Guillevin Code Series – New Rules Around GCFIs

September 25, 2023

By William (Bill) Burr[i]


[i] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com..

Guillevin Code Series

New rules around GCFIs: Outdoor Receptacles, Receptacles Within 2.5 Meters of Finished Grade, Branch Circuits Below Grade and Flood Hazards – Canadian Electrical Code, Part 1[i], 25th

The 2021 edition of the CE Code, Rule 26-704 – Protection of Receptacles by A Ground Fault Circuit Interrupter of The Class A Type, subrule 1, requires that all 15A and 20A receptacles within 2.5 meters of finished grade be protected by Class A type GCFI.  

Note that a Class A Ground Fault Circuit Interrupter will interrupt the circuit to the load, within a predetermined time, when the ground fault current is 6 mA or more but not when the ground fault current is 4 mA or less. The requirement for Class A GFCI protection is not intended to apply to receptacles supplying specific-use appliances located behind such appliances as washers, dryers, fridges, ranges, built-in microwaves, and other similar appliances, provided that those receptacles, by their location, are rendered essentially inaccessible for use by other portable appliances.

Additionally, as per new subrule 2 of Rule 26-704, vehicle heater receptacles are no longer excluded from GFCI requirements. Previously this rule only applied to residential areas, now it applies to all areas. This is an important change for safety. It doesn’t matter what the classification is, the hazard is the same whether it’s a parking lot, commercial building, amusement park, etc.  

For receptacles intended for vehicle heaters installed per Rule 8-400 Branch Circuits and Feeders Supplying Heater Receptacles for Vehicles Powered by Flammable or Combustible Fuels, it should be noted that CSA Part II Standards C22.2 No. 191 – Engine Heaters and Battery Warmers, permits specified heaters with sheathed heating elements to leak 4 mA of current for the first 10 min after power is applied. If two or more heaters are protected by the same Class A GFCI device, the cumulative leakage current at power-on may result in tripping. Tripping of the GFCI device can also be an indication that replacement or maintenance of the heater or heaters is required.

Along with new rules surrounding electrical equipment that has been exposed to ingress of water, there are a few new rules surrounding flood hazard zones. Two new items added to Section 0 – Definitions include:

Flood elevation — elevation of surface water resulting from a flood event designated by provisions of the National Building Code of Canada or provincial or territorial building codes, local building or zoning regulations, or local flood-proofing policies. A flood elevation corresponds to a flood hazard zone and may be driven by rivers surpassing their banks, precipitation exceeding storm water capacity, ice jamming, sea level rise, and storm surging.

Flood hazard zoneA flood hazard zone is designated by provisions of the provincial or territorial building codes, local building or zoning regulations, or local flood-proofing policies. Various terminology is used to define flood hazard zones, including floodplains, floodways, and flood fringes. Maps may be available in some jurisdictions to define floodplains corresponding to a certain return period.

New subrule 3 of Rule 2-032 – Damage and Interference, requires that Electrical equipment exposed to water ingress be evaluated to the original standard to which it was approved by an organization, acceptable to the Authority Having Jurisdiction, to determine whether the equipment may be placed back into service.

New subrule 1) c) v) of Rule 6-206 – Consumer’s Service Equipment Location, stipulates that a service box cannot be located in areas below the flood elevation as designated by local floodplain management regulations or bylaws. This provides for effective and safe disconnection of the service entrance equipment during a flood event to prevent flood water from affecting access to the service disconnecting means.

New Rule 26-652 – Branch Circuits Below Ground Level in Areas Designated as Flood Hazard Zones, requires that branch circuits located below grade level in flood zones have ground fault protection to de-energize all normally ungrounded conductors with a ground fault setting sufficient to allow normal operation of the connected loads under normal conditions. Ground fault protection is a means of detecting and interrupting a ground fault current at a level less than the current required to operate the circuit overcurrent device. This Rule does not necessarily require Class A GFCI protection. However, it does not specify that Class A GFCI protection is prohibited. As above, flood hazard zones are designated by local floodplain management regulations or bylaws. management regulations or local by-laws

New Rule 26-712Sump Pump Receptacles requires, that for buildings in a flood zone, sump-pump receptacles are to be located above the flood elevation or be marked as suitable for submersion.

The Authority Having Jurisdiction in a particular region is responsible for establishing the process of identifying flood hazard zones and flood elevations throughout the country. As noted above, local floodplain management regulations or bylaws usually determine this.

These changes are an example of how the Canadian Electrical Code is adapting to climate change. The World Resources Institute predicts that flood damage in Canada could cost urban areas $8.8 Million by 2030.


[i] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit Store – CSA Group. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit Store – CSA Group or call 1-800-463-6727.

Recommended

Guillevin Code Series: New Rules Surrounding Farm Buildings Housing Livestock

In response to several high-profile barn fires, the Ontario Ministry of Agriculture, Food and Rural Affairs (OMAFRA) formed the Reducing the Risk of Barn Fires Advisory Panel, to consider the next steps for government, agencies, and farm owners to help reduce the risk of barn fires and the loss of animals. Read More

Related Articles


Latest Articles

  • Electric Avenue Responds to Enel X’s Exit from North American Market with a Call for Open-Source EV Charging Standards

    Electric Avenue Responds to Enel X’s Exit from North American Market with a Call for Open-Source EV Charging Standards

    October 4, 2024 Electric Avenue has issued a response to the recent announcement that Enel X, a major player in the EV charging space, will be shutting down its North American operations effective October 11, 2024. This decision leaves over 170,000 EV chargers across the U.S. and Canada without software support, rendering them largely inoperable…. Read More…

  • Electrical Safety Authority Recognizes Safety Excellence in Ontario at its 2024 Annual Meeting

    Electrical Safety Authority Recognizes Safety Excellence in Ontario at its 2024 Annual Meeting

    September 30, 2024 PUC Services Inc., Bluewater Power, Hydro One & London Hydro, Elexicon Energy, Mellon Inc., and Ottawa Community Housing were honoured at the 2024 Ontario Electrical Safety Awards for exemplary electrical safety leadership. The Electrical Safety Authority (ESA) held its Annual Meeting and Ontario Electrical Safety Awards earlier this month to celebrate leadership… Read More…

  • Incentives for Tubular LEDs Now Available in BC

    Incentives for Tubular LEDs Now Available in BC

    September 30, 2024 Changes in technology and safety prompt update of BC Hydro incentive to include Tubular lamp replacements BC Hydro’s Alliance of Energy Professionals members have been asking for it as far back as 2015, and it’s now arrived. Tubular lamp replacements will now qualify for incentive funding through the business energy saving incentives (BESI) program. “We… Read More…

  • 2024 IDEAL National Championship Wraps up in West Palm Beach, Florida

    2024 IDEAL National Championship Wraps up in West Palm Beach, Florida

    September 30, 2024 IDEAL successfully concluded the 2024 IDEAL National Championship, with the finals taking place in West Palm Beach, Florida this past weekend. Between April and July, IDEAL organized 10 qualifying events across Canada, engaging over 500 enthusiastic student apprentices eager to demonstrate their troubleshooting abilities. Each event’s top finisher advanced to the at-home… Read More…


Changing Scene