada Homes will also help fight homelessness by building transitional and supportive housing – working with provinces,… Read More…