Guide to the Canadian Electrical Code, Part 1[i] – A Road Map: Section 44 — Theater Installations

by William (Bill) Burr[i]

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook but will hopefully provide some help in navigating the Code. These notes are based on the 26th edition.

Rule 44-000 Scope – states that Section 44 is a supplementary or amendatory section of the code and applies to electrical equipment and installations in buildings or parts thereof that are used for dramatic, operatic, motion picture or other shows. It should be noted that, because of rapid advances in the theater industry, some rules in this Section may refer to electrical equipment that may be obsolete. The CEC Handbook provides additional notes and diagrams to better explain this Section.

The Section is divided into 5 parts –
  • General rules, which applies to all theater installations,
  • Fixed stage switchboards,
  • Portable switchboards on stage,
  • Fixed stage equipment, and
  • Portable stage equipment.
General

Rule 44-100 Travelling shows – requires that a permit must be obtained before any electrical equipment is used for the initial performance of a travelling theater company, circus, or other type of travelling show, even if held in a theater. This ensures that a qualified person oversees the installation.

Rule 44-102 Wiring method requires that all wiring, in the stage, stage wing areas, orchestra pits and projection booths must be in rigid metal conduit, electrical metallic tubing, mineral-insulated cable, flexible metal conduit, armoured cable, lead-sheathed armoured cable, aluminum-sheathed cable, or copper-sheathed cable. Note that surface raceways are not permitted on the stage side of the Proscenium wall. Flexible cord or cable is permitted in accordance with Rules 44-252, 44-320, 44-350, and44-354of this Section and other wiring must be in accordance with Section 12 or Section 76. The proscenium is the frame separating the stage from the audience.

Rule 44-104 limits the number of border, stage pocket, or remote-control circuit conductors to the requirements of Rule 12-910.  In addition, the fill of conductors is limited to 20% of the cross-sectional area of auxiliary gutters or metal wireways.

Rule44-106 permits aisle light circuits to supply up to 30 – 25-watt lights.

Fixed stage switchboards

Rules 44-200 and 44-202 require fixed stage switchboards to:

  • be dead front,
  • have mechanical protection above the switchboard covering the full length as well as the space between the board and the wall behind,
  • have exposed live parts on the back of the board enclosed by the walls of the building, by metallic mesh grilles, or by other acceptable methods, and
  • have a self-closing door at the entrance of the enclosure.

Rule 44-204 specifies that only externally operated enclosed switches shall be used.

Rule 44-206 requires that a pilot lamp:

  • protected by a 15 amp or less overcurrent device, and
  • connected ahead of any master switch

be included in every switchboard enclosure that is connected to the circuit supplying the switchboard.

Rule 44-208 specifies that the fuse(s) for switchboards can be either plug or cartridge type but must be provided with an additional separate enclosure.

Rule 44-210 requires that an overcurrent device:

  • be connected in the ungrounded conductor of each circuit leaving the switchboard, and
  • thatnotwithstanding Rule 30-104, a 120-volt luminaire may be protected by an overcurrent device rated up to 100 A.

Rule 44-212 governs the installation of lighting dimmers and requires that:

  • they must be completely disconnected from the supply when they are in the open position,
  • resistance typedimmers that do not open the circuit may be connected in a grounded neutral conductor,
  • all current-carrying parts of dimmers must be enclosed to prevent accidental contact.

Rule 44-214 requires that stage and gallery pockets, which are receptacles in the performance space used to power stage lighting, be controlled from the switchboard.

Rule 44-216 provides that,due to the high heat and vibration that may be associated with switchboards, some additional requirements that insulated conductors must have are:

  • an ampacity concurrent with the switch or overcurrent device to which they are connected.
  • bushed holes where they pass through a metal enclosure,
  • wire strands soldered together fastening under a clamp or binding screw, and
  • soldered into a lug or connected to a solderless lug, where the insulated conductor is No.8 AWG or larger.
Portable switchboards on stage

Rule 44-250 provides that portable switchboards must be constructed in substantial enclosures, which may be open during operation, if there are no exposed live parts except on dimmer faceplates.

Rule 44-252 requires that portable switchboards be supplied from an externally operated, enclosed, fused master switch within the switchboard that:

  • is supplied by a flexible cord, type S, SO, or ST, that has sufficient ampacity to carry the total load current of the switchboard,
  • arranged to cut off current from all apparatus within the enclosure, except the pilot light, and
  • has an ampere-rating of the fuses not greater than the total load current of the switchboard.
Fixed stage equipment

Rule 44-300 specifies that footlights be installed in individual outlet boxes, where connected using rigid metal conduit or EMT, or in a metal trough to ensure bonding continuity. 

Rule 44-302 provides minimum thickness of not less than:

  • 0.78 mm thick for metal work forfootlights, borders, proscenium sidelights, and strips, and
  • 0.53 mm thick for metal work of bunches and portable strips.

Rule 44-304 requires that terminals of lampholders have a clearance of a minimum of 13mm from the metal trough. 

Rule 44-306 calls forsuitable guards to protect borders, proscenium sidelights, and strips from mechanical damage and accidental contact with combustible material.

Rule 44-308 specifies that suspended luminaires in borders and strips must be electrically and mechanically safe. 

Rule 44-310 because of possible severe vibration, conductor termination at lampholders need to have a positive and reliable connection by soldering or suitable solderless connections.

Rule 44-312 identifies that mogul lampholders need to be double-walled with adequate ventilation between the walls.

Rule 44-314 requires that conductors supplying field assembled foot, border, proscenium, and portable strip luminaires must have insulation rating suitable for the high operating temperatures involved and not less than 125 °C.

Rule 44-316 reiterates thatbranch circuit overcurrent protection for footlights, border lights, and proscenium sidelights must be consistent with Rule 30-104.

Rule 44-318 states that pendant lights containing lamps with more than 100-watt capacity need to be provided with a minimum 13mm mesh guard to contain and prevent falling glass.

Rule 44-320 specifies thatflexible cord supplying border lights must be:

  • S, SO, or ST type
  • fed from points on the grid iron or from other acceptable overhead points, but not from side walls,
  • arranged so that clamps and binding screws are free from strain,
  • provided with a metal bushing where passing through a metal or wooden enclosure, and
  • located to permit convenient access to terminals or binding posts inside the switchboard enclosure.

Rule 44-322 addresses the flexibility of wiring for arc pockets, which are receptacles that supply carbon-arc lighting fixtures.

Rule 44-324 states that at least one receptacle installed in gallery pockets be rated not less than 30 amps for use by higher capacity lighting equipment.

Rule 44-326 specifies thatarc and incandescent receptacles cannot be interchangeable and receptacles and plugs intended for the connection of:

Rule 44-328 requires that curtain motors must be the enclosed type.

Rule 44-330 governs the control and operation of flue dampers, which are located above the stage to allow smoke to exit in case of fire.Where stage flue dampers are released by an electrical device it must be:

  • held in the closed position and automatically released on power interruption,
  • controlled by at least two single-pole switches enclosed in self-closing but un-locked or latched metal boxes, one located at the electrician’s station, and the other as per Rule 28-604, and
  • rated for full circuit voltage, with minimal circuit resistance, and located in a protective metal box in the loft above the scenery.
Portable stage equipment

Rule 44-350 requires that electrical fixtures attached to scenery must be securely fastened and supplied with flexible cord or cable suitable for hard usage and selected in accordance with Rules 4-012 and 4-040. In addition, bushings must be used where stems of fixtures extend through the scenery.

Rule 44-352 directs that where festooned lighting is used that the joints be staggered and that guards or shades be used to prevent contact with combustible material.

Rule 44-354 states that supply cords be provided for wiring methods for:

  • arc lamps, bunches, or other portable equipment must be approved for extra-hard usage,
  • other miscellaneous portable equipment may be other than extra-hard usage, and,
  • all selected as per Rules 12-402 (1) and 12-406 9(1).

Rule 44-356 requires that special stage effects portable equipment must be acceptable to the local AHJ and located to prevent flames, sparks or hot particles contacting combustible material.


[i] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.


[i] Source: CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2024 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

Related Articles


Latest Articles

  • Guide to the Canadian Electrical Code, Part 1[i], 26th Edition– A Road Map: Section 56

    Guide to the Canadian Electrical Code, Part 1[i], 26th Edition– A Road Map: Section 56

    February 6, 2026 The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual Read More…

  • 3D Printing: Inside Lighting’s Next Revolution

    February 5, 2026 While 3D printing in mass production was once a dream, advancements in the technology have moved it more into the mainstream. The technique, which is also referred to as additive manufacturing, has rapidly evolved from a niche prototyping tool into a transformative production method for many sectors, including the lighting industry. As Read More…

  • Microgrids & Power Quality: Designing Resilient, Clean Facility Power

    Microgrids & Power Quality: Designing Resilient, Clean Facility Power

    February 5, 2026 In an era of extreme weather, aging infrastructure, and ever‑rising energy demands, many facility managers are rethinking their relationship with the grid. Microgrids offer a way to take control and operate autonomously when necessary. A microgrid is more than just backup, when designed properly, it becomes a platform for resiliency, efficiency, and Read More…

  • ITC 101: Understanding NEMA Ratings for Electrical Enclosures

    ITC 101: Understanding NEMA Ratings for Electrical Enclosures

    February 5, 2026 Understanding NEMA Ratings for Electrical Enclosures NEMA Ratings are an essential classification system used across North America to define the environmental and mechanical protection provided by electrical enclosures. Developed by the National Electrical Manufacturers Association (NEMA), these ratings help engineers, installers, and specifiers identify the appropriate enclosure type for industrial, commercial, and outdoor Read More…


Changing Scene

  • Lighting What’s Next: Stanpro Celebrates 65 Years

    Lighting What’s Next: Stanpro Celebrates 65 Years

    February 6, 2026 “We didn’t get here by standing still. For 65 years, we’ve shaped how we think, how we design, and what responsibility means,” the company said in a LinkedIn post. “Today, that thinking takes a new form. Not to change who we are, but to express our evolution more clearly. This is Stanpro, Read More…

  • Housing Priorities on Track in New Brunswick, but More Work to do: Hickey

    Housing Priorities on Track in New Brunswick, but More Work to do: Hickey

    February 6, 2026 Efforts to support the creation of new affordable housing and reduce chronic homelessness are on track, but there is still lots of work to do, according to David Hickey, the minister responsible for the New Brunswick Housing Corporation. New data indicates progress has been made on three key government priorities related to Read More…

  • BJ Electric is now Bernie’s Electric Supplies Ltd

    BJ Electric is now Bernie’s Electric Supplies Ltd

    February 6, 2026 BJ Electric has announced the company has rebranded as Bernie’s Electric Supplies Ltd, a nod to their founder. “BJ Electric Supplies is now Bernie’s Electric Supplies—in honor of our founder, Bernard Joseph Thompson, and the values that have guided the company for nearly 50 years. As we grow and evolve, this name Read More…

  • The Government of Canada Introduces the Build Canada Homes Act

    The Government of Canada Introduces the Build Canada Homes Act

    February 6, 2026 The Government of Canada has introduced the Build Canada Homes Act, legislation that will establish Build Canada Homes as a Crown corporation whose mandate will be dedicated to building affordable housing in communities across the country. As Canada’s affordable housing builder, this legislation will equip Build Canada Homes with the necessary tools to Read More…