Fundamentals of Harmonic Distortion in a World of Rising Non-Linear Loads

Harmonics

 

May 7, 2018

By Owen Hurst

With a focus this month of power quality, test and measurement, it seems prudent to take a minute to return to the basics for understanding harmonic distortion, particularly as the use of items with non-linear loads continues to increase.

Harmonics have been around since the first AC generator was turned on over 100 years ago. However, harmonics were initially not an issue as they very minor over linear loads. It wasn’t until the 1960s that the impact of harmonic distortion became apparent. This is confirmed by V.J. Gosbell, an associate professor at the University of Wollongong who said, “Harmonic distortion is not generally due to the operation of the power system, and was largely absent before the 1960s. At about this time, a different type of customer load with electronic power supplies became popular.”[1] These new products, such as computers and household appliances with electronic controls, had a non-linear load, and if we consider how many items we now use with electronic control it is easy to see how harmonic distortion has become a major issue.

Variable frequency drives (VFDs) also cause a non-linear load that can create harmonic distortion for manufacturing and industrial applications as well.

Harmonics Chart 1

 

 

 

 

 

But first, let’s just step back and take a brief look at what exactly harmonic distortion is.

The easiest way to understand harmonic distortion is to consider the differences in linear and non-linear loads. If we have a standard AC source and a load draw that is linear the draw current will be sinusoidal in nature and for the most part does not disrupt the waveform (See fig.1). For ideal operation the draw does not create a distorted waveform but as mentioned is sinusoidal.
Harmonics Chart 2Harmonics Chart 3

However, if the load draw is non-linear (such as with electronic controls) the waveform is distorted and no longer sinusoidal even though it is drawing from a sinusoidal source (See fig.2). In reality the complexity of the fundamental wave is not important, it is just an element of multiple waveforms that are called harmonics.

Harmonics therefore have frequencies that are integer multiples of the waveform’s frequency. To provide an example on a “60Hz fundamental waveform, the 2nd, 3rd, 4th, and 5th harmonic components will be at 120Hz, 180Hz, 240Hz, and 300Hz respectively.

Thus, harmonic distortion is the degree to which a waveform deviates from its pure sinusoidal values as a result of the summation of all these harmonic elements.”

Important to note here is that harmonics should not be confused with spikes, dips, impulses, oscillations or other forms of transients.

Now that we have identified what harmonics are we can consider how they are measured, which inevitably is the determining factor for identifying if harmonic distortion is causing negative effects on the system. To do this it is necessary to measure total harmonic distortion (THD). THD “is the summation of all harmonic components of the voltage or current waveform compared against the fundamental component of the voltage or current wave.”[5] This can be calculated using a standard mathematical equation, or more often is determined using test and measurement devices that perform the calculations for you. Either way, the higher the percentage the more harmonic distortion on the signal.

Although there are no enforced standards for harmonic distortion they have received a good deal of attention and many utilities have their own regulations which tend to follow the “IEEE Recommended Practices and Requirements for Harmonic Control in Electric Power Systems” (IEEE std. 519-1992).

Standard 519 by the IEEE notes that “computers and allied equipment, such as programmable logic controllers, frequently require ac sources that have no more than 5% harmonic voltage distortion factor, with the largest single harmonic being no more than 3% of the fundamental voltage. Higher levels of harmonics result in erratic, sometimes subtle, malfunctions of the equipment that can, in some cases, have profound consequences.”

Although the standard is voluntary, it is an extremely valuable guideline that has been adopted by many utility companies across the country. With overall harmonic distortion lower than 5%, and no one harmonic registering higher than 3% equipment damage or malfunction is unlikely.

Harmonics Chart 4

However, if harmonic distortion is higher there is the potential for costly equipment damage and potentially dangerous situations for employees. “High levels of harmonic distortion can cause such effects as increased transformer, capacitor, motor or generator heating, misoperation of electronic equipment, incorrect readings on meters, misoperation of protective relays and interference with telephone circuits.”

Harmonic distortion can substantially limit the life cycle of equipment and potentially lead to outright system failure, resulting in additional costs for equipment replacement and loss of revenue due to potential shutdowns. Further, in rare cases, the heat generated in motors and drives has the potential to cause fires, which is obviously a safety hazard.

So, it is critically important to ensure that measurements of harmonics are undertaken and that any harmonic distortion that presents potential issues are addressed. There are several ways to mitigate harmonic distortion, the most common being the installation of a harmonic filter which shunts or absorbs specific harmonics from the power supply. Another potential resolution is a Pulse Width Modulated (PWM) rectifier which can eliminate a number of harmonics to gain acceptable levels.

Harmonic distortion is not going to go away, and we continue to increase our use of items with non-linear load draws increasing issues with harmonic distortion that will inevitably require more direct attention from regulatory bodies.

Owen Hurst is Managing Editor of EIN’s sister publication, Panel Builder & Systems Integrator: http://panelbuildersystemsintegrator.ca

Notes
1. V.J. Gosbell. “Harmonic Distortion in the Electrical Supply System,” PQC TECH Note 3 (Power Quality Centre), 2000, p. 2
2. Total Harmonic Distortion and Effects in Electrical Power Systems, Associated Power Systems, https://www.aptsources.com/wp-content/uploads/pdfs/Total-Harmonic-Distortion-and-Effects-in-Electrical-Power-Systems.pdf
3. Total Harmonic Distortion and Effects in Electrical Power Systems
4. Power System Harmonics: A Reference Guide to Causes, Effects and Corrective Measures, Allen-Bradley, April 2001, p. 1
5. Total harmonic Distortion and Effects in Electrical Power Systems
6. Power System Harmonics, p. 3

Sources
Power System Harmonics: A Reference Guide to Causes, Effects and Corrective Measures, Allen-Bradley, April 2001, pp. 1-7
Alex baitch, M.H. Bollen and V.J. Gosbell, “The Reporting of Distribution Power Quality Surveys” CIGRE/IEEE PES International Symposium on Quality and Security of Electrical Power Delivery Systems, October 2003, pp. 48-53
Total Harmonic Distortion and Effects in Electrical Power Systems, Associated Power Systems, https://www.aptsources.com/wp-content/uploads/pdfs/Total-Harmonic-Distortion-and-Effects-in-Electrical-Power-Systems.pdf
V.J. Gosbell. “Harmonic Distortion in the Electrical Supply System,” PQC TECH Note 3 (Power Quality Centre), 2000, pp. 2-10

Images Source: http://automationwiki.com/index.php/Total_Harmonic_Distortion

 

Related Articles


Latest Articles

  • Stephanie Medeiros on EV Infrastructure in Canada, Innovative Technologies, Well-Planned Charging Networks, & Commercial Fleets

    Stephanie Medeiros on EV Infrastructure in Canada, Innovative Technologies, Well-Planned Charging Networks, & Commercial Fleets

    September 3, 2026 By Blake Marchand In this Q&A with Stephanie Medeiros, the Head of Mobility at Schneider Electric Canada provides insight into her perspective on EV charging infrastructure in Canada, factors that will contribute to growing EV adoption, grid modernization for commercial fleets, the role of Vehicle-to-Grid and other innovative approaches to electrification. The focus of… Read More…

  • LEDVANCE: Understanding Light Beam Angles

    LEDVANCE: Understanding Light Beam Angles

    September 3, 2026 Light Beam Angles: How It Affects Different Types of Lighting, Where It Is Applied & What to Consider When Choosing the Right One Beam angle is important in lighting design. It determines how light spreads within a space and influences both functionality and atmosphere. By understanding beam angles, you can achieve both… Read More…

  • ITC 101 Series: Why Certifications (UL, CSA) Matter in Industrial Components

    ITC 101 Series: Why Certifications (UL, CSA) Matter in Industrial Components

    September 2, 2026 By ITC Electrical Components When selecting industrial electrical components, certification is more than a logo on a datasheet. A certification mark indicates that a product or component has been independently evaluated against specified requirements for its intended market. In North America, selecting products with the appropriate certification can affect regulatory acceptance, equipment… Read More…

  • Project Spotlight: Leigh Square Fountain

    Project Spotlight: Leigh Square Fountain

    September 2, 2026 In spring 2025, the City of Port Coquitlam unveiled a transformed Leigh Square, reimagined as a vibrant, accessible, and welcoming gathering place in the heart of downtown. At the heart of the renewed plaza, a Bellagio-style programmable dancing fountain is integrated directly into the paving—three interlocking rings where jets rise, fall, and… Read More…


Changing Scene

  • 2026 Ontario Apprenticeship Awards Call for Nominations

    2026 Ontario Apprenticeship Awards Call for Nominations

    September 3, 2026 Skilled Trades Ontario is proud to open nominations for the 2026 Ontario Apprenticeship Awards, recognizing outstanding apprentices, journeypersons, organizations and skilled trades leaders who are helping strengthen Ontario’s apprenticeship system. Award recipients will be announced at the Ontario Apprenticeship Summit on November 4, 2026, at the Toronto Congress Centre. Nominations must be submitted… Read More…

  • Bartle & Gibson Announces New Partnership with Hubbell Canada

    Bartle & Gibson Announces New Partnership with Hubbell Canada

    September 3, 2026 Bartle & Gibson Co. Ltd., an Alberta-based premier plumbing, heating and electrical distributor and Hubbell Canada have announced a new regional partnership enabling increased access to Hubbell Canada’s end-to-end electrical product portfolio across Western Canada. “With our strong presence in the west through 31 branches and counting located in Alberta, Saskatchewan, British… Read More…

  • Bartle & Gibson Opens Salmon Arm Location

    Bartle & Gibson Opens Salmon Arm Location

    September 3, 2026 Bartle & Gibson opened their new Salmon Arm location on July 20th. The Salmon Arm location features: This site is strategically positioned in the city of Salmon Arm, located near to the busy Picadilly Mall.  Salmon Arm branch is located at: 621- 10 Street SW Salmon ARM, BC V1E 1T1 Photo Source Read More…

  • MacKinnon Magnetics Announces Partnership with Resilient Sales Corporation in Northeastern Ontario

    MacKinnon Magnetics Announces Partnership with Resilient Sales Corporation in Northeastern Ontario

    September 3, 2026 MacKinnon Magnetics is pleased to welcome Resilient Sales Corporation as their newest sales agency partner. Resilient Sales will represent MacKinnon Magnetics across Northeastern Ontario, including the Districts of Muskoka and Parry Sound. Key markets include Sudbury, North Bay, Timmins, Kirkland Lake, Sault Ste. Marie, Huntsville, Bracebridge and Parry Sound. “This partnership expands… Read More…