Point Source Ventilation And You – Part II

Vent PCMK

 

Some point source fans accommodate plug and play features.

Paul Laplante (LaplanteRicard&Associés), in collaboration with Milan Jovanovic

In last week’s article I discussed the topic of point source ventilation stemming from bath fans, the need for them to be certified for performance and sound levels, Canada’s national building codes pertaining to spot ventilation and finally in Quebec’s case the Novoclimat guidelines and requirements. 

Let’s continue with information that hopefully will round out what you need to properly size /select/supply the proper amount of supply wiring in a given situation.

Many reliable manufacturers such as S&P (Soler Palau), Broan and Nutone now also show performance curves or charts at a level of 0.25 PSI in order to reflect the reality of most installations. In fact, it has been demonstrated when adding a couple of transitions (elbows) and taking into account the type of ducting used, the lengths found on average installs in housing projects or residences that the pressure rises substantially above normal standard HVI test requirements at 0.1 PSI.

How does this affect what you need? First and foremost, determine by rule of thumb, 1 CFM per square foot as a minimum. Once you have arrived at the result, look at the 0.25PSI level on the manufacturers’ data sheets and select the unit that meets the total CFM you calculated at that static level rather than the 0.1PSI.

So in a case where you believe you need 90 CFMs at .25 PSI, chances are you will have to move to a unit that shows 110 CFM at 0.1PSI with either a 4” or 6’’ transition collar (duct adapter).

Toggle Switches

Toggle Switches

Multi level condominium towers and you

The Canadian National Building Code CNB-2005 (Modified) Section 6.2.2 and/or 9.32.3 states in the event of inability to install a central HRV in each unit due to space and design constraints the following as an acceptable and recognised substitute: the installation of a 2 speed bath fan, with a mandatory continuous speed at all times always with the possibility of switching the unit off in the event of prolonged absence. S&P PC110X-2 model for example meets the minimum 90 CFM at 0.1 PSI in high speed at a level of less than 0.3 sones, while performing at 30 to 40 CFM in low speed continuous mode. The use of such a fan then meets or exceeds the minimum air change requirements of 1 complete air change in the housing unit, every 3 hours.

The catch: to avoid depressurization the above installation must have a way to compensate for the air extracted with new air. Depressurisation has negative effects on buildings (it can permit radon gas infiltration) and/or on mechanical products such as water heaters, fireplaces or stoves not equipped with outside air supplies (direct vents). Avoiding depressurization can be accomplished by means of a small duct system and 120 V damper and contactor linked to the operation of the fan while it is in continuous mode. Some colder areas of the country include a duct heater within the configuration. 

How many supply wires do I need?

It is critical when using a 2-speed, positive off during prolonged absence to provide for a 3-wire feed in leading to a two commutator wall plug. In this fashion a PC110X-2 for example will be in the ‘’on’’ position of one of the commutators, switch the fan on continuous low. This must be first satisfied in order to then energise the second high speed thru the second wall switch. The key is that end user, should he select the off function cannot bypass the continuous low function when he arrives back from his prolonged absence and forgets to rearm it, and in it’s stead attempt to put the fan on high speed. 

Vent Plug and Play

How it’s done.

Are 3 wires enough?

If I may, I would say no, not with today’s multi-featured bath fans. If anything, I would suggest in renovation projects to provide for 5 to 6 wires to the units.

Why? That’s a lot of wire in case… Yes but many of today’s fans can accept after-install accessories that upgrade them from simple fans to smart fans. Some accept add-on motion detectors, humidity detector, and even a complete change of grills to transform the ordinary unit in a beautiful light/night light grill configuration like S&P PC50 to 150 CFM units. 

Finally, you are unsure that the fan you have selected and put in your truck to go on the job site is adequate for the job at hand. You get in the install area, make a quick recheck of the CFMs required with that rule of thumb I described and… the room is now larger than anticipated or the owners decided to add a separate shower or spa.

What are you going to do? Install the fan you have that you now know will not meet the needs of the area? Return it to your wholesaler? What a waste of time.

Consider the available alternates that the new DC motor technology has given the forward thinking ventilation manufacturers and your problems are solved.

Some manufacturers now offer a fan like Soler Palau’s PCD110 series that, through a series of selectable switches on the unit, will provide you from 80CFM- 90-110-120 right up to 140 CFMs.The performances will be certified providing you install it with the corresponding 4” or 6” inch duct collar that is provided. I suggest you use a 6’’ preferably for 110CFM and up.The technology even gives you the choice of selecting between one with a humidity sensor or another with a motion detector.

I do hope I have managed to give you more insight into the do’s and don’ts related to the spot ventilation market for bath fans. I am also hopefulthat with this information in mind that you will continue to distinguish yourself as the go-to company, contractor, builder,promoter,architect or engineer for your knowledge, your push for the best, and the best satisfaction experience for the one who will benefit most from that all this care — your end user and customer for a long time to come.


 

Paul Laplante is a manufacturing agent and co-owner of LaplanteRicard& Associates. He has worked in the electrical and ventilation fields for more than 35 years. Milan Jovanovic has worked in the field of mechanical ventilation for a number of years and is a former president of A.S.H.R.A.E.’s Quebec City chapter (2005-2006).

 

Related Articles


Latest Articles

  • CAF-FCA Provides Recomendations on Apprenticeship Investment

    CAF-FCA Provides Recomendations on Apprenticeship Investment

    April 13, 2025 CAF-FCA have provided an outline of actionable recommendations—developed through national consultation—to enhance accessibility, reduce financial barriers, and better align apprenticeship training with industry needs. Source Read More…

  • New Report: Preparing Alberta’s Buildings for Severe Weather

    New Report: Preparing Alberta’s Buildings for Severe Weather

    April 13, 2025 Alberta is facing more severe weather events, with rising temperatures, wildfires, and more frequent extreme storms threatening homes and businesses. Our report, Preparing Alberta’s Buildings for Severe Weather−written in partnership with the Alberta Ecotrust Retrofit Accelerator program−highlights the need for deep retrofits to ensure the province’s buildings can withstand these changing conditions. Four… Read More…

  • CCA Bulletin: Managing Tariff Risks in Construction Projects

    CCA Bulletin: Managing Tariff Risks in Construction Projects

    April 13, 2025 This bulletin was prepared by select members of the Canadian Construction Association’s (CCA) General Contractors National Advisory Council. Its purpose is to assess the potential impacts of tariffs and counter-tariffs on general contractors in Canada focusing specifically on: In both areas, the bulletin explores both upstream and downstream impacts – examining how… Read More…

  • Video: ABB Installation Products Proudly Powering Canada

    Video: ABB Installation Products Proudly Powering Canada

    April 7, 2024 From coast to coast, ABB Installation Products is built by Canadians, for Canadians—delivering high-quality solutions that power industries and support communities across the country. Read More…


Changing Scene

  • PEI’s First Net Zero Ready School Officially Opens

    PEI’s First Net Zero Ready School Officially Opens

    April 13, 2025 Island students, their families and the Sherwood school community came together today to celebrate the opening of PEI’s first net zero ready school. The new Sherwood Elementary School, built next to the former school, offers over 82,000 square feet of space with many innovative features to promote enhanced learning experiences for up… Read More…

  • Nova Scotia Invests to Connect Nova Scotians to Skilled Trades

    Nova Scotia Invests to Connect Nova Scotians to Skilled Trades

    April 13, 2025 The Province is helping more Nova Scotians explore and connect to careers in skilled trades through a $10-million investment in the construction industry. The investment will support more skilled trades training through three key initiatives: “Nova Scotia needs more skilled trades professionals to support our growing economy and to build the homes,… Read More…

  • PEI Tables Bill Aimed to Eliminate Trade and Labour Barriers

    PEI Tables Bill Aimed to Eliminate Trade and Labour Barriers

    April 13, 2025 Hon. Rob Lantz, Premier of Prince Edward Island, introduced the Interprovincial Trade & Mobility Act in the provincial legislature. This bill will allow Prince Edward Island to eliminate unnecessary barriers to trade and labour mobility with reciprocating jurisdictions.   The Bill will accept provincial inspections and standards on goods coming from a… Read More…

  • PEI Minimum Wage Set to Increase

    PEI Minimum Wage Set to Increase

    April 13, 2025 Minimum wage in Prince Edward Island will increase incrementally to $17 per hour by April 1, 2026.  The Employment Standards Board reviews minimum wage annually and provides their recommendation to government.  Go HERE for more information Source Read More…