Test Your Knowledge of the Canadian Electrical Code – Part 1 — The Answers: Fire Alarm Systems

EIN Code Quiz2 400

June 11, 2021

In the last installment, you had the opportunity to answer our questions about the Code and best practices. Here are the answers to those questions.

Fire Alarm Systems, Smoke and Carbon Monoxide Alarms, and Fire Pumps

Q: What rule specifies the requirements for insulated conductors and cables in fire alarm systems and what are the requirements?

A: Rule 32-100 specifies the requirements for insulated conductors and cables in fire alarm systems which include:

  • copper material
  • ampacity
  • use of optical fiber cables
  • use of stranded conductors
  • insulation rated at 300 volts
  • determining wire size for raceways or integral assemblies
  • selection in accordance with rules 12-102(3)or 12-122(1)

Q: What rule requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller, except?

A: Rule 32-306 requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller:

  • Except a circuit breaker that is permanently labeled identifying it as a fire pump disconnect.
  • In addition, the circuit breaker must be lockable in the closed position and may be in the separate service box as in Rule 32-304

Q: In the case where this circuit breaker is installed in an emergency power supply circuit between the emergency power source and the fire pump transfer switch, the rating of the circuit breaker shall be?

A: As per rule 28-200:

  • Be set or rated to not less than the rating of the overcurrent protection provided integral with the fire pump transfer switch
  • Indefinitely carry the locked rotor current of the fire pump
  • Where it is installed in a normal supply circuit be rated not less than the overcurrent protection of the fire pump controller
  • Where the circuit breaker is installed in an emergency supply feeder between the emergency generator and the fire pump transfer switch, the feeder must bypass the generator main circuit breaker and be connected directly to the emergency generator.

Go HERE to discuss

Related Articles


Latest Articles


Changing Scene

  • SATCO Celebrates 60 Years of Excellence in Lighting, NUVO Marks 20 Years of Design Innovation

    SATCO Celebrates 60 Years of Excellence in Lighting, NUVO Marks 20 Years of Design Innovation

    April 10, 2026 SATCO proudly announces the celebration of its 60th anniversary, marking six decades of sustained growth, innovation, and service excellence. Concurrently, NUVO, a prominent lighting brand under the SATCO umbrella, celebrates its 20th anniversary, highlighting two decades of cutting-edge design and creative solutions for residential and commercial spaces. Founded in 1966, SATCO has Read More…

  • D.A.D. Sales Welcomes New Team Members

    D.A.D. Sales Welcomes New Team Members

    April 10, 2026 D.A.D. Sales announced the addition of Bradey Cameron as an Application Specialist on the D.A.D. Sales Solutions team, Katherine Dickson as an Account Manager on the D.A.D. Sales team, supporting Northern Alberta, and Wendy Dyble as an Account Manager / Inside Sales on the D.A.D. Customer Service Team. “Bradey brings a strong Read More…

  • Liteline Introduce New Regional Sales Manager for GTA

    Liteline Introduce New Regional Sales Manager for GTA

    April 10, 2026 Liteline announced on LinkedIn that Peter McCumber has joined their team as Regional Sales Manager for the GTA. “We are excited to welcome Peter as Liteline’s Regional Sales Manager-GTA! Peter brings more than two decades of experience in the electrical manufacturing and wholesale industry, where he has established himself as a dynamic Read More…

  • Dixon Relocates Mississauga Branch to Better Serve Customers

    Dixon Relocates Mississauga Branch to Better Serve Customers

    April 10, 2026 Dixon proudly announces the relocation of its Mississauga branch to 6197 Kennedy Road, enhancing accessibility and customer convenience. Strategically positioned along a busy corridor with excellent access to Highways 401, 410 and 403, the new 14,000-square-foot facility offers improved convenience for customers and partners. The branch features a modern storefront, an enhanced Read More…