Guide to the Canadian Electrical Code, Part I — Instalment 36

Bill Burr

 

Apr 22, 2018

By William (Bill) Burr

In this article: Section 72 — Mobile home and recreational vehicle parks. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating the code.

Rule 72-000 notes that this is a supplementary or amendatory section of the code and applies to the services and distribution facilities for mobile home and recreational vehicle parks.

Rule 72-100 requires that each mobile home and recreational vehicle be provided with service equipment in accordance with Section 6.

Rule 72-102 outlines the demand factors for various service and feeder conductor arrangements:

• for service or feeder conductors supplying an individual mobile home or more than one mobile home — Rules 8-200 and 8-202, respectively

• for the minimum ampacity of the consumer’s service and feeder conductors for recreational vehicle parks, calculated based on the rating of the receptacles and the following demand factors:

o 100% of the first five highest rated, plus
o 75% of the next ten receptacles, plus
o 50% of the next ten receptacles, plus
o 25% of the remainder

• multi-wire circuit receptacles are counted as two receptacles

• the highest rated receptacle is used as the basis for calculation

Rule 72-104 permits feeders for the park consumer’s service equipment and the park distribution centres to be installed as per Section 6.

Rule 72-106 requires that the branch circuit for each recreational vehicle lot receptacle have a suitable, accessible overcurrent device and disconnecting means.

Rule 72-108 requires that the branch circuit for each mobile home lot have a suitable, accessible overcurrent device and disconnecting means and be located within a weatherproof enclosure if installed outdoors.

Rule 72-110 specifies the connection facilities for recreational vehicles and mobile homes and outlines:

• the types of 15A, 20A, 30A, and 50A receptacles required where installed on recreational vehicle lots

• the requirement for a permanent connection to a mobile home, except that for a home with a 50A rated overcurrent protection, a 50 A, 125/250 V, 3-pole, 4-wire Type 14-50R receptacle may be permitted (under Rule 2-030)

• all receptacles must be mounted in a horizontal plane, or so that the u-ground slot is uppermost

• 15A and 20A receptacles must be protected by a Class A type ground fault circuit interrupter

Rule 72-112 states that power supply cords may be permitted for the connection of

• recreational vehicles, only where the cords are not subject to severe physical abuse or extended periods of use

• mobile homes only when the lot is equipped with a 50 A, 3-pole, 4-wire Type 14-50R receptacle (permitted under Rule 2-030)

In the next instalment, we will be discussing Section 74 — Airport installations.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

**Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting; billburr@gmail.com

 

Related Articles


Latest Articles


Changing Scene

  • SATCO Celebrates 60 Years of Excellence in Lighting, NUVO Marks 20 Years of Design Innovation

    SATCO Celebrates 60 Years of Excellence in Lighting, NUVO Marks 20 Years of Design Innovation

    April 10, 2026 SATCO proudly announces the celebration of its 60th anniversary, marking six decades of sustained growth, innovation, and service excellence. Concurrently, NUVO, a prominent lighting brand under the SATCO umbrella, celebrates its 20th anniversary, highlighting two decades of cutting-edge design and creative solutions for residential and commercial spaces. Founded in 1966, SATCO has Read More…

  • D.A.D. Sales Welcomes New Team Members

    D.A.D. Sales Welcomes New Team Members

    April 10, 2026 D.A.D. Sales announced the addition of Bradey Cameron as an Application Specialist on the D.A.D. Sales Solutions team, Katherine Dickson as an Account Manager on the D.A.D. Sales team, supporting Northern Alberta, and Wendy Dyble as an Account Manager / Inside Sales on the D.A.D. Customer Service Team. “Bradey brings a strong Read More…

  • Liteline Introduce New Regional Sales Manager for GTA

    Liteline Introduce New Regional Sales Manager for GTA

    April 10, 2026 Liteline announced on LinkedIn that Peter McCumber has joined their team as Regional Sales Manager for the GTA. “We are excited to welcome Peter as Liteline’s Regional Sales Manager-GTA! Peter brings more than two decades of experience in the electrical manufacturing and wholesale industry, where he has established himself as a dynamic Read More…

  • Dixon Relocates Mississauga Branch to Better Serve Customers

    Dixon Relocates Mississauga Branch to Better Serve Customers

    April 10, 2026 Dixon proudly announces the relocation of its Mississauga branch to 6197 Kennedy Road, enhancing accessibility and customer convenience. Strategically positioned along a busy corridor with excellent access to Highways 401, 410 and 403, the new 14,000-square-foot facility offers improved convenience for customers and partners. The branch features a modern storefront, an enhanced Read More…