Guide to the Canadian Electrical Code, Part 1[i], 26th Edition – A Road Map: Section 32

April 7, 2025

by William (Bill) Burr[i]

Section 32 – Fire Alarm Systems, Fire Pumps, and Carbon Monoxide Alarms.

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the Code.

32

Section 32, as outlined in rule 32 -000 Scope, is a supplementary or amendatory section of the code and provides additional and specific requirements for the location, installation, wiring, and protection, of fire alarm systems, fire pumps and smoke and carbon monoxide alarms required by the National Building Code of Canada as referenced in Appendix G. For further information, reference should also be made to Canadian Standard CAN/ULC – S524 Standard for the Installation of Fire Alarm Systems published by ULC Canada. Appendix B contains important additional helpful notes, and the CEC Handbook also contains helpful information.

Rule 32-100 specifies the requirements for conductors in fire alarm systems which include copper material, ampacity, use of optical fiber cables, use of stranded conductors, insulation rated at 300 volts, determining wire size for raceways or integral assemblies, and selection in accordance with rules 4-008(1) or 4-020(1).

Rule 32-102 outlines wiring methods for installation of conductors either in metal, non-metallic raceway, or having metal armour or sheath.  Where installed in buildings of combustible construction conductors may be installed in accordance with Section 12.  Conductors need to be installed independent of any other wiring except for point of supply, signal, ancillary device or communication circuits and must be insulated for the highest voltage rated conductor. Communication circuits must conform to Section 60.

Rule 32-104 requires that all exposed non-current-carrying parts of electrical equipment be bonded to ground in accordance with Section 10.  In addition, non-metallic fire alarm wiring systems must incorporate a bonding conductor.

Rule 32-106 denotes that for electrical supervision, each circuit conductor terminal shall be independentlyterminated. 

Rule 32-108 specifies that the fire alarm system power supply, except for included additional control units or transponders, be on a separate circuit and that the overcurrent devices and disconnecting means be permanently identified as a fire alarm system, be coloured red, and lockable in the on position.

Rule 32-110 provides installation requirements for permanently connected smoke alarms and carbon monoxide alarms in dwelling unitsthat are required by the National Building Code of Canada (see Appendix G).  The rule requires that smoke and carbon monoxide alarms be supplied from a circuit that will provide an indication, if shut off, for instance with a lighting or mixed lighting and receptacle circuit with no disconnect, including a GFCI or AFCI device, between the alarms and the branch circuit overcurrent device.  Interconnection of alarms may use a class 2 power supply in accordance with Rules 12-506 to 12-524.

Rule 32-200 requires that conductors for the supply of a fire pump supplied from the emergency power source have an ampacity not less than 125% of the full load current rating of the motor or sum of multiple motors and auxiliary motors and be protected from fire exposure to provide continuing operation during a fire as required by the National Building Code of Canada (see Appendix G)

Rule 32-202 outlines the requirements for wiring methods of fire pumps to be installed in metal raceways, in armour or metal sheathed cable, selected in accordance with Rule 4-888(1), in rigid non-metallic conduit imbedded in concrete, or electrical non-metallic tubing imbedded in concrete.

Rule 32-204 provides that a separate service box for a fire pump and equipment may be installed in conformance with Rule 32-206 below and, notwithstanding Rule 6-102(2), may be located remote from other service boxes.

Rule 32-206 requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box and the fire pump transfer switch or controller, except a circuit breaker that is permanently labeled identifying it as a fire pump disconnect. In addition, the circuit breaker must be lockable in the closed position and may be in the separate service box as in Rule 32-204 above. In the case where this circuit breaker is installed in an emergency power supply circuit between the emergency power source and the fire pump transfer switch the rating of the circuit breaker shall be as per Rule 28-200. Where it is installed in a normal supply circuit the rating should be not less than the overcurrent protection of the fire pump controller.

Rule 32-208 requires that where an on-site electrical transfer switch is used to provide emergency power supply to a fire pump, it must be provided solely for the fire pump, located in a barriered or separate compartment or enclosure, permanently labeled as the fire pump power transfer switch, and approved for fire pump service. Where more than one fire pump is provided, a transfer switch is required for each fire pump.

Rule 32-208 provides that overload and overheating protection for branch circuit, control, or equipment conductors shall not be required but shall be protected by the motor branch circuit overcurrent device.

Rule 32-210 specifies that ground fault protection shall not be installed in a fire pump circuit.

In the next installment, we will be discussing Section 34 – Signs and Outline Lighting.


[i] Source: CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit Store – CSA Group or call 1-800-463-6727. With the permission of CSA Group, the material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit Store – CSA Group or call 1-800-463-6727.

[i] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com..

Related Articles


Latest Articles

  • Nova Scotia Power Introduces Virtual Wiring Inspection for Residential Solar Rough-Ins

    Nova Scotia Power Introduces Virtual Wiring Inspection for Residential Solar Rough-Ins

    August 10, 2026 Nova Scotia continues to experience unprecedented building growth. Together, with the Department of Labour, Skills and Immigration they are exploring risk-based electrical inspections to ensure the process is safe, efficient, and adaptable to the province’s ongoing growth. As solar adoption also continues to grow, Nova Scotia Power wants to improve the interconnection experience for contractors and customers. A virtual… Read More…

  • Webinar Replay: Delta Transformers and Intralec “Powering the Green Grid”

    Webinar Replay: Delta Transformers and Intralec “Powering the Green Grid”

    August 10, 2026 Renewable energy projects are becoming more common and more complex. For distributors and contractors alike, understanding how transformer selection impacts performance, compliance, and installation is increasingly important. In this webinar, Delta Transformers & Intralec break down the role of modern transformers in renewable energy systems, with real-world insight into how they support… Read More…

  • BluWave-ai Along with 4 Ontario Utilities Launch Province-Wide EV and Distribution Grid Load Management AI Project

    BluWave-ai Along with 4 Ontario Utilities Launch Province-Wide EV and Distribution Grid Load Management AI Project

    August 10, 2026 Building on 2.5 years of operationalization of BluWave-ai EV Everywhere™ across Canadian electricity systems, now working with Oshawa Power, Oakville Hydro, Enova Power, and Essex Powerlines in Ontario as the province onboards a projected 500,000 EVs BluWave-ai along with four Ontario utilities announce the launch of a province-wide EV and distribution grid load management… Read More…

  • Prysmian’s $3.8B Atkore Deal would add Quebec Fiberglass-Conduit Plant to Canadian Footprint

    Prysmian’s $3.8B Atkore Deal would add Quebec Fiberglass-Conduit Plant to Canadian Footprint

    August 4, 2026 Prysmian’s proposed US$3.8-billion acquisition of Atkore is primarily a move to deepen the Italian cable manufacturer’s U.S. electrical-products presence, but it also carries a meaningful Canadian angle for the electrical channel. If the transaction closes as expected, Prysmian would add Atkore’s FRE Composites manufacturing operation in Saint-André-d’Argenteuil, Que., near Montréal, to its… Read More…


Changing Scene

  • Munden Munden Enterprises and Lotus LED Lights Partner in Atlantic Canada

    Munden Munden Enterprises and Lotus LED Lights Partner in Atlantic Canada

    August 10, 2026 Munden Enterprises has announced a partnership with Lotus LED Lights as their representative across Atlantic Canada. “Lotus brings patented innovation, clean architectural design, installer friendly solutions, North American warehouse support, and warranty confidence to a lighting category where consistency, availability, and long-term support matter.” Read More…

  • Elec-Tech Sales Ltd. Announce New Partnership with CMP Products in BC

    Elec-Tech Sales Ltd. Announce New Partnership with CMP Products in BC

    August 10, 2026 Elec-Tech Sales Ltd. is excited to announce is new partnership with CMP Products in British Columbia. “We are looking forward to expanding the CMP footprint throughout the province on their comprehensive portfolio of cable glands & cable cleats. Please reach out to our team with any inquiries,” the company said, Read More…

  • Seacliff Electric Welcomes New Project Manager

    Seacliff Electric Welcomes New Project Manager

    August 10, 2026 Seacliff Electric welcomed Clayton Miller to Seacliff Electric as their newest Project Manager in a LinkedIn post. “With more than 20 years of experience in the electrical industry, Clayton brings a wealth of knowledge spanning project management, estimating, and field operations. His extensive background and industry expertise will be a valuable addition… Read More…

  • Nedco’s Newly Renovated Lindsay Branch is Now Open

    Nedco’s Newly Renovated Lindsay Branch is Now Open

    August 10, 2026 The renovated Nedco Lindsay branch is now open and ready to welcome customers, partners and employees. This transformation reflects the work of a dedicated team who carried the project from planning to completion. “The leadership of Marleah Richards as Branch Manager played a key role throughout the renovation and helped bring the… Read More…