Paul Laplante (LaplanteRicard&Associés), in collaboration with Milan Jovanovic

In last week’s article I discussed the topic of point source ventilation stemming from bath fans, the need for them to be certified for performance and sound levels, Canada’s national building codes pertaining to spot ventilation and finally in Quebec’s case the Novoclimat guidelines and requirements. 

Let’s continue with information that hopefully will round out what you need to properly size /select/supply the proper amount of supply wiring in a given situation.

Many reliable manufacturers such as S&P (Soler Palau), Broan and Nutone now also show performance curves or charts at a level of 0.25 PSI in order to reflect the reality of most installations. In fact, it has been demonstrated when adding a couple of transitions (elbows) and taking into account the type of ducting used, the lengths found on average installs in housing projects or residences that the pressure rises substantially above normal standard HVI test requirements at 0.1 PSI.

How does this affect what you need? First and foremost, determine by rule of thumb, 1 CFM per square foot as a minimum. Once you have arrived at the result, look at the 0.25PSI level on the manufacturers’ data sheets and select the unit that meets the total CFM you calculated at that static level rather than the 0.1PSI.

So in a case where you believe you need 90 CFMs at .25 PSI, chances are you will have to move to a unit that shows 110 CFM at 0.1PSI with either a 4” or 6’’ transition collar (duct adapter).

Toggle Switches

Toggle Switches

Multi level condominium towers and you

The Canadian National Building Code CNB-2005 (Modified) Section 6.2.2 and/or 9.32.3 states in the event of inability to install a central HRV in each unit due to space and design constraints the following as an acceptable and recognised substitute: the installation of a 2 speed bath fan, with a mandatory continuous speed at all times always with the possibility of switching the unit off in the event of prolonged absence. S&P PC110X-2 model for example meets the minimum 90 CFM at 0.1 PSI in high speed at a level of less than 0.3 sones, while performing at 30 to 40 CFM in low speed continuous mode. The use of such a fan then meets or exceeds the minimum air change requirements of 1 complete air change in the housing unit, every 3 hours.

The catch: to avoid depressurization the above installation must have a way to compensate for the air extracted with new air. Depressurisation has negative effects on buildings (it can permit radon gas infiltration) and/or on mechanical products such as water heaters, fireplaces or stoves not equipped with outside air supplies (direct vents). Avoiding depressurization can be accomplished by means of a small duct system and 120 V damper and contactor linked to the operation of the fan while it is in continuous mode. Some colder areas of the country include a duct heater within the configuration. 

How many supply wires do I need?

It is critical when using a 2-speed, positive off during prolonged absence to provide for a 3-wire feed in leading to a two commutator wall plug. In this fashion a PC110X-2 for example will be in the ‘’on’’ position of one of the commutators, switch the fan on continuous low. This must be first satisfied in order to then energise the second high speed thru the second wall switch. The key is that end user, should he select the off function cannot bypass the continuous low function when he arrives back from his prolonged absence and forgets to rearm it, and in it’s stead attempt to put the fan on high speed. 

Vent Plug and Play

How it’s done.

Are 3 wires enough?

If I may, I would say no, not with today’s multi-featured bath fans. If anything, I would suggest in renovation projects to provide for 5 to 6 wires to the units.

Why? That’s a lot of wire in case… Yes but many of today’s fans can accept after-install accessories that upgrade them from simple fans to smart fans. Some accept add-on motion detectors, humidity detector, and even a complete change of grills to transform the ordinary unit in a beautiful light/night light grill configuration like S&P PC50 to 150 CFM units. 

Finally, you are unsure that the fan you have selected and put in your truck to go on the job site is adequate for the job at hand. You get in the install area, make a quick recheck of the CFMs required with that rule of thumb I described and… the room is now larger than anticipated or the owners decided to add a separate shower or spa.

What are you going to do? Install the fan you have that you now know will not meet the needs of the area? Return it to your wholesaler? What a waste of time.

Consider the available alternates that the new DC motor technology has given the forward thinking ventilation manufacturers and your problems are solved.

Some manufacturers now offer a fan like Soler Palau’s PCD110 series that, through a series of selectable switches on the unit, will provide you from 80CFM- 90-110-120 right up to 140 CFMs.The performances will be certified providing you install it with the corresponding 4” or 6” inch duct collar that is provided. I suggest you use a 6’’ preferably for 110CFM and up.The technology even gives you the choice of selecting between one with a humidity sensor or another with a motion detector.

I do hope I have managed to give you more insight into the do’s and don’ts related to the spot ventilation market for bath fans. I am also hopefulthat with this information in mind that you will continue to distinguish yourself as the go-to company, contractor, builder,promoter,architect or engineer for your knowledge, your push for the best, and the best satisfaction experience for the one who will benefit most from that all this care — your end user and customer for a long time to come.


 

Paul Laplante is a manufacturing agent and co-owner of LaplanteRicard& Associates. He has worked in the electrical and ventilation fields for more than 35 years. Milan Jovanovic has worked in the field of mechanical ventilation for a number of years and is a former president of A.S.H.R.A.E.’s Quebec City chapter (2005-2006).

 

Changing Scene

  • Prev
Eleven highly accomplished Hamiltonians are being honoured by Mohawk College as Distinguished ...
Canada’s Minister of Natural Resources recently announced the Governor in Council has ...
ABB recently won an order of eBus charging solutions to support TTC as it modernizes its service ...
A consortium of Canadian energy organizations has been shortlisted to develop the electricity ...
Skills Ontario Summer Camp is a week-long day program for kids entering Grades 7-9.   ...
  Glen Dimplex Americas is proud to announce that its Vancouver facility was recently ...
May 13 to 19 is Powerline Safety Week in Ontario, which is meant to inform people across the ...
Divisional Lighting Manager Salma Siddiqui, the initiative will focus on making Westburne the ...
As of April 30, Natural Resources Canada has new dry-type transformer energy efficiency ...
Ontario Power Generation (OPG), in partnership with the Six Nations of the Grand River Development ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

 

ABB CMD

ABB has appointed Maryrose Sylvester as Country Managing Director (CMD) and Head of Electrification for the United States, effective August 1, 2019.

In the CMD role, she will succeed Greg Scheu, who will support a smooth transition until his retirement at the end of October 31, 2019.

Sylvester was most recently President & CEO of “Current, powered by GE”, a GE startup business that was acquired in April by New York-based private equity firm American Industrial Partners.

 



Read More

 

 

 

 

CyberSecurityDuring a recent Industrial Control Systems Joint Working Group meeting, representatives from the National Electrical Manufacturers Association (NEMA), U.S. Department of Defense (DOD) and International Society of Automation (ISA) outlined a new program to address the growing risk of unprotected and under-protected building control systems in the U.S. and abroad.

Building owners, users, and manufacturers of control systems continuously work to find practical ways to create safe and more secure environments.

 

 

Read More

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

IoTElectrical contractors are approaching a tipping point in terms of pursuing roles and opportunities in the growing market of smart buildings, according to Smart Buildings And Internet of Things (IoT) Impact on Electrical Contracting, a new report from Electri International. Part 1 of this 3-part series provided an overview of the IoT challenges facing electrical contractors; Part 2: opportunities. Here in Part 3: two case studies.

Manitoba Hydro Place 

The first LEED Platinum Certified building in Canada, Manitoba Hydro Place (MHP) is considered the country’s greenest and most energy-efficient building. 

Read More 

Lighting LEEDThe Rivierè-des-Mille-Îles Park encompasses an array of natural forest, waterways, marshland and shoreline in the city of Laval, Quebec. With its exceptional biodiversity, it’s a unique natural attraction for the city, and welcomes over 150,000 visitors annually.

The Exploration Centre is the latest addition to the park and was built as the main visitor welcome area. The pavilion stands out with its modern and avant-garde architecture, and magnificent view of the nearby river.

 


Read more about Lighting Design...

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
Proper illumination to exit a premises during a power failure is critical for safety. Lightheaded's ...
Emerson today introduced the new Appleton ATX FNLED non-metallic, hazardous area linear luminaire ...
Molex launches a Micro Power Distribution Box (µPDB) Sealed Module with two versions: ...
Eureka, a decorative lighting solutions company, recently announced the release of the Lily ...
Audacy Lighting Controls is the easy-to-program mobile app developed to operate your Audacy ...
AEMC's Ground Resistance Tester Model 6472 now includes two additional test voltages of 10 and 60 ...
Following their recent improvements to the IPL series architectural light, First Light Technologies ...
The BoxLED is available in both LED highbay and LED floodlight models. The BoxLED as been ...
Arlington's new cord grips are ideal for solar jobs - and more - requiring the connection of ...
Littelfuse, a global manufacturer of technologies in circuit protection, power control and sensing, ...

 

Fluke Insulated Hand ToolElectricians and facility maintenance technicians should ideally work on de-energized electrical equipment, but that isn’t always possible, so their hand tools should provide as much protection as possible. The new Fluke1000 V Insulated Hand Tools are designed to keep workers safe in hazardous areas and are rugged enough to use in the toughest environments without breaking.

Fluke Insulated Hand Tools are manufactured using state-of-the-art German steel to Fluke’s exacting standards for quality, ruggedness, and reliability. 

 


Read More

 

 

Maxlite TrimaxMaxLite has earned a U.S. patent for the innovative linking design features of its TriMax Vapor Tight fixture. This patent, issued as U.S. Patent No. 10,168,012, brings the number of MaxLite’s issued and pending patents worldwide to 106, a testament to MaxLite’s focus on developing cutting-edge innovation.

The TriMax is engineered with connections at the top of the fixture that maintain a hermetic seal when two or more 4’ fixtures are linked together. By simply snapping a toolless connection bracket into place, installers can uniquely create an IP66 rated lighting solution that is 8’ or longer. 

Read More...

 

Peers & Profiles

  • Prev
Con’s Electric Company Limited was established in 1985. Based in Timmins Ontario, only 700 ...
Mark Unsworth is an electrical engineer with over 35 years of experience in project management, ...
Manygo Ho is an electrical designer with AECOM’s Buildings and Places group. Manygo designs ...
Don Neigel is Manager of the CSA-certified panel shop at Delta, BC’s Optimil Machinery. ...
New Brunswick Power recently struck a deal with Joi Scientific to develop an innovative technology ...
The Shock Doctors is an electrical contracting company operating out of Orillia, Barrie and ...
Michael Gindalang works for Dupar Controls as a panel builder for the elevator and keypad industry. ...
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Matt Stanson is a master electrician with over 30 years of experience. He now leads a team of ...
After eight months, 263 events, 17 broken clocks, and thousands of competitors, Ideal ...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil