The Importance of Trip-Free Operation and Its Characteristics

Trip-free circuit breakers

 

Anthony T. Ricciuti

One of the many often desirable characteristics in the specifications and marketing literature for medium voltage circuit breakers is “trip-free.” Unfortunately, there are many misconceptions about this characteristic.
Definitions

For IEEET rated products, there are several related definitions of “trip-free”:

•    In the most general definition of “trip-free,” the contacts of the circuit breaker must return tothe open position and remain there when an opening operation follows a closing operation,regardless of whether the closing signal, force,or action is maintained.

•    A common variant is called “electrically trip-free.” For a medium voltage circuit breaker tobe considered electrically trip-free, the circuit breaker must be able to receive and respond to an electrical opening signal regardless of whether an electrical closing signal is energized.

•    “Mechanically trip-free” operations refer to a mechanical release mechanism that can open the medium voltage circuit breaker regardless of whether any closing release device operated by any means is activated or maintained.Medium voltage circuit breakers can also be hydraulically trip-free or pneumatically trip-free if they contain a hydraulic or pneumatic opening release device, respectively,that are capable of opening the circuit breaker regardless of whether any closing release device operated by any means is activated or maintained.

Any of these variants of trip-free operation may include a trip-free relay, in which its operation alters a closing release circuit, permitting an opening release to operate unimpeded by a closing release operation in any state. For IEC rated products, although the standard recommends that the suitability for trip-free operations should be provided to customers that are specifying medium voltage circuit breakers,no specific definition is provided for this function.

Physical requirements

For IEEE rated products, if a mechanical opening release operation is maintained on a medium voltage circuit breaker, then any closing release operation signal must not result in contact movement that reduces the open gap between the contacts by more than 10%. This characteristic is often confused with the definition of trip-free.However, if any opening release operation isinitiated simultaneously with any closing release operation signal, contact movement up to and including a momentary touching of the main circuit breaker contacts is acceptable before the circuit breaker completes the opening operation.

Additionally, because electrical opening release operation circuits typically employ auxiliary switch contacts internal to the circuit breaker, and therefore the electrical release operation circuit remains open until the main contacts of the circuit breaker have closed, when an electrical opening release operation circuit is maintained, the momentary touching of the main contacts is acceptable before the circuit breaker completes the opening operation.

Figure 1: Eaton medium voltage circuit breaker operation

Eaton Circuit breaker


Anthony T. Ricciuti is a Specialist Engineer at Eaton, a power management company with 2014 sales of US$22.6 billion. Anthony has a Bachelor’s degree in Mechanical Engineering and more than 20 years of experience in the design, testing, and analysis of circuit breakers. This article first appeared as an Eaton white paper, www.eaton.com/Eaton/OurCompany/WhitePapers/FeaturedWhitePapers/index.htm.

Related Articles


Latest Articles


Changing Scene

  • LEDVANCE Canada Announces Leadership Updates

    LEDVANCE Canada Announces Leadership Updates

    February 19, 2026 LEDVANCE Canada is sharing two leadership updates that further strengthen support for customers and channel partners across the country. Lori Bagazzoli has been appointed Head of Strategic Sales – LEDVANCE Canada, with a focus on expanding support for the Project and Specification market and accelerating growth in strategic opportunities. In this role, Lori Bagazzoli Read More…

  • Franklin Empire Inc. Announces Acquisition of O’Neil Electric Supply, Strengthening its Presence in Ontario and Eastern Canada

    Franklin Empire Inc. Announces Acquisition of O’Neil Electric Supply, Strengthening its Presence in Ontario and Eastern Canada

    February 18, 2026 Franklin Empire Inc., a leading independent electrical distributor in Eastern Canada, is proud and excited to announce that it has entered into a definitive agreement to acquire O’Neil Electric Supply, an Ontario-based electrical distributor, subject to customary closing conditions, including receipt of required regulatory approvals. This strategic acquisition further strengthens Franklin Empire’s Read More…

  • Nominations Now Open for 8th Biennial MEET Innovation Awards

    Nominations Now Open for 8th Biennial MEET Innovation Awards

    February 13, 2026 The Mechanical Electrical Electronic Technology Show (MEET) is pleased to announce that the ‘MEET Innovation Awards’ will return as part of the 2026 edition of the show. The purpose of these awards is to recognize innovative products in the industry. Individuals and businesses are encouraged to nominate themselves or others by completing this online form no Read More…

  • 2026 ECABC Hall of Fame Nominations

    2026 ECABC Hall of Fame Nominations

    February 12, 2026 On June 2nd, ECABC will hold a Hall of Fame Induction Ceremony as part of their Awards Gala Dinner at the Association’s 2026 Conference and AGM in Kelowna. ECABC would like to invite you to nominate an extraordinary individual from the electrical industry to join the organizations esteemed Hall of Fame! Induction into the Read More…