Test Your Knowledge of the Canadian Electrical Code – Part 1 — The Answers: Fire Alarm Systems

EIN Code Quiz2 400

June 11, 2021

In the last installment, you had the opportunity to answer our questions about the Code and best practices. Here are the answers to those questions.

Fire Alarm Systems, Smoke and Carbon Monoxide Alarms, and Fire Pumps

Q: What rule specifies the requirements for insulated conductors and cables in fire alarm systems and what are the requirements?

A: Rule 32-100 specifies the requirements for insulated conductors and cables in fire alarm systems which include:

  • copper material
  • ampacity
  • use of optical fiber cables
  • use of stranded conductors
  • insulation rated at 300 volts
  • determining wire size for raceways or integral assemblies
  • selection in accordance with rules 12-102(3)or 12-122(1)

Q: What rule requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller, except?

A: Rule 32-306 requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller:

  • Except a circuit breaker that is permanently labeled identifying it as a fire pump disconnect.
  • In addition, the circuit breaker must be lockable in the closed position and may be in the separate service box as in Rule 32-304

Q: In the case where this circuit breaker is installed in an emergency power supply circuit between the emergency power source and the fire pump transfer switch, the rating of the circuit breaker shall be?

A: As per rule 28-200:

  • Be set or rated to not less than the rating of the overcurrent protection provided integral with the fire pump transfer switch
  • Indefinitely carry the locked rotor current of the fire pump
  • Where it is installed in a normal supply circuit be rated not less than the overcurrent protection of the fire pump controller
  • Where the circuit breaker is installed in an emergency supply feeder between the emergency generator and the fire pump transfer switch, the feeder must bypass the generator main circuit breaker and be connected directly to the emergency generator.

Go HERE to discuss

Related Articles


Latest Articles


Changing Scene

  • Intralec Named New Sales Agency Partner for IDEAL Electrical in Central & Southwestern Ontario

    Intralec Named New Sales Agency Partner for IDEAL Electrical in Central & Southwestern Ontario

    July 7, 2025 Intralec Electrical Products is proud to announce our new partnership with IDEAL Electrical as their sales agency for the Central & Southwestern Ontario regions. As a Canadian manufacturer with over 60 years of experience producing quality products—many of which, like the Can-Twist wire connector and Yellow 77 lubricant, are made in Ajax,… Read More…

  • City of Winnipeg Continues to Improve Online Permits System

    City of Winnipeg Continues to Improve Online Permits System

    July 4, 2025 The City of Winnipeg has launched an improved Permits Online web portal. This upgrade aims to make the permit process more convenient for customers. Permits Online is a one-stop shop to manage the permit process. Now, the web portal is easier to use because customers can navigate it using their mobile device. The portal… Read More…

  • Schneider Electric Launches Chapter 3 of Sustainability School

    Schneider Electric Launches Chapter 3 of Sustainability School

    July 4, 2025 Schneider Electric, the leader in the digital transformation of energy management and automation, has launched Chapter 3 of its online Sustainability School, a free training program designed to empower its channel ecosystem partners to become leaders in sustainability. This chapter will focus on teaching businesses how to decarbonize and unlock the competitive… Read More…

  • United Chargers Launches Grizzl-E Club Charger-as-a-Service Subscription Model

    United Chargers Launches Grizzl-E Club Charger-as-a-Service Subscription Model

    July 4, 2025 United Chargers Inc., known for the Grizzl-E line of EV chargers, announces Grizzl-E Club, a first-of-its-kind charger as a service that provides a free EV Charger and pays drivers back for charging. Grizzl-E Club is designed to make EV ownership more rewarding, accessible, and future-ready. Beginning July 1st, Canadians can join the Grizzl-E… Read More…