Wiring MethodsWilliam (Bill) Burr

The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.In this article: Section 12 — Wiring Methods.

It should be noted that while many other sections of the code are commonly used by designers, installers and regulators, Section 12 is mostly used byelectricians, who must clearly understand all aspects of wiring, and by electrical inspectors, who audit compliance of the wiring methods with the code requirements. Electrical inspection authorities must always be consulted on specific issues related to wiring methods.

Section 12 is a general section and applies to all wiring installations except for
•    Class 2 circuits
•    community antenna distribution and radio and television circuits
•    opticalfibre cables
•    communication circuit conductors
•    conductors integral to factory-built equipment

That is, unless specified in the respective code sections covering those type of installations. We will discuss this later when dealing with Sections 16, 54, 56, and 60in future instalments.

The rules of this section may also be modified by the provisions of Section 32 — Fire alarm systems, Section 36 — High voltage installations or Section 45 — Emergency power supply, unit equipment exit signs and life safety systems.

Section 12 of the Code is divided into six parts:
•    General Requirements
•    Conductors
•    Raceways
•    Cablebus
•    Manufactured wiring systems
•    Installation of boxes, cabinets, outlets and terminal fittings

Generally the definitions in Section 0 apply throughout, but there are some special terminology definitions in the sub-section rules covering flat conductor cable type FCC.

In the General Requirements part, rules 12-010 to 12-020 apply specifically to locations where fire, mechanical, moisture or other environmental issues must be considered or locations where wiring may be prohibited, such as ducts and plenum chambers, underground installations, hoistways, lightning down conductors, entry of raceways and cables into buildings, and wiring under raised floors for data processing.

The Conductors part includes the rules applying to the installation of all types of conductors.It is divided into a general subdivision and individual subdivisions for each type of conductor.

In the General subdivision of Conductors,Rule 12-100 establishes that types of conductors must be chosen for their location with respect to moisture, corrosive action, temperature, degree of enclosure and mechanical protection as set out in Table 19. The Appendix B notes offer additional specifications on choosing the appropriate type of conductor.

Rules 12-102 to 12-120 provide general considerations for the installation of all conductors, such as:
•    the treatment of insulated conductors
•    flame test coverings
•    multi- and single-conductor cables
•    conductors in parallel
•    radii of bends in conductors
•    conductor joints and splices
•    treatment of the ends of insulated conductors
•    termination of conductors
•    termination and splicing of aluminum conductors
•    supporting of conductors

You will find, again, that extensive notes in Appendix B provide additional helpful information, including a diagram outlining configurations for installing parallel conductors.

The rest of the Conductor subdivision deals with the rules for specific types of conductors:
•    open wiring Rules 12-200 to 12-224 apply to single conductors run as open wiring (colloquially referred to as “knob and tube wiring”)
•    exposed wiring on exteriors of buildings and between buildings on the same premises —Rules 12-302 to 12-318
•    barebusbars and risers —Rules 12-400
•    non-metallic-sheathed-cable: Rules 12-500 to 12-526 (NMSC)
•    armoured cable —Rules 12-600 to 12-618
•    mineral-insulated cable, aluminum-sheathed cable, and copper-sheathed cable —Rules 12-700 to 12-716
•    flat conductor cable Type FCC —Rules 12-800 to 12-824

The third part, Raceways, includes the rules applying to the installation of all types of raceways.It is divided into a general subdivision and subdivisions for each type of raceway.

The General subdivision,Rules 12-902 to 12-944, governs the installation of all
•    raceways and conductors run in raceways
•    types of conductors and cable suitable for use in raceways as per Table 19
•    conductors in raceways
•    protection of conductors at the ends of raceways
•    inserting conductors in raceways
•    conductors, in conduit and tubing
•    joints or splices within raceways
•    stranding of conductors, electrical continuity of raceways
•    mechanical continuity of raceways
•    junction of open wiring and raceways
•    entry of underground conduits into buildings
•    raceways installed underground or where moisture may accumulate
•    metal raceways in plaster
•    protection for raceways installed in concrete, cinder concrete, and cinder fill
•    raceways completely installed before conductors are installed
•    capping of unused raceways
•    maximum number of bends in raceways
•    metal raceways embedded in slabs, pavement or roadbeds

The rest of the Raceways part documents the rules for specific types of raceways:
•    rigid and flexible metal conduit:Rules 12-1000 to 12-1014
•    rigid PVC conduit: Rules 12-1100 to 12-1124
•    rigid types EB1 and DB2/ES2 PVC conduit: Rules 12-1150 to 12-1166
•    rigid RTRC conduit: Rules 12-1200 to 12-1220
•    liquid-tight flexible conduit: Rules 12-1300 to 12-1308
•    electrical metallic tubing: Rules 12-1400 to 12-1414
•    electrical non-metallic tubing: Rules 12-1500 to 12-1514
•    surface raceways: Rules 12-1600 to 12-1614
•    underfloor raceways: Rules 12-1700 to 12-1718
•    cellular floors: Rules 12-1800 to 12-1820
•    auxiliary gutters: Rules 12-1900 to 12-1904
•    busways and splitters: Rules 12-2000 to 12-2020
•    wireways: Rules 12-2100 to 12-2112
•    cable trays: Rules 12-2200 to 12-2210

The fourth part, Cablebus, includes the rules applying to the installation of cablebus as a complete system.Rules 12-2252 to 12-2260 include:
•    the use of Cablebus
•    methods of installation
•    connection to other wiring methods
•    provisions for bonding
•    ampacities of conductors in cablebus

The fifth part, Manufactured wiring systems, includes Rules 12-2500 and 12-2502 specifying the uses permitted, and Installation of Manufactured wiring systems

The sixth sub-section, Installations of boxes, cabinets, outlets, and terminals, includes Rules 12-3000 to 12-3036 that cover
•    outlet boxes
•    outlet box covers
•    terminal fittings
•    terminal fittings behind switchboards
•    boxes in concrete construction
•    outlet box supports, boxes, cabinets and fitting supports
•    accessibility of junction boxes, outlet boxes, cabinets and fittings
•    outlet boxes attached to existing plaster work
•    outlet boxes, etc., in damp places
•    entrance of conductors into boxes, cabinets and fittings
•    unused openings in boxes, cabinets, and fittings
•    extensions from existing outlets
•    multi-outlet assemblies
•    conductors in boxes, cabinets or fittings
•    wiring space in enclosures
•    maximum number of conductors in a box,
•    pull box or junction box sizes

 In the next installment we will be discussing Section 14 — Protection and control.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

Read the rest of the instalments in the series:
Part 1: Guide to the CE Code, Part I – A Roadmap (Installment 1 in a Series)
Part 2:
A Road Map to the CE Code, Part I – Installment 2
Part 3: Guide to the Canadian Electrical Code, Part I – Installment 3
Part 4: A Road Map to the CE Code, Part 1 – Installment 4
Part 5: Guide to the Canadian Electrical Code, Part I — Installment 5
Part 6: Guide to the Canadian Electrical Code, Part I — Installment 6
Part 7: Guide to the Canadian Electrical Code, Part I — Installment 7
Part 8: Guide to the Canadian Electrical Code, Part I — Installment 8
Part 9:
Guide to the Canadian Electrical Code, Part I — Installment 9
Part 10: Guide to the Canadian Electrical Code, Part 1 - Installment 10
Part 11: Guide to the Canadian Electrical Code, Part 1 - Installment 11


 

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Changing Scene

  • Prev
Join ESA on Zoom for their first webinar of the fall, Electrically Safe Work ...
Being able to quickly adjust to the unexpected is a big part of any construction project, but solar ...
Rob McKinney will present on "The Eight Steps to Digitize Construction Workflow" during this ...
CE Pro announced the winners of the 2020 CE Pro BEST (Best Electronics Systems Technologies) ...
Nexans Canada has launched a service providing cable reel tracking via connected devices. The ...
The Manitoba government has expanded its Back to Work in Manitoba Wage Subsidy Program as part ...
As part of ESA’s expanding online services, the new Plan Review Portal will provide more options ...
Looking to enhance your business skills as an Electrical Contractor? These courses were designed to ...
Southwire has aquired Construction Electrical Products (CEP) of Livermore, CA. Serving the ...
A century of trust: UL in Canada is celebrating our 100th anniversary! We proudly support the ...


Arlington TVCE Pro announced the winners of the 2020 CE Pro BEST (Best Electronics Systems Technologies) Awards at CEDIA Expo Virtual this week. Arlington is pleased to announce that their Low profile 5x8" Steel TV Box™ (TVL508S) won the CE Pro BEST Award in the Mount Lift Media Concealment category.

 This year’s winning entries were chosen by an independent voting panel of integrators along with the editors of CE Pro.

 

 

 

Read More


 

Connected Drum Internet of Things Nexans Canada has launched a service providing cable reel tracking via connected devices. The “Connected Drum” Internet of Things (IoT) service allows customers to benefit from real-time location, theft and loss detection and management of residual cable lengths on reels. 

By tracking and monitoring a fleet of cable reels that are off-site or at subcontractor locations, significant savings can be realized. The service includes an online and mobile software platform for efficient and convenient management. This innovation provides customers with the real-time location of each reel as well as an alert system for monitoring on-site events including deliveries and pick-ups.

Read More


 

 

ManitobaThe Manitoba government has expanded its Back to Work in Manitoba Wage Subsidy Program as part of its continued commitment to safely restarting the provincial economy.

“The Back to Work wage subsidy is benefiting hundreds of Manitoba businesses that are bringing back employees who were laid off during the COVID-19 pandemic, and hiring more staff to boost their operations and provide valued services to Manitobans,” said Manitoba Premier Brian Pallister. “Manitoba has designed some of Canada’s strongest support programs to help relieve small businesses of unexpected financial burdens...

Read More


 



Terry BeckerBy Terry Becker

We are quickly approaching January 2021 and publication of the 5th edition of the CSA Z462 Workplace electrical safety Standard. This is good news for Canada as we continue to evolve in our identification and management of the electrical hazards of arc flash and shock.

But as I have quoted in the past, we need to ensure we are getting it right, and there is still a lot of work to be done. Most of the focus has been on arc flash and I am concerned that the electric shock hazard has been neglected.

Read More


 

Product News

  • Prev
Harmonious design, superior technology and safe operation merge in °STELPRO’s all-new programmable ...
SmartDC™ fast charging stations are specifically designed to resist vandalism and perform ...
Mersen and F & K DELVOTEC have joined forces to create the optimum battery assembly solution to ...
Lighting Analysts have announced the release of Luxiflux® Area, a web-based exterior lighting ...
EarthTronics architectural grade Lumen & Color Selectable LED Downlight Fixture Series offers ...
The optimally engineered diffuser throws the light downwards exactly where it is required, while ...
The RMHO series of high output remote heads are ideal for applications requiring maximum light ...
RDR Residential Downlights are LED retrofit options to replace legacy downlights in many existing ...
Lightheaded’s Contortionist series features a dual axis so that it can be tilted and rotated with ...


 

EarthTronics LED Downlight FixtureEarthTronics architectural grade Lumen & Color Selectable LED Downlight Fixture Series offers three different color temperature and lumen levels to ensure proper lighting for a variety of new construction and retrofit/renovation applications including wet locations such as soffit and covered walkway installations that are out of direct weather.

Designed for flexibility with a high 90+ CRI for enhanced color clarity, the Lumen & Color Selectable LED Downlight Series is available in 6”, 8” and 9.5” fixtures. The 6” fixture can be switched to 7, 10 or 18 watts to produce 700, 1000 and 1500 lumens, while the 8” fixture can be set at 10, 15 or 22 watts to deliver 1000, 1500 and 2000 lumens. 

Read More


 

Betacalo Soft SQThe optimally engineered diffuser throws the light downwards exactly where it is required, while creating a subtle indirect glow on the ceiling. Ideally suited for atriums, lobbies, boardrooms and reception areas.

Body: Aluminum and steel.

Diffuser: Opal acrylic.

Drivers: HPF electronic for 120-277V (EU-240V)

Remote mounting of drivers: Wire Size (max distance from canopy to drivers) 18 AWG - 9.5' (2.9m), 16 AWG - 19.5' (5.9m), 14 AWG - 29.5' (9m). Drivers must be accessible after installation.  

Read More


 

Peers & Profiles

  • Prev
Today, control systems are penetrating nearly every industry imaginable, and it is no surprise ...
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Dee Durant is an industrial electrician apprentice attending Conestoga College and an Ambassador ...
ECAO recently launched a new program called Future Leaders Advisory Council (FLAC). Their inaugural ...
At 14, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate Institute in ...
Meredith Halfpenny is a Wind Site Technician with Boralex where she inspects, maintains, and ...
Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently ...
Shannon Tymosko is a first-year apprentice with IBEW (International Brotherhood of Electrical ...
ELG Electric is an electrical contractor based out of Goderich, Ontario serving the area’s ...
Founded by Warren Osak, Electromate specializes in Robotic and Mechatronic Solutions, distributing ...

Dee DurantDee Durant is an industrial electrician apprentice attending Conestoga College and an Ambassador for Kick Ass Careers. As an ambassador for KickAss Careers she spent time shadowing mentor and KickAss founder Jamie McMillan attending events for the organization.

The advancement of women in male dominated industries is an important endeavor for Durant, inspired by her mother, who was the first woman on the Brantford Police department. In EIN's interview with Durant, she discussed the future of electrical work, and how the ongoing pandemic is affecting our country’s students.

Read More


 

ECAO's Graeme AitkenBy Blake Marchand

ECAO recently launched a new program called Future Leaders Advisory Council (FLAC), their inaugural meeting was held virtually this past June. Discussing the thought process behind FLAC, ECAO Executive Director, Graeme Aitken explained there were a number of factors that went into the decision.

The program is meant to be a resource for young professionals in the electrical industry for networking, building professional development skills, mentorship, and learning about the inner workings of the industry in general.

 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil