Using Encircled Flux Compliant Light Sources For Testing Fibre Optic

September 28, 2016

International standards development organizations including ISO/IEC and ANSI/TIA are updating several key standards documents that affect field-testing of fibre optic cabling. In particular the standards now describe the use of encircled flux compliant light sources.

Encircled flux refers to the distribution of light exiting the launch fibre of a light source used for testing. An ideal launch condition is one where light intensity is an even radial pattern across the face of the launch fibre. The purpose of the standards is to ensure that different test systems from any manufacturer report the same loss for a given cable under test.

Variation in LED and VCSEL launch patterns means that the optical power injected into the cable under test can result in variances in measured power loss values depending on connector alignment or the rotation of the launch cable. This is especially critical in multimode systems where the large fibre core will accept the uneven distribution from the light source and couple it into the cabling under test.

Figure 1 depicts the output from an LED into the launch fibre. While the light is distributed axially through the fibre, the intensity is much higher at the edge of the core (represented by a darker red colour) and a noticeable amount of power is present in the cladding (outer ring), creating an overfilled launch condition.

The results are artificially high loss readings when mandrels are not used on the launch cable or when there is mild misalignment between two connectors.

The reasons are that light in the cladding attenuates very quickly, and if this jumper were connected to the power meter during calibration, the light in the cladding will be detected, though it will dissipate in the cable under test and result in a high insertion loss measurement.

Additionally, when the core is overfilled, small misalignments between two connectors can result in abnormally high loss. Especially if the power distribution is weighted to the outside of the core as depicted in Figure 1.

Figure 2 depicts the output from a VCSEL, which is a low cost laser used in multimode systems to provide higher bandwidth at longer distances. A VCSEL typically has an elongated output that creates a “blade” of light in the fibre core that maintains its shape as it propagates down the cable.

VCSELs also produce spots of high intensity light that further reduce the even distribution of power. In this diagram the spots appear to be dirt, but are actually intense modes (beams) of light.

Rather than try and control the output pattern of LEDs and VSCELs, the solution to the problem is to use specialized launch cables (in the past called mode conditioning cables) that accept an uneven light pattern, scramble it and emit an even light pattern.

These cables can be used with virtually any LED light source and make it encircled flux compliant. While these specialty cables are expensive, they have the benefit of allowing installers to keep their existing multimode light sources and make them encircled flux compliant by simply replacing the launch cable.

Figure 3 depicts an encircled flux launch cord connected to a light source. This cord replaces the standard launch cord when testing the installed cabling. The output from the EF launch cord into the fibre under test has an even distribution pattern that does not extend into the cladding of the fibre. Because the distribution pattern depends on whether the fibre core is 50 or 62.5 micron, the EF cord used for testing must match the core size of the fibre under test.

 

 

 

 

 

 

 

 

 

Multimode fibre optic systems do have limitations when compared to single-mode, but their key advantage is the lower cost of the active equipment in the system. And as multimode systems support data rates of 100Gb/s and more, the loss budgets become increasingly stringent.

Therefore, installers need to utilize every tool and technology available to ensure they obtain accurate test data and give themselves the best probability of a problem-free testing experience.

While the encircled flux testing requirements will slowly make its way into contracts and testing requirements, installers should not delay in ensuring the test cords that accompany their power meters and light sources are made with reference grade connectors.

One last note; even the best connectors, launch cables and testers are useless if the end faces are not kept perfectly clean. It’s critical that technicians apply best practices and clean the ports of the test equipment and test cords every time they are used.

When combined, reference-grade connectors/cords, encircled flux compliant launches and clean connectors will provide the best possible testing experience resulting in fewer failed tests and less time spent troubleshooting.

This article was first published online by Ideal Networks: www.idealnetworks.net/US/EN/News/Using-Encircled-Flux-Compliant-Light-Sources-for-Testing-Fiber-Optic.aspx.

 

 

Related Articles


Latest Articles

  • Take the Lesson

    Take the Lesson

    September 2, 2024 By Keith Sones, seasoned utility industry executive “I really don’t want to do this.” “You have to Keith. You have no choice. You can’t leave him hanging” replied my wife. I stared at the phone like a child looks at liver on their plate. They know you have to eat it but also… Read More…

  • Quebec Drives the Growth in Residential Building Construction in June, 2024

    Quebec Drives the Growth in Residential Building Construction in June, 2024

    Investment in building construction grew 2.8% to $21.4 billion in June, after a slight increase of 0.8% in May. These increases partly reflect April’s record high of $13.4 billion in total building permits value, since investment levels for a given period are driven by permits issued in prior months. The June increase in investment in building construction was primarily… Read More…

  • Western Memorial Regional Hospital Sets New Infrastructure Precedent and Receives LEED Silver Certification 

    Western Memorial Regional Hospital Sets New Infrastructure Precedent and Receives LEED Silver Certification 

    August 16, 2024 The new Western Memorial Regional Hospital in Corner Brook is home to Canada’s largest geothermal system, which has set a precedent for modern infrastructure for both Newfoundland and Labrador and North America. The geothermal field is approximately 600 feet below the hospital’s parking lot, and provides 100 per cent of the ground… Read More…

  • Brightening Communities: LED Technology in Action

    Brightening Communities: LED Technology in Action

    August 15, 2024 By Alex Price, Brand & Planning Manager, Current LightingTechnical Contributor: Gary Steinberg, Senior System Manager (Outdoor LED Fixtures), Current Lighting As the landscape of Canadian cities continues to evolve, the importance of outdoor lighting cannot be overstated. From enhancing public safety to promoting economic activity and fostering a sense of community, well-planned… Read More…


Changing Scene

  • Schneider Electric Launches SMART Buildings Division to Drive Sustainable Building Innovation in Canada

    Schneider Electric Launches SMART Buildings Division to Drive Sustainable Building Innovation in Canada

    Schneider Electric is transforming its Digital Buildings business in Canada with the launch of the SMART Buildings Division. This evolution marks a strategic move to deliver comprehensive solutions and services that support building owners and operators in achieving their decarbonization and sustainability goals. The demand for smart buildings is surging, driven by a global shift… Read More…

  • Introducing Alan Bearden as Interim President of Southwire Canada

    Introducing Alan Bearden as Interim President of Southwire Canada

    September 4, 2024 Southwire Canada is pleased to announce that Alan Bearden has been appointed Interim President. In this role, Alan will provide leadership and guidance for Southwire’s Canada-based organization, ensuring continuity and driving growth during this transitional period. Alan Bearden brings a wealth of experience to the position, having joined Southwire in 2008. Over… Read More…

  • A Partnership Between Electromag Graybar Canada and Phoenix Contact

    A Partnership Between Electromag Graybar Canada and Phoenix Contact

    September 3, 2024 Electromag Graybar Canada, a pioneer in industrial automation solutions and pneumatic products, is excited to announce a partnership with Phoenix Contact, a global leader in electrification, networking, and industrial automation. This collaboration, which initially began in the Langley and Ontario branches, is now expanding to Quebec. The alliance aims to provide cutting-edge… Read More…

  • Sonepar Announces the Retirement of William (Bill) C. Smith, Electrozad Director of Transitional Business

    Sonepar Announces the Retirement of William (Bill) C. Smith, Electrozad Director of Transitional Business

    September 2, 2024 William (Bill) C. Smith, Director, Transitional Business of Electrozad Supply Company Limited announced his retirement as of August 30th, 2024 after 49 years of leadership. Bill began his electrical career working part-time at Electrozad Supply while completing a Sales & Marketing Program at St. Clair College.  After his first full-time position in… Read More…