Guide to the Canadian Electrical Code, Part 1 — Instalment 14 

June 8, 2016

William (Bill) Burr

In this article: CE Code Section 24 — Health care areas. The code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

General

Rule 24-000 Scope, outlines that this section amends or supplements the general requirements of the code. It has been compiled by the Technical Committee on Applications of Electricity in Health Care along with the Committee on the Canadian Electrical Code, Part I, and provides specific rules for patient care areas and essential electrical systems in health care facilities. This section does not amend or supplement the provisions of Section 60 – Electrical communications systems, except for bonding as per rule 24-104(7) or equipment in shower stalls and bathtub enclosures as per rule 24-108.

Rule 24-002 Special terminology provides definitions for terms used in this section, which is additional or supplementary to the definitions in Section 0.

Section 24 is divided into three main parts: Patient care areas, Isolated systems, and Essential electrical systems.

Patient care areas

According to 24-002, patient care areas are areas intended primarily for the provision of diagnosis, therapy, or care. Also, note that patient care areas include not only hospitals but also patient care areas of other health care facilities and medical clinics where basic, intermediate or critical care is carried out. Appendix B contains important additional notes for this section.

Rule 24-100 describes that the rules of this part apply to patient care areas designated as basic, intermediate, or critical care as designated by the administration of the health care facility in accordance with CSA Z32-15 Electrical safety and essential electrical systems in health care facilities and CSA Z8000-11 Canadian health care facilities.

Rule 24-102 contains the rules for the characteristics of circuits in basic care areas. Communication or nurse call equipment must follow the rules of Section 16 for a Class 1 circuit.

Rule 24-104 deals with bonding to ground in basic care areas. Note also that exposed non-current-carrying metal parts of communication, radio, television and non-electrical equipment must be bonded to ground with a copper conductor sized as per Table 16A or 16B and connected to an equipment bonding conductor or bonding busbar.

Rule 24-106 outlines the requirements for installing receptacles in basic care areas. Where receptacles are intended for patient care they need to be located to prevent unintended use. Receptacles located where cleaning takes place need to be located 300mm above the floor. Receptacles installed in washrooms must be within 1.5m of a sink, outside of bathtub or shower stall and protected by a class A GFCI. Housekeeping receptacles need to be identified. All non-locking receptacles except those in bathrooms or washrooms must be hospital grade. Receptacles supplied from the essential electrical system must be exclusively coloured red. Isolated ground type receptacles cannot be used in this area.

Rule 24-108 permits emergency signaling and similar equipment manufactured to CAN/CSA-C22.2 No.60601 series of standards to be installed at normal heights in bathtub enclosures and shower stalls.

Rule 24-110 deals with the characteristics of branch circuits in intermediate and critical care areas. These circuits may be either a grounded system as in 24-102 or an isolated ground system as per rule 24-200. Branch circuits supplying loads within patient care environments must be 2-wire circuits except for multiphase equipment.

Rule 24-112 requires that bonding to ground in intermediate and critical care areas conform to rule 24-104, whether supplied from grounded distribution system or an isolated wiring system.

Rule 24-114 specifies that receptacles in intermediate and critical care areas must meet the requirements of rule 24-106 and be identified if supplied from an isolated system.

Rule 24-116 requires that receptacles in areas subject to standing or drenching fluids be protected with a class A GFCI or be supplied by an isolated system.

Isolated systems

According to 24-002, an isolated system is an electrical distribution system in which no circuit conductor is connected directly to ground.

Rule 24-200 outlines that rules 24-202 to 24-208 apply to isolated systems for circuits in intermediate and critical care patient care areas. Branch circuits supplying only fixed luminaires and permanently connected equipment may be supplied by a conventional grounded system as long as circuits are in separate raceways.

Rule 24-202 specifies the means of supply of isolated systems by the secondary of an isolating transformer, a motor-generator set, or an isolated battery powered inverter. Where multiple isolated power systems serve one patient care area, they must be bonded together.

Rule 24-204 outlines the required characteristics for single-phase isolated circuits.

Rule 24-206 provides that an individually isolated single phase system supplying only a single load may optionally use a line isolation monitor and that overcurrent devices need not be installed.

Rule 24-208 specifies the requirements for three-phase isolated systems.

Essential electrical systems

According to 24-002, an essential electrical system is a system that has the capability of restoring and sustaining a supply of electrical energy to specified loads in the event of a loss of the normal supply of energy.

Rule 24-300 sets out that rules 24-302 to 24-306 apply to portions of a health care facility in which the interruption of the normal power supply would jeopardize the safe and effective care of patients.

Rule 24-302 outlines that the health care administration designates which supply load circuits are essential electrical circuits and that the wiring of the essential electrical system must be kept separate from other wiring and equipment.

Rule 24-304 provides for the selection, installation and operation of transfer switches for essential electrical systems.

Rule 24-306 describes the requirements for an emergency supply

In the next instalment, we will discuss Section 26 — Installation of electrical equipment

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

Photo Credit: David Castillo Dominici and FreeDigitalPhotos.net


Read the rest of the instalments in the series:
Part 1: Guide to the CE Code, Part I – A Roadmap (Installment 1 in a Series)
Part 2:
A Road Map to the CE Code, Part I – Installment 2
Part 3: Guide to the Canadian Electrical Code, Part I – Installment 3
Part 4: A Road Map to the CE Code, Part 1 – Installment 4
Part 5: Guide to the Canadian Electrical Code, Part I — Installment 5
Part 6: Guide to the Canadian Electrical Code, Part I — Installment 6
Part 7: Guide to the Canadian Electrical Code, Part I — Installment 7
Part 8: Guide to the Canadian Electrical Code, Part I — Installment 8
Part 9:
Guide to the Canadian Electrical Code, Part I — Installment 9
Part 10: Guide to the Canadian Electrical Code, Part 1 – Installment 10
Part 11: Guide to the Canadian Electrical Code, Part 1 – Installment 11
Part 12: Guide to the Canadian Electrical Code, Part 1 — Instalment 12
Part 13: Guide to the Canadian Electrical Code, Part 1 — Instalment 13 
Part 14: Guide to the Canadian Electrical Code, Part 1 — Instalment 14
Part 15: Guide to the Canadian Electrical Code, Part I — Instalment 15


William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

 

 

 

Related Articles


Latest Articles

  • Celebrating 25 years: Hong Kong International Lighting Fair (Autumn Edition) Returns from October 27-30

    Celebrating 25 years: Hong Kong International Lighting Fair (Autumn Edition) Returns from October 27-30

    September 27, 2023 By Elle Bremmer Celebrating its 25th edition, the Hong Kong International Lighting Fair is set to illuminate the global lighting industry once again from October 27 to 30, 2023. This highly anticipated event, hosted at the Hong Kong Convention and Exhibition Centre, promises to showcase a wide range of state-of-the-art lighting innovations… Read More…

  • Remembering a Pillar of the Canadian Electrical Industry: Pierre Desilets

    Remembering a Pillar of the Canadian Electrical Industry: Pierre Desilets

    September 27, 2023 It is with profound sadness that we announce the passing of Pierre Desilets, a committed figure in the electrical industry, who had dedicated a lifetime to advancing safety standards, codes, and regulations. Pierre had been battling cancer with immense resilience for an extended period. His unwavering commitment to his work and his… Read More…

  • Housing Starts Flat in August

    Housing Starts Flat in August

    September 25, 2023 The trend in housing starts was flat in August at 244,507 units, up 0.8% from 242,552 units in July, according to Canada Mortgage and Housing Corporation (CMHC). The trend measure is a six-month moving average of the monthly SAAR of total housing starts for all areas in Canada. The monthly seasonally adjusted annual… Read More…

  • Lineman’s Testing Laboratories’ (LTL) Comprehensive Expertise Makes Rexel Aquisition an Ideal Partnership

    Lineman’s Testing Laboratories’ (LTL) Comprehensive Expertise Makes Rexel Aquisition an Ideal Partnership

    September 25, 2023 By Blake Marchand Earlier this year, Rexel announced the acquisition of Lineman’s Testing Laboratories (LTL), which allows Rexel to offer a complementary range of products and services and enhanced opportunities in the value-add market. LTL is a unique company with three comprehensive areas of expertise, Power Technical Services (Electrical Engineering & Substation… Read More…


Changing Scene

  • HPS Announces Ted Simpson as Vice-President of Marketing

    HPS Announces Ted Simpson as Vice-President of Marketing

    September 27, 2023 HPS is pleased to announce the appointment of Ted Simpson to the position of Vice-President of Marketing. Ted succeeds Michael Frayne as Michael transitions to the role of Senior Vice President of Power Quality and Power Conversion Solutions. Ted is a highly experienced marketing professional with over 20 years of expertise in… Read More…

  • New Funding for Apprenticeship in Alberta will Create 2,000 More Seats

    New Funding for Apprenticeship in Alberta will Create 2,000 More Seats

    September 25, 2023 A $12.4-million investment from Alberta’s government will create almost 2,000 new apprenticeship seats across the province. Alberta’s economy has momentum, and more skilled labourers are needed to support the province’s workforce, especially in the construction industry. To meet growing demand for highly skilled tradespeople across sectors, and in response to feedback from… Read More…

  • ABB Expands its Pointe-Claire Installation Products Facility

    ABB Expands its Pointe-Claire Installation Products Facility

    ABB is investing CA$16 million in its Installation Products Division manufacturing facility in Pointe-Claire, Canada. Read More…

  • Enhanced GST Rental Rebate Bill Proposed for Purpose-Built Rental Housing 

    Enhanced GST Rental Rebate Bill Proposed for Purpose-Built Rental Housing 

    September 22, 2023 On September 14, 2023, the Prime Minister announced that the government will introduce legislation to enhance the Goods and Services Tax (GST) Rental Rebate on new purpose-built rental housing, to incentivize construction of much-needed rental homes for Canadians. To build more rental housing, the removal of GST will apply to new purpose-built… Read More…