|

Guide to the Canadian Electrical Code, Part 1[i], 26th Edition – A Road Map: Section 6

February 8, 2024

By William (Bill) Burr[i]

Often, Code users encounter situations where they find themselves at odds with the rules contained in the Canadian Electrical Code, Part I (the Code). These situations usually are a result of a misreading, misunderstanding, misapplication, or inability to locate the requirement that is needed or that is relevant to their tasks. The Code is a comprehensive document. Sometimes, it can seem daunting to quickly find the information you need.  This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B, or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the Code.

Section 6

Section 6 – Services and Service Equipment.

Section 6 of the code outlines the rules applicable to the electrical installation of service equipment, including the consumer’s service and the supply service. As per the definitions in Section 0:

  • a consumer’s service includes all that part of the consumer’s installation from the service box or equivalent, up to the point connection is made to the supply service,
  • a service box is an assembly consisting of an enclosure that can be locked or sealed, containing either fuses and a switch, or a circuit breaker, and designed so that it is possible to operate either the switch or circuit breaker to the open position by manual means when the box is closed,
  • a supply service means any one set of conductors run by a supply authority from its mains to a consumer’s service,
  • a service room is a room or space provided in a building to accommodate building service equipment, and constructed in accordance with the National Building Code of Canada, or applicable local legislation, and
  • a supply authority is any person, firm, corporation, company, commission, or other organization responsible for an electrical power distribution network that connects to a consumer’s service.
  • Note that “supply authority” can include public utilities as well as private electrical power networks that are considered to be supply authorities by the regulatory authority having jurisdiction. Also, according to the scope outlined in Section 0, equipment and work employed by the supply authority, in its function as a utility, are not covered by this code. However, this section does have rules only for the attachment point of the supply service. The rest is deemed to be outside the scope of the code since it is installed by the utility.

As noted above, this section deals with all electrical services. However, services and service equipment over 750 volts may be changed by rules in Section 36 – High-voltage installations. We will discuss these modifications when we get to Section 36, but if you intend to install a high-voltage service be aware there may be rating, capacity and overcurrent protection modifications for high-voltage service equipment rules.

General – Rules 6-100 to 6-116 deal with the number, arrangement, and location of electrical services.

Rule 6-100 provides a special terminology definition applicable to this section:

  • Transformer rated meter mounting device, which is a meter mounting device with current transformers that may have test switches mounted in the same enclosure, and

Normally, according to Rule 6-102, only one service is run to a building, however, more than one supply service may be run to any building provided that each supply service is supplying:
• fire pumps, in accordance with Section 32
• an industrial establishment, or
• completely self-contained row-type occupancies, with separate entrances to ground level.

The service boxes for such supply services associated with multiple supply services must be grouped, where practicable. Where this is not possible, a permanent diagram must be affixed beside each supply service box showing where the other service boxes are located. In any case, the Appendix B note to this section advises that it is prudent to consult with the supply authority on the number and location of supply services.

Rule 6-104 further provides for a maximum of four consumer’s services of the same voltage and characteristics (normally the number of phases) run to any one supply service.

Rules 6-106 to 6-110 provide rules regarding service supply from:

  • 6-106 more than one system,
  • 6-108 an electric railway, and
  • 6-110 for a 3-wire system where more than two 120-volt circuits are installed.

Rules 6-112 to 6-116 outline the requirement for support, clearance, and termination of consumer’s service conductors or cables and the location of a consumer’s service head. The Appendix B notes for this section are very helpful in designing and installing a consumer’s service.

Rule 6-112 outlines that a means of attachment be provided for all supply or consumer’s service conductors or cables and requires that:

  • the point of attachment must be:
    • on the same side of the building as the consumer’s service head or equivalent,
    • solidly anchored to the structure or service mast,
    • in a position that allows the overhead service conductors or cables to have an angle away from the structure,
    • in compliance with the requirements of the supply authority;
  • the point of attachment of supply or consumer’s service conductors or cables must not exceed 9 m above grade or sidewalk and be located so the clearance of supply conductors or cables at any point above finished grade must be at least:
    • 5.5 m across highways, streets, lanes, and alleys,
    • 4 m across driveways to residential garages,
    • 5 m across driveways to commercial and industrial premises, and
    • 3.5 m across ground normally accessible to pedestrians only;
  • exposed service conductors or cables must be located above windows, doors, and porches or have a clearance of at least 1 m;
  • where service masts are used, they must be of metal and assembled from components suitable for service mast use. Provided that all other requirements for a service mast are followed, Rigid steel conduit of 63 minimum nominal trade size, may be used;
  • bolts must be used for securing the means of attachment at the point of attachment, and not less than 38mm in any dimension on wooden structural members;
  • the supply or consumer’s service conductor support must not be attached to the roof of a structure, except to fasten the upper service mast support, eye bolt, and guy wire attached, to a main structural member of the roof.

Rule 6-114 outlines the methods of terminating conductors or cables at consumer’s services and requires that:

  • the supply end of a consumer’s service be equipped with a service head that is suitable for use in a wet location, except for:
    • service cables that are continuous from the supply service to the service equipment,
      • single or multi-conductor cables, the service head may be omitted, provided that.
      • the cable ends in a termination suitable for exposure to the weather, or the cable ends are sealed with self-sealing weather-resistant thermoplastic tape or heat-shrinkable tubing,
      • both single and multi-conductor cables are bent as necessary so the conductors emerging from the sealed point of the cable termination point downwards, and
      • the cables are held securely in place by a clamp, fitting, or cable termination;
  • conductors of different polarity be brought out through separately bushed holes of the service head;
  • consumer’s service conductors be installed so that the consumer’s service conductors beyond the service are adequate to enable connection to the supply service conductors with a minimum length of 750 mm and be provided with drip loops as specified in Rule 6-302 (3); and
  • the overhead supply service conductors or cables and the consumer’s service conductors be arranged according to the requirements of Rule 6-116 to prevent moisture and water from entering service raceways, cables, or equipment.

Rule 6-116 outlines the location of the consumer’s service head location and requires that it be installed in compliance with the requirements of the supply authority; and in such a position that the point of emergence of the conductors from the consumer’s service head or equivalent is a minimum of 150 mm and a maximum of 300 mm above; and a maximum of 600 mm horizontally, from the support for attachment of the overhead service conductors or cables.

Control and Protective Equipment – This part of this section specifies how services are controlled, as well as measures for the protection of persons and property.

Rules 6-200 to 6-204 delineate the need for and for the arrangement of service boxes.

Rule 6-202 requires that in multiple occupancy and in single occupancy multi-rate service:

  • each subdivision of the main consumer’s service be provided with a separate service box, or equivalent multi-service equipment except where a special permission deviation as per Rule 2-030 for single occupancy multi-rate services only has been allowed, and  
  • where the main consumer’s service overcurrent devices adequately protect any subdivision of the main consumer’s service, the separate service box for the subdivision may be omitted.

Rule 6-204 requires that where a service box has one or more fuse holders, which are accessible without opening the door, the fuse holder and fuses must be completely enclosed behind a separate door with a spring or substantial catch closure.

Rules 6-206 to 6-214 discuss:

  • the location of consumer’s service equipment and conductors,
  • the use of oil switches and oil circuit breakers as service switches,
  • wiring space in enclosures, and
  • marking of service switches.

Rule 6-206 outlines the consumer’s service equipment location and requires that equipment:

  • be installed in a location that complies with the requirements of the supply authority,
  • be readily accessible or have the means of operation readily accessible, except as provided for below re unauthorized operation,
  • be placed within the building being served as close as practicable to the point where the consumer’s service conductors enter the building and
  • not be in:
    • coal bins, clothes closets, bathrooms, and stairways,
    • rooms where the ambient temperature exceeds 30 °C under normal conditions,
    • dangerous or hazardous locations,
    • locations where the headroom clearance is less than 2 m,
    • in any similar undesirable places or
    • areas below the flood elevation, and
  • where subject to unauthorized operation, the service disconnecting means may be made inaccessible by:
    • an integral locking device,
    • an external lockable cover, or
    • location of the service box inside a separate building, room, or enclosure.

The service disconnecting means may be placed on the outside of the building or on a pole if it is:

  • installed in an enclosure designed for use in outdoor locations or protected against the weather; and,
  • protected against mechanical damage, if located less than 2 m above ground.

Again, Appendix B suggests that the local regulatory authority be consulted regarding the locking of service boxes in the ‘on’ position and the location of service boxes and meter mounting devices, as the supply authority requires access to this service equipment.

Rule 6-208 provides direction on the location of consumer’s service conductors and requires that raceways or cables containing consumer’s service conductors be located outside buildings unless they:

  • are embedded in and encircled by not less than 50 mm of concrete or masonry,
  • are directly buried in accordance with Rule 6-300 and located beneath a concrete slab not less than 50 mm thick,
  • are run underneath a structure in a non-combustible crawl space, not more than 1.8m in height and not used for storage of combustible material, or
  • enter the building for connection to a service box.

Rule 6-210 gives direction on oil switches and oil circuit breakers used as consumer’s service switches and requires that:

  • isolating switches be installed on the supply side and interlocked with oil switches and oil circuit breakers, except for metal-clad equipment, where the primary isolating device is the equivalent of an isolating switch or link, and
  • where overcurrent trip coils are used for breakers, one must be installed on each ungrounded conductor of the circuit; or
  • where the capacity of the transformers and the extent of the network supplying the service is sufficiently small, and a deviation has been allowed in accordance with Rule 2-030, two trip coils, one in each phase of a 4-wire, two-phase ungrounded service, may be used.

Rule 6-212 requires that.

  • wiring space in enclosures for circuit breakers and externally operated switches are not used as junction boxes, troughs, or raceways for conductors feeding through or tapping off to other electrical equipment except for service equipment designed for accommodating current monitoring devices, and
  • consumer’s service conductors entering a service box that is not equipped with a barrier between the line and load sides:
    • enter the service box as close as practicable to the line terminals of the main switch or circuit breaker, and
    • not meet or cross conductors connected to the load terminals of the main switch or circuit breaker. (note practicable means doable or feasible vs practical which means useful).

Rule 6-214 requires that if there is more than one service box, each box must be labelled in a conspicuous, legible, and permanent manner to indicate clearly which installation or portion of an installation it controls.

Wiring Methods  – This part has guidelines for the selection, minimum size, and installation of consumer’s service conductors.

Rules 6-300 to 6-304 provide the methods for installing consumer’s service conductors and cables and address:

  • Rule 6-300, the installation of underground consumer’s service conductors, 
  • Rule 6-302, the installation of overhead consumer’s service conductors, and
  • Rule 6-304, the use of mineral insulated and aluminum sheathed cables.

Rule 6-306 specifies that consumer’s service raceways:

  • contain only consumer’s service conductors,
  • be protected from mechanical damage, and
  • have a minimal cross-section size of 21mm.

Rule 6-308 provides that where a neutral conductor is installed in a consumer’s service raceway it shall be insulated, except a bare neutral conductor is permitted to be installed as per Rule 6-302 when the neutral conductor is used as a part of assembly of a busway, or neutral supported cables NS75 or NS90.

Rule 6-310 prohibits the use of joints and splices in a consumer’s service conductor except:

  • with a clamp, lug, or bolted connection in a meter mounting device using, a connector designed for the purpose at the service head, where exposed wiring is used for an overhead service, as per Rule 6-302 2).
  • by a joint underground, where such a joint is required to repair damage to the original installation or to accommodate a pole or service relocation, and is made as per the requirements of Rule 12-112 (5); or
  • where a conductor transition is made to meet the requirements of Rule 4-006 or Rule 8-102.

Rule 312 requires that, to drain condensation, a consumer’s service raceway entering a building be:

  • sealed and be suitably drained where it enters the building above grade level, and
  • not be terminated on top of the service box, except where drained outdoors

Metering Equipment  – This part gives us the guidelines for the selection, arrangement and installation of meters and metering equipment. Metering equipment includes current and potential transformers and associated measuring equipment.

Rules 6-402 to 6-410 outline:

  • the location and method of installing meter loops,
  • selection and installation of instrument transformer enclosures,
  • disconnecting means for meters,
  • location of meters and the space required for meters.

Finally, Rule 6-412 has specifications for metering impedance grounded systems.

These are the specific rules that apply to all services. However, the rules of the other general sections also may apply to services and service equipment selection and installation.

In the next installment we will discuss Section 8 – Circuit loading and demand factors.


[i] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com..


[i] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit Store – CSA Group or call 1-800-463-6727. With the permission of CSA Group, the material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit Store – CSA Group or call 1-800-463-6727.

Related Articles


Latest Articles

  • Declines in Ontario and Manitoba Construction Intentions Push Down the Non-Residential Sector

    Declines in Ontario and Manitoba Construction Intentions Push Down the Non-Residential Sector

    December 16, 2024 The total value of building permits issued in Canada decreased by $399.1 million (-3.1%) to $12.6 billion in October. This comes on the heels of a strong September, during which construction intentions rose by $1.3 billion to the second-highest level in the series. Despite the monthly decline in October, the total value of building permits… Read More…

  • Lighting Control Basics for Home Automation

    Lighting Control Basics for Home Automation

    By Matthew Biswas Do your eyes roll when you hear terms like Smart home technology?  Or are you a true believer?  As it turns out controlling electrical devices via low-voltage technology can be easier to implement and use than many of us thought. The Lutron Caseta system uses the internet and Radio Frequency to instantly… Read More…

  • Grounded in Ontario: The Future of Energy Storage Systems

    Grounded in Ontario: The Future of Energy Storage Systems

    December 16, 2024 Technical Advisor Trevor Tremblay explains why following best practices and relying on licensed professionals will ensure a smooth and secure transition when integrating this exciting new technology. Energy Storage Systems (ESS) are revolutionizing the way individuals and businesses manage energy, providing cost-saving opportunities, increased energy reliability, and a pathway toward sustainability. In… Read More…

  • 4 in 5 Canadians See Electrifying Public Transit as Key to Advancing Climate Action, Schneider Electric Survey Finds

    4 in 5 Canadians See Electrifying Public Transit as Key to Advancing Climate Action, Schneider Electric Survey Finds

    December 13, 2024 Schneider Electric has released new survey findings showing Canadians are increasingly concerned about the environmental impact of traditional public transit emissions. According to the survey, 83 per cent of Canadians recognize the need for electrified transit to support a sustainable future and are seeking actionable and innovative solutions to ease the nation’s… Read More…


Changing Scene