Guide to the Canadian Electrical Code, Part I

Bill Burr

Sept 3, 2020

By William (Bill) Burr

Since earlier articles were based on the 23rd Edition of the CEC, Part I, I have revised this series of articles to reflect any changes made pursuant to the 24th and 25th Editions. (The 24th Edition of the CEC, Part I, (C22.1-18) * is available from CSA Group. The 25th Edition (C22.1-21) is scheduled to be published in January 2021.

The code is a comprehensive document. Sometimes, it can seem quite daunting to quickly find the information you need. In this current series of articles, I will provide a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating while reading the code. Here in this issue: Section 22 — Locations in which corrosive liquids, vapours, or excessive moisture are likely to be present.

General

Section 22 amends or supplements the general requirements of the code. It provides specific rules for locations classified as Category 1 (moisture) or Category 2 (corrosive) environments that are significant enough to interfere with normal operation of electrical equipment.

A Category 1 location is defined as one where moisture in the form of vapour or liquid is present. The moisture can be caused by condensation, dripping or splashing of liquid, or other means. A Category 2 location is defined as one where corrosive liquids or vapours are likely to be present. Where neither Category is mentioned in a rule in this section, then the rule applies to both categories. Appendix B contains examples of some Category 1 and 2 occupancies.

Equipment

As per rule 22-100, only equipment that is essential to the process being carried out in that area may be located in a Category 1 or 2 location, as per Appendix B and Table B22-1. Service equipment, motors, panelboards, switchboards, and similar equipment need to be installed outside the category area. This includes any enclosures containing molded case circuit breakers in a Category 2 location, unless they have been approved and marked as suitable for that application, because internal corrosion can occur.

Rules 22-102 (1) to (6) outline the types of construction required of equipment to be installed in the various moist or corrosive atmospheres. Electrical equipment located in a Category 1 location must be suitable for wet locations. Electrical equipment located in a Category 2 location must be corrosion resistant. Where the electrical equipment is, or is likely to be, partially or wholly submerged, it must be of a submersible type of construction. This information is marked on the equipment if not self-evident.

Rules 22-104 to 22-108 specify requirements for wiring devices, connectors, flexible cords, and portable power cables to be installed or used in Category 1 or Category 2 locations.

Wiring

Rule 22-200 provides the requirements for wiring in Category 1 locations. Generally, insulated conductors and cables must be selected in accordance with Rule 4-008(1) and Table 19. Note that NM cable must be NMU or NMWU, MI cable must be spaced 6mm from any wall at supports, and aluminum conductors must have joints adequately sealed against moisture.

Rule 22-202 provides the requirements for wiring in Category 2 locations. All insulated conductors and cables must have protection from corrosion. NMW and NMWU cable is permitted. Raceways, Insulated Conductors, and cables may only be used as permitted by Table 19. MI, alu-sheathed and copper-sheathed cable must be suitably corrosion protected. Any termination or joint of aluminum conductors must be adequately sealed against ingress of corrosive liquids or vapours.

Rule 22-204 outlines the appropriate wiring methods in buildings housing livestock or poultry. Again generally, these are wet or damp locations and all wiring must be selected in accordance with Rule 4-008(1), with consideration given to adequate ventilation for a damp location. NMW or NMWU cable may be used, but aluminum conductors may not, and NMS cable must be provided with mechanical protection against damage by rodents.

Rule 22-206 deals with wiring in curling or skating rinks. Generally, lighting areas are subject to condensation so wiring must be selected in accordance with Rule 4-008(1) and Table 19 for wet locations. Other areas may be wired in accordance with Section 12, observing any moisture conditions. Areas with adequate mechanical ventilation (at least three changes per hour) may be considered dry locations.

Drainage, sealing, and exclusion of moisture and corrosive vapour

Rules 22-300 and 22-302 specify methods for excluding moisture and corrosive vapours from entering conduit, insulated conductors and cables, equipment, or locations through the use of suitable fittings, drip loops, adequate drainage, sealing, and orientation.

Circuit control

Rule 22-400 requires that each circuit in a Category 1 or 2 location must be capable of being de-energized from outside the location.

Materials

Rule 22-500 specifies that all metal materials including conduit, enclosures, and even every nut, bolt and screw must be corrosion protected or resistant to the specific corrosive environment.

Bonding

Rule 22-600 requires all non-current carrying metal parts of equipment to be bonded to ground as per Section 10.

Sewage lift and treatment plants

Rules 22-700 to 22-710 apply to installations in sewage lift, pumping stations and treatment plants where moisture, corrosion, explosions, fire, and atmospheric poisoning can occur. Note that the rules of Section 18 apply to associated methane gas generating facilities.

Rule 22-702 outlines some special terminology used in this subsection to define continuous positive pressure ventilation, dry well, suitably cut off, and wet well.

Rule 22-704 provides guidelines for the classification of these types of areas that may be both Category 1 or 2, and hazardous locations under Section 18. Reference material for hazardous area classification can be found in NFPA 820. Appendix B also has some notes regarding safety issues in these types of facilities.

Rule 22-706 specifies that wiring methods in these types of areas shall be in accordance with Rules 22-200, 22-202 or Section 18 depending on the location classification. Note that there are some restrictions, conditions and special handling for metal conduit, tubing, armoured cable, mineral-insulated cable, aluminum sheathed cable, and copper-sheathed cable.

Electrical equipment

Rule 22-708 specifies that electrical equipment in these types of areas shall be in accordance with the other applicable sections of the code or Section 18, depending on the location classification. Note that there are some restrictions, conditions and special handling for receptacles, lighting switches, unit emergency lighting equipment, emergency lighting control units, heating equipment, motors, and any electrical equipment in a wet well. Also note in sub-rule 22-708(4) that ventilation fans shall not be located in a wet well. One other significant sub-rule 22-708(5) requires that areas provided with continuous positive ventilation must be interlocked to de-energize all electrical equipment if the ventilating equipment becomes inoperative, unless the electrical equipment in that area is marked for use in an explosive gas atmosphere location.

Rule 22-710 requires all structural steel below ground, in contact with earth, to be bonded to the system ground.

A new section is being added to the 25th edition of the Code. Note that Authorities Having Jurisdiction have various schedules for adopting a new edition of the Code. Check with your local AHJ if these new rules are in force in your area.

Farm buildings housing livestock

New Rules 22-800 to 22-808 set requirements for electrical equipment and installation in farm buildings housing livestock.

Rule 22-802 provides new terminology used in this sub-section that are not contained in Section 0, and include definitions for Wash-down, Specialty type equipment, Suitably cut off, and Livestock.

Rule 22-804 sets out the Classification of these areas as either Category 1 or Category 2 as per Rule 22-100, and notes that locations in a farm building suitably cut off from a Category 1 or 2 location are considered dry locations.

Rule 22-806 requires that electrical equipment, except specialty equipment, be installed in accordance with Rules 22-102 to 22-108 above and additionally requires that:

• wire connectors for permanently connected equipment contain anti-corrosion compound

• electrical equipment incorporating overcurrent devices be installed in locations suitably cut off from Category 1 or Category 2 locations, or in enclosures with continuous positive pressure ventilation in as per Rule 22-702

• receptacles and general use switches installed in a wash-down area be protected by a suitable enclosure as per Rule 2-400

• exposed lamps be shatter-resistant and not a pendant lampholder

Rule 22-808 outlines that:

• wiring methods be in accordance with Rule 22-202 except that EMT not be used, grounding and bonding conductors be insulated or have corrosion protection, and all exposed connections have corrosion protection

• aluminum conductors not be used, except for feeders supplying panelboards as per Rule 22-806

• cables without metallic armour be protected from rodents by rigid steel or rigid non-metallic conduit when installed less than 300 mm above any horizontal surface, on the side of floor joists less than 100 mm below upper surface of floor joists, in attics or concealed spaces

• all raceways, fittings, junction boxes, cable assemblies and associated connectors, devices and covers be corrosion resistant

In the next instalment we will be discussing Section 24 — Patient care areas.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Related Articles


Latest Articles


Changing Scene