Guide to the Canadian Electrical Code, Part 1 — Installment 11

March 2 2016

William (Bill) Burr

The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code. In this article: Section 18 Hazardous locations, Part 2.

Section 18 covers installation of electrical equipment in hazardous locations as defined in Section 0, such as areas in which there is a potential for the ignition of explosive or combustible gases, dusts, fibres or flyings due to the design, installation or use of electrical equipment. Since the information in this instalment is extensive it is presented in two parts. This Instalment is Part 2.

Explosive gas atmospheres

This part contains rules for the installation of electrical equipment in all locations where explosive gas may be present.

Installations in Zone 0 locations

Rule 18-090 — Zone O is the hazardous location where explosive gas atmospheres are present continuously or for long periods and is the most restrictive. No electrical equipment or wiring may be installed in a Zone 0 hazardous location unless it meets the requirements of subrule 18-090 (2). Also note the marking requirements for Zone 0.

Rule 18-092 — seals are required where conduit leaves a Zone 0 location, and at the first point of termination of cables after entry to the Zone 0 location. Unbroken rigid conduit passing through a Zone 0 need not be sealed if the termination points are outside Zone 0. Seals are not required to be explosion-proof or flame-proof but must be identified for minimizing the passage of fluids or dusts and be accessible.

Installations in Zone 1 locations

Rule 18-100 — electrical equipment suitable for Class I Division 1 with protection level Ga or Gb and protection levels as outlined in 18-100(c) may be installed in a Zone 1 location.

Rule 18-102 — rigid metal conduit, hazardous location cables, explosion proof or flame proof “d” boxes, and fittings with threaded connection to conduit and cable glands shall be used for wiring in Zone 1. In addition, threads and joints need to comply with 18-102 (3), (4) and (5), and cables need to be supported to prevent stress at cable glands.

Rule 18-104 provides the rules for sealing conduits and cables entering enclosures in and leaving Zone 1 locations.

Rule 18-106 provides requirements for the installation of motors in Zone 1 locations. Additional guidance is given in Appendix B.

Rule 18-108 provides the rules for installation of Luminaires in Zone 1.

Rule 18-110 — flexible cords are permitted in Zone 1 where flexibility is required but must be installed in accordance with 18-110 (1) and (2).

Installations in Zone 2 locations

Rule 18-150 provides the rules for the installation of equipment in Zone 2. Note that equipment suitable for Class I Division 2 and Zone 0 and Zone 1 are permitted to be installed in Zone 2. Also note that transformers, capacitors, solenoids, and other non-arcing, non-sparking or non-heat-producing devices are permitted in Zone 2 locations.

Rule 18-152 provides rules for wiring methods in Zone 2.

Rule 18-154 provides rules for sealing conduit, cable and equipment in Zone 2.

Rule 18-156 provides rules on installation of luminaires in Zone 2.

Rule 18-158 — flexible cords are permitted in Zone 2 where flexibility is required but must be installed in accordance with 18-158 (1).

Explosive dust atmospheres

This part contains rules for the installation of electrical equipment in all locations where combustible and explosive metal dust may be present.
Installations in Zone 20 locations

Rule 18-190 — like Zone O, Zone 20 is the most restrictive hazardous location where explosive dust atmospheres are present in the form of a cloud of dust in air continuously or for long periods. No electrical equipment or wiring may be installed in a Zone 20 hazardous location unless it meets the requirements of Subrule 18-190.

Rule 18-192 provides requirements for wiring methods in Zone 20.

Rule 18-194 provides requirements for seals for a Zone 20 location.

Rule 18-196 — flexible cords are permitted in Zone 20 where flexible connections are required and shall be extra-hard-usage cord with cable glands.
Installations in Zone 21 locations

Rule 18-200 provides rules for installation of equipment in Zone 21. Equipment suitable for Class II Division 1 is permissible as well as equipment with the noted types of protection in (b) and ©.

Rule 18-202 — rigid metal conduit, hazardous location cables, explosion proof or flame proof “d” boxes, and fittings with threaded connection to conduit and cable glands shall be used for wiring in Zone 21. In addition, threads and joints need to comply with 18-202 (3), (4) and (5), and cables need to be supported to prevent stress at cable glands.

Rule 18-204 provides rules for sealing raceway equipment in Zone 21.

Installations in Zone 22 locations

Rule 18-250 provides rules for installation of equipment in Zone 22. Equipment suitable for Class II Division 2 is permissible as well as equipment with the noted types of protection in (b) and (c). This rule also provides rules for installation of cranes, hoists and other material handling equipment in Zone 22 locations.

Rule 18-252 provides rules for wiring methods in Zone 22.

Rule 18-254 provides the same sealing requirements as Zone 21.

In the next instalment we will discuss Section 20 — Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing Processes and aircraft hangars.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

Read the rest of the instalments in the series:
Part 1: Guide to the CE Code, Part I – A Roadmap (Installment 1 in a Series)
Part 2:
A Road Map to the CE Code, Part I – Installment 2
Part 3: Guide to the Canadian Electrical Code, Part I – Installment 3
Part 4: A Road Map to the CE Code, Part 1 – Installment 4
Part 5: Guide to the Canadian Electrical Code, Part I — Installment 5
Part 6: Guide to the Canadian Electrical Code, Part I — Installment 6
Part 7: Guide to the Canadian Electrical Code, Part I — Installment 7
Part 8: Guide to the Canadian Electrical Code, Part I — Installment 8
Part 9:
Guide to the Canadian Electrical Code, Part I — Installment 9
Part 10: Guide to the Canadian Electrical Code, Part 1 – Installment 10
Part 11: Guide to the Canadian Electrical Code, Part 1 – Installment 11


 

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Related Articles


Latest Articles

  • ABB’s Care and Modernization Services Breathe Second Life into Legacy Equipment

    ABB’s Care and Modernization Services Breathe Second Life into Legacy Equipment

    April 23, 2024 In today’s world with environmental concerns top of mind, ABB offers sustainable options to extend equipment life through refurbishment and repair—which support a circular economy and reduce landfill footprints. In this context, ABB Canada’s Brampton facility is recognized for offering customized solutions for a growing list of ABB , GE, and non-ABB… Read More…

  • ESA Warns of Unapproved Deprivation Tanks and Electrical Equipment Used by Float Escape Inc. in Ontario

    ESA Warns of Unapproved Deprivation Tanks and Electrical Equipment Used by Float Escape Inc. in Ontario

    April 23, 2024 The Electrical Safety Authority (ESA) is notifying the public about unsafe Deprivation Tanks used for floatation therapy. These products are unapproved and have not been tested for compliance with any Canadian electrical safety standards. Name of Product: Deprivation Tanks (and related various electrical equipment such as pumps, water heaters and control panels). Models: Unknown… Read More…

  • Industrial Projects Lead Non-Residential Construction Intention Gains

    Industrial Projects Lead Non-Residential Construction Intention Gains

    April 22, 2024 Month over month, the total value of building permits in Canada increased 9.3% to $11.8 billion in February. The non-residential sector grew 12.3% to $4.7 billion due to the issuance of several major construction permits, while the residential sector increased 7.4% to $7.1 billion. Ontario (+21.7% to $5.0 billion) led the growth, with gains occurring across all components. On… Read More…

  • Multi-Unit Component Weighs on Investment for February Building Construction Investment

    Multi-Unit Component Weighs on Investment for February Building Construction Investment

    April 22, 2024 Month over month, investment in building construction declined 1.1% to $19.3 billion in February. Investment in the residential sector decreased 1.2% to $13.4 billion, while investment in the non-residential sector fell 0.9% to $6.0 billion. On a constant dollar basis (2017=100), investment in building construction fell 1.2% to $11.9 billion in February, following a flat (+0.0%) movement in the previous… Read More…


Changing Scene

  • Introducing Next Sales and Marketing Inc.

    Introducing Next Sales and Marketing Inc.

    Apr 25, 2024 Dear Valued Business Partners, In an ongoing effort to provide our Partners with the best quality product, service & support, we are excited to announce the appointment of Next Sales and Marketing, as our agent representing Liteline in Atlantic Canada, beginning April 27th, 2024. Next Sales and Marketing caters to a wide… Read More…

  • Lumen Recognized for their Commitment to Sustainable Practices

    Lumen Recognized for their Commitment to Sustainable Practices

    April 23, 2024 Lumen is proud to announce that it has been honored by Ecovadis with a prestigious silver medal. This award recognizes Lumen’s ongoing efforts to integrate sustainable practices into its operations and its unwavering commitment to environmental responsibility. Ecovadis is a globally recognized assessment platform that provides sustainability ratings for companies. It focuses… Read More…

  • CCA Calls for Meaningful Investment as Housing Takes Centre Stage in Budget 2024

    CCA Calls for Meaningful Investment as Housing Takes Centre Stage in Budget 2024

    April 22, 2024 The federal government’s housing strategy is a long-awaited step forward to build more homes, but significantly more investment is needed to address critical infrastructure needs and the housing crisis, says Canada’s construction industry. The federal government’s plan announced in this Budget, as well as actions taken through the 2023 Fall Economic Statement,… Read More…

  • BCCA Response to Federal Budget 2024

    BCCA Response to Federal Budget 2024

    April 22, 2024 BCCA response to the federal budget announcement: The 2024 Federal Budget falls short on a number of policies required to meet the needs of BC’s construction industry, specifically in terms of workforce solutions and infrastructure. Our concern is that demand stimulated by aggressive housing targets and loan programs will surpass the BC… Read More…