This is the third of a series of articles detailing significant changes for the 2015 Canadian Electrical Code Part I (CE Code). Specifically, Sections 2, 4, 6, 8, 10 and 12.The rules in this article are limited to changes adopted by CE Code Technical Committee and not subject to further changes. It should be noted that until a formal memorandum of revisions to the CE Code is published by the Canadian Standards Association (CSA), the information provided in this article is simply based on the observations of the writer.

Section 2

A new rule has been added to Section 2 to provide direction regarding withstand ratings of equipment and equipment with a slash voltage rated such as 125/250V, 120/240V, 208Y/120V, 480Y/277V, or 600 Y/347V, etc. Electrical equipment intended to withstand short circuit current but not intended to interrupt the short circuit current is rated with either a withstand rating or a short circuit current rating (SCCR). New Subrule (1) will provide code users with information required to establish safe installation of the electrical equipment with a SCCR or withstand rating. New Subrule (2) is intended to align requirements in the CE Code with limitations of the applicable product standards and will provide code users with information required to establish proper operation of the electrical equipment without having intimate knowledge of the individual standards. Equipment marked with a slash voltage rating is intended for connection to a system that is solidly grounded.

Existing Table 65 has been expanded to include three new enclosure types. Types 3X, 3RX, and 3SX are enclosures that are provided with corrosion protection.

Rule 2-324 has been revised by replacing the requirement for the 1m clearance distance between arc-producing electrical equipment and a combustible gas relief device or vent, with a reference to CSA Standard B149.1 Natural Gas and Propane Installation Code. A new Appendix B note will also be added with the required clearance measurements from the 2010 edition of CSA Standard B149.1

Codes Controller Nameplate

Photo 1 shows a nameplate of a manual self-protected combination motor controller with slash rating of 600Y/347V; when used on a 600V system, this equipment can only be connected to a solidly grounded wye system.

Section 4

In Section 4, a proposal for Rule 4-004 was accepted that aligns the ampacities for single conductor and multi-conductor cables with existing ampacities in Rule 12-2210. Also for Rule 4-004 new subrules, Appendix B notes, configuration drawings, and ampacity tables have been added to clarify ampacities for cable rated between 5 and 46kV. With this change, the titles of Tables 1 through 4 were renamed limiting the maximum voltage to 5kV. The final change to Rule 4-004 is in the underground ampacity tables found in Appendix D; these tables have been now recalculated, and the maximum continuous load conditions from Rule 8-104 were also removed from the tables. At first glance, it will appear that ampacities for underground installation have increased, but keep in mind the maximum continuous load will need to be limited in accordance with Rule 8-104.

Rule 4-006 regarding temperature limitations has been expanded from two to six subrules. The changes include the minimum size for the first 1.2m of conductor to be terminated to equipment based on the allowable ampacity in the corresponding temperature column in Tables 1 through 4 with the relevant correction factors applied. The 90°C default in Subrule (2) has been replaced to align with the termination temperature limitations in the product standards. This change means that for low voltage equipment rated 100 Amps or more marked for use with a conductor larger than No. 1, the default temperature is 75°C, and for low voltage equipment rated 100 Amps or less marked for use with a conductor smaller than No. 1, the default temperature is 60°C.

Cord sets (extension cords) have been added to Rule 4-012 (3), limiting the use of flexible cords and cord sets to the existing requirements in Subrule (3).

Codes Termination Temp

Photo 2 shows the termination temperature of 75°C on a 350 Amp dc rated breaker.

Section 6

Rule 6-402(2) has been expanded to allow 320 Amp meter mounting devices with a by-pass means to be connected on the line side of the service box. This allowance was added to recognize the increased load from electric vehicles and to recognize similar provisions in the standard for existing meter mounting equipment available and certified for use in Canada.

Codes Service Size

Photo 3 shows a type of facility where historical data could be used to determine the service size. Photo courtesy of Tim Hortons Inc.

Section 8

Rule 8-102 covering voltage drop requirements has been expanded from two to four subrules. The main changes are the addition of a new table detailing the maximum length for single dwelling unit branch circuit rated not more that 120V and 20 Amp, and a subrule for industrial establishments where the design will ensure the voltage at the point of utilization is within the tolerance of the connected device.

At the request of the chair of the CE Code, a task group was formed to compare the size of non-residential services and feeders required by Section 8 with actual loads. As a result, Section 8 has seen many changes. First is the addition of definitions “Basic load,” “Calculated load,” and “Demonstrated load” in the special terminology in Rule 8-002. A basic load includes the lighting and receptacles as calculated using Table 14; a calculated load is a load calculated in accordance with Section 8; a demonstrated load is the maximum load recorded over a minimum of 24 months for the same type of facility.

Second is the addition of two subrules to Rule 8-106: one to allow demonstrated loads to be used for feeder and service calculation when performed by a qualified person recognized by the authority having jurisdiction (most likely by a professional engineer or an engineering technologist), and second to allow the acceptable qualified person to apply a demand factor determined by the qualified person.

Third is a wording change to Rule 8-210 for other types of occupancies including the removal of “power loads” and the addition of “motor loads.”And fourth, to combine Rules 8-302 and 8-212 as Rule 8-212 Exit sign, emergency lighting, and show window loads.

Codes Igard

Photo 4 shows a ground fault detection device that can be used to satisfy Rule 10-106. Photo provided by i-Gard.

Section 10

Section 10 will now recognize material other than copper for uses as a ground conductor in Rules 10-402, 10-406, 10-626, 10-702, 10-802, 10-806, 10-810, 10-816, 10-1000, and 10-1108. In addition, to address possible corrosion issues, a new Subrule (2) has been added to Rule 10-802.

Rule 10-106 has changed by moving the Appendix B note regarding the location and identification of a ground fault detection device to a new Subrule (3) making this a mandatory requirement.

A new Subrule (5) has been added to Rule 10-618 to require a separate bonding conductor to bond fixed equipment when single conductor cables are installed with one end isolated to comply with Rule 4-010.

Rules 10-902 and 10-904 have been amalgamated into a new rule that does not favour a water pipe as a grounding electrode over other acceptable grounding electrodes. This new rule also provides direction that the connection to metallic water pipe in-situ grounding electrodes must be as near as practicable to the point of entrance in the building.

Rule 10-1102 (2) has been modified to require the alarm indicator installed to detect a fault on a system rated 5kV or less with a neutral grounding device is to be identified, and visible or audible to persons monitoring the status of the system. In addition, a new Subrule (5) was added to require the conductor to be continuous between the neutral grounding device and the ground electrode.

Section 12

Rules 12-510, 12-706, 12-1010, 12-1308, and 12-1504 have been expanded to allow cable ties of a type specifically approved for the purpose to be used for support of cables and flexible conduit and tubing. The requirements for cable ties have been removed from CSA Standard C22.2 No 18.5-13 and are now found in CSA Standard C22.2 No. 62275-10. To assist code users, a note and table have been added in Appendix B to explain the different types of cable ties and where they can and cannot be used. As of June 2014, each cable tie is required to be marked with the manufacturer’s or responsible vendor’s name, trademark or identifying symbol. In addition, the following markings are required to be provided on labels, packaging, or installation instructions shipped with the cable tie instructions provided with the product:

1. a) maximum operating temperature

2. b) minimum operating temperature

3. c) minimum installation temperature if lowerthan 0⁰C (temperature at time of installation advisory only to installer for cold temperature handling)

1. d) minimum and maximum bundle diameter

2. e) loop tensile strength; and

3. f) type designation

The marking indicating the classification “Resistant to ultraviolet light” in accordance with C22.2 No. 62275-10 Clause 6.5.1.2 may alternatively be marked “For use outdoors” or “For use outdoors or indoors” or with an equivalent wording.

Codes Table 1

Table 1 has been determined from CSA Standard C22.2 No. 62275-10 detailing the types of cable ties and approved usage.

Rule 12-516 for the protection for cable in concealed installations has been revised requiring protector plates used to protect cables installed within 32 mm from the edge of studs, joists, or similar member to be specifically approved for the purpose. This change is to recognize new testing requirements for protector plates and is intended to stop the use of unapproved protection like the sides of device boxes being used for this purpose. As an alternative, these rules now recognize a new product called a cylindrical bushing that can be inserted in the hole through the member, provided the cylindrical bushing extends a minimum of 13 mm beyond both sides of the member.

Extra heavy wall reinforced thermosetting resin conduit (RTRC) Type XW has been added to Rules 12-000, 12-1202, and 12-1216. RTRC Type XW conduit is designed to be installed in specified hazardous locations. In addition to the change in Section 12, Rule 18-152 Wiring methods, Class I, Division 2, and Rule 18-252 Wiring methods, Class II, Division 2 have been modified to recognize RTRC Type XW conduit.

Codes Cable Ties

Photo 5 shows a Type 21S cable tie used to support cables.

Similar to existing Rule 12-1164, a new Rule 12-1124 has been added to provide direction for the installation and construction of split straight conduit for PVC installations both above and below grade.

The cable tray rule in Section 12 has seen three more changes: first is an exception added to Rule 12-902(2) for cable tray not requiring the separation of different systems; the second is the addition of a new Subrule (7) for Rule 12-2200 that allows a reduced clearance for cable tray through chases, under grating, under process pipes, and other such obstructions; the third addition is a new Subrule (3) added to Rule 12-2208 allowing cable tray with only armoured cable to be installed without additional bonding of the cable tray provided warning notices are posted indicating that only interlocking metal armour cables or continuous metal sheath cables can be installed.

Codes Protection Plate

Photo 6 shows the traditional approved protection plates and the new cylindrical bushing used to provide protection for cables installed within 32mm from the edge of studs, joists, or similar member. Photo provided by Thomas and Betts.

Rule 12-2252 has been changed to recognise Class A and Class B cablebus from the new CSA Standard C22.2 No 273 Cablebus, which defines Class A and Class B cablebus as

• Class A cablebus — cablebus that provides protection from contact with conductors by design and construction of the enclosure
• Class B cablebus — cablebus that does not provide protection from contact with conductors by design and construction of the enclosure

Note: Cablebus not marked as Class A is considered to be Class B cablebus.

Codes XW Conduit

Photo 7 shows the installation of RTRC Type XW conduit. Photo provided by Champion Fiberglass, Inc.

Codes Straight Conduit

Photo 8A shows a split straight conduit used to repair a damage raceway.

Codes Split Straight Conduit

Photo 8B. Sample of a split straight conduit.Photo courtesy of IPEX.

Rule 12-3000 for Outlet boxes, and Rule 12 3002 for Outlet box covers, each have a new subrule to require floor boxes to be installed in accordance with the manufacturer’s installation instructions for the type of floor intended and that the box cover needs to be specifically approved for the type of floor intended. CSA Standards 18.1, Metallic outlet boxes, 18.2, Non-metallic outlet boxes, and 85, Rigid PVC boxes and fittings require that all floor boxes must be provided with installation instructions indicating the type of floor structure for which they are intended to be installed. Floor box covers intended for use only in a floor covered with carpet or wood are marked on the product or smallest unit shipping carton “Not for use with tile covered floors” or the equivalent.

Codes Cablebus

Photo 9 shows the installation of a Class B cablebus permitted only for installations where accessible only to authorized persons, isolated by elevation or by barriers, and where qualified electrical maintenance personnel service the installation. Photo compliments of Power Bus Way.

Codes Carpet Instal

Photo 10 shows a carpet installation using a cover and a carpet flange – not suitable for tile-covered floors. Photo compliments of Hubbell Canada LP

Codes Tile Instal

Photo 11 shows a tile installation using a cover evaluated to the more-severe scrub water test for tile floors installed with a specific type of sub-plate for tile floors. Photo compliments of Hubbell Canada LP.

Codes Flush Box

Photo 12 shows an example of a flush box installed in a masonry wall that is not approved for installation in a masonry wall and will not provide a sufficient seal between the outlet box and the cover plate.

Rule 12-3016 has two new subrules, and the title has been revised to read: Outlet boxes, cabinets, and fittings. Subrule (3) will require outlet boxes intended for installation of a wet location cover plate to be installed so that the box and cover are in intimate contact and will provide a seal to prevent ingress of water into the outlet box. Subrule (4) Flush boxes, cabinets and fittings shall be of a type suitable for the intended location of installation. Will require flush boxes to be of a type approved for the intended location of installation. As an example, a flush box installed in a masonry wall needs be approved for installation in a masonry wall.

Read Part 1 of CE 2015 Code Changes here.
Read Part 2 of CE 2015 Code Changes here.
Read Part 4 of CE 2015 Code Changes here.
Read Part 5 of CE 2015 Code Changes here.


Steve Douglas is an IAEI International Past President. He is also the Senior Technical Codes Specialist for QPS Evaluation Services. As the International Association of Electrical Inspectors representative on Part I and Part II of the Canadian Electrical Code, Steve is the vice chair of the CE Code Part I, chair of CE Code Part I Subcommittees for Section 2, and 12, and a member on Sections 40, 64, 68, 76 and Appendix D. In addition, Steve is Chair of the CSA Standards C22.2 No. 273 Cablebus, C22.6 No. 1, Electrical Inspection Code for Existing Residential Occupancies committee, Chair of the SPE-1000 Working Group, and a member on committees for the Objective Based Industrial Electrical Code, Safety Management Systems, Solar Photovoltaic Modules, Photovoltaic Cable, Fuel Cells, Wind Turbines, Distribution transformers, Outlet Boxes, and Wiring Fittings Hardware and Positioning Devices.

Changing Scene

  • Prev
 Canada’s National Electrical Trade Council (NETCO) is pleased to announce that IDEAL ...
The Government of Saskatchewan is engaging the public to help ensure health and safety legislation ...
Despite electrical shock being a serious and potentially dangerous event, it is frequently ...
Acuity Brands, Inc. has announced its Care222® filtered far-UVC module with patent-pending ...
LEDVANCE, the makers of SYLVANIA general lighting in the United States and Canada, recently ...
The federal governemnt launched a Call for Proposals under the new Apprenticeship Service, to ...
ECAO and OEL are working on obtaining more contractor experiences with the ESA permit system. ...
Agents of Change is an event for stakeholders from Canada's electricity and beyond to build ...
Schneider Electric is introducing a personalized digital experience for logged in customers ...
Teledyne Technologies Incorporated announced the successful completion of the acquisition of FLIR ...


 

SaskatchewanThe Government of Saskatchewan is engaging the public to help ensure health and safety legislation meets the needs of employers and workers in the province. From August 16 to October 18, 2021 citizens can provide input on part III (occupational health and safety) of The Saskatchewan Employment Act.

"Our province has a plan for growth that includes ensuring we have safe and healthy workplaces" Labour Relations and Workplace Safety Minister Don Morgan said. 

 


Read More


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

Desert HomeA combination of stunning design, a spectacular desert setting, and exceptional architectural lighting is a winning combination for a private residence just outside of St. George, Utah. JRC Lighting was hired by the homeowner to create the lighting concept for the showpiece home.

"The house has an almost industrial look to it, with a focus on clean lines," said Kevin Meredith, principal at JRC Lighting. "My goal was to keep the lighting understated and let the architecture, and the views, sell themselves.”

 

Read More


 

 

David GordonBy David Gordon

This summer EiKO is launching its Z10 product offering. I know, what is Z10 other than the sports cars some of us remember (’69 Z10 Camaro or a 2009 BMW Z10, but let’s go with an American muscle car!)?

So, since it seemed like a sports car “name” (since sports car naming seems to be in numbers), we reached out to Sarah Eastman, VP Marketing for EiKO, who shared that Z10 is an alliance of manufacturers who have developed standards to support an easier lighting controls process within fixtures (remember, I’m not a product maven).
Read More


 

Product News

  • Prev
Atkore’s FRE Composites® BreathSaver® XW fiberglass conduit system uses a non-metallic, phenolic ...
Atkore’s FRE Composites® fiberglass conduit recently experienced increased demand in above- and ...
4 speed Supreme Series fan with an optional speed controller DMD-LED-3.      
Set up, switch out and print faster than you ever imagined with the BradyPrinter i5300 ...
Siemens whole-house protection devices defend the sensitive electronics that are susceptible to ...
LSP05GI Series LED Lighting Surge Protection Modules are designed for use in outdoor and commercial ...
Milwaukee Tool expands their Lighting Solutions once again with the introduction of the M12™ ...
M12™ Cable Stripper Kit for Cu THHN / XHHW aims to improve the cable stripping experience. With no ...
Here’s the easy, NEAT way to mount single or two-gang boxes between wood or metal studs with ...
LEDVANCE, the makers of SYLVANIA general lighting in the United States and Canada, has released the ...

 

Milwaukee M12 Cable StripperM12™ Cable Stripper Kit for Cu THHN / XHHW aims to improve the cable stripping experience. With no exposed blades, the cordless cable stripper provides safer stripping than with a knife. The cable stripper's compact, right-angle design allows you to maneuver it more easily in tight spaces with less strain on the wrist. The bushing design and adjustable depth gauge deliver cleaner, more accurate and consistent strips across all sizes.

The cable jacket stripping tool is not only compatible with all MILWAUKEE® bushings but is also compatible with competitive quick-change bushings.

 

Read More


 

 

Incoplas HybridThe Incoplas® LED Hybrid is a durable multi-purpose and corrosion-resistant LED lighting solution that can be used in heavy industrial applications where hazardous location lighting is required.

Certifications

Class 1:

Flammable Gases and Liquids

Division 2: The hazardous atmosphere is only available infrequently (i.e. in case of spill).

 

Read More


 

 

EarthTronics 25-Watt Emergency Driver for Linear HighbayEarthTronics LED emergency drivers regulate the power supplied to the LED fixture so that it can operate as a light source in the event of a power failure. The purpose of emergency lighting is to ensure that lighting is provided promptly, automatically and for a suitable time when the normal power supply fails.

This insures that people within the building can evacuate safely in the event of an emergency. All EarthTronics emergency drivers meet specific UL, CSA and NFPA requirements. Always consult local code requirements when specifying emergency lighting products.

Read More


 

Peers & Profiles

  • Prev
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...
As a 34-year-old female owner of an electrical contracting business, Danielle Gray may be unique. ...
Mark Klein is Co-President of Klein Tools, managing Sales & Marketing activities, alongside ...
Bryan Smith started his now 20-year career at the ground floor, so to speak, as a draftsperson and ...
From small construction to sophisticated industrial projects, House of Electrical Supplies has been ...
Kyle Manfredi is the owner of ARK Electrical alongside his wife, Shannon. Operating out of ...


EngWorksBy Blake Marchand

EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After a short time we realized there was a niche in hazardous locations, in particular in hazardous area classification design requirements for various facilities. And also helping people understand just how the Canadian Electrical Code applies to hazardous locations.”

Given the complexity of hazardous locations, Bozek saw a need for education while working in the field and began developing training courses designed.

Read More


 

 

Eric TordjmanBy Blake Marchand

Headquartered in Concord, Ontario, Mercury Lighting services national retail, multi-residential/commercial property management, energy service companies (ESCO), and auto dealerships. “From design to specifications, we offer turn-key services that go beyond the typical distributor model,” explained Mercury Lighting Vice President, Eric Tordjman. Their value-added approach leverages well-established supplier relations to help clients find a lighting solution that suits their needs.

“How we differentiate ourselves is we’re lighting specific, we do very little in the way of electrical, and really emphasizing our expertise towards solutions selling...

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil