Electri-Flex Flexible Liquid-Tight Steel Conduit
February 10, 2020
This flexible liquidtight steel conduit is certified by the Canadian Standards Association for “Heavy-Duty” applications. Its design and function is similar to that of type LA, except that it cannot be used as a ground return path per the Canadian code.
Construction:
Inner Core:
- – Hot Dipped Galvanized Steel
- – 3/8” – 1-1/4” Squarelock Profile with continuous cord packing
- – 1-1/2” – 4” Fully Interlocked Profile
Liquidtight Jacket:
- – Flexible PVC
- – Resistant to Oils and Mild Acids
- – FT-4 Flame Retardant
- – Sunlight Resistant (UV)
- – Marked HD for “Heavy-Duty”
APPLICATION:
This conduit is intended for use according to the Canadian Electrical Code (CEC CSA 22.1-18) as described in clause 12-1300 for dry, damp or wet locations.
- – Conforms to CSA C22.2 No. 56-17 Annex A “Heavy Duty”
Hazardous Locations areas where flexibility is necessary:
- – Class I Div 2: CSA 22.1 J18-152 (1) (i)
- – Class II Div 1: CSA 22.1 J18-204 (4) (b)
- – Class II Div 2: CSA 22.1 J18-254 (1) (h)
- – Class III Div 1: CSA 22.1 J18-304 (1) (f)
- – Class III Div 2: CSA 22.1 J18-354 (h)
- – Zone 2: CSA 22.1 18-152 (1) (h)
- – Zone 20: CSA 22.1 18-192 (3) (a)
- – Zone 21: CSA 22.1 18-202 (4) (a)
- – Zone 22: CSA 22.1 18-252 (1) (h)
Go HERE for more information.